Watts LF007M2-QT

Watts LF007M2-QT Double Check Valve Assembly, 1 1/2 Inch Instruction Manual

Model: LF007M2-QT

1. Produk Langkungview

The Watts LF007M2-QT 1 1/2" Lead Free Double Check Valve Assembly is engineered to prevent the backflow of polluted water from entering the potable water supply. This is crucial for protecting against back siphonage and backpressure, adhering to national plumbing codes and water authority requirements. Its design emphasizes ease of maintenance with a compact, modular structure and a single access cover for in-line repairs. It is ideally suited for continuous pressure piping applications and cross-connections identified as non-health hazards, as well as for controlling contaminants at the service line entrance.

Watts LF007M2-QT Double Check Valve Assembly

Image: Watts LF007M2-QT Double Check Valve Assembly, showing the main body, shutoff valves, and test cocks.

Produk Leuwihview Video (Similar Product Type)

Video: An animated overview of a Bronze Double Check Valve Backflow Preventer Assembly, highlighting its features and typical installation in a residential setting. This video provides a general understanding of double check valve assemblies.

Produk Leuwihview Video (Related Series)

Video: Hiji leuwihview of the Watts Series LF825Y Reduced Pressure Zone Assembly. While a different model, it demonstrates the general principles and applications of Watts backflow prevention devices.

2. Fitur

  • Lead-Free Bronze Construction: Ensures durability and compliance with lead-free regulations.
  • Replaceable Check Seats and Discs: Allows for economical repairs and extended product life.
  • Modular Compact Design: Facilitates easy installation and maintenance without requiring special tools.
  • One Cover Design: Simplifies maintenance procedures.
  • Top-Mounted Test Cocks: Provides convenient access for testing and servicing.
Watts LF007M2-QT Double Check Valve Assembly with quarter-turn shutoffs

Gambar: Hiji sisi view of the Watts LF007M2-QT Double Check Valve Assembly, highlighting the quarter-turn shutoff valves and compact design.

3. Spésifikasi

BahanPerunggu
Ukuran barang (L x W x H)17.88 x 9.5 x 7.25 inci
Ukuran Sambungan Inlet1.5 inci
Tipe Sambungan InletNational Pipe Tapered (NPT)
Ukuran Sambungan Outlet1.5 inci
Tipe Sambungan OutletNPT
Jumlah Palabuhan2
Spesifikasi MetASSE 1013, NSF/ANSI 372, RoHS, EPA
Item Beurat6.72 pon
Watts LF007M2-QT Double Check Valve Assembly full view

Gambar: A komprehensif view of the Watts LF007M2-QT Double Check Valve Assembly, showcasing its full dimensions and components.

4. Instalasi jeung Setup

Always consult local building and plumbing codes prior to installation. If this information is not consistent with local building codes, the local codes should be followed. It is important that the assembly be easily accessible to facilitate testing and servicing. A properly-sized drain line and air gap should be piped from the relief valve connection of the assembly. In areas where freezing conditions occur, backflow preventers should be installed above ground in an insulated enclosure. Backflow preventers should not be installed in pits unless approved by local codes. In such cases, a modified pit installation is preferred.

Watts LF007M2-QT Double Check Valve Assembly side view

Gambar: Hiji sisi view of the Watts LF007M2-QT Double Check Valve Assembly, illustrating its connection points for installation.

5. Parentah Operasi

The Watts LF007M2-QT Double Check Valve Assembly is designed for continuous pressure piping applications. Once properly installed and tested, the device operates automatically to prevent backflow. Regular testing by a certified backflow prevention device tester is required to ensure proper operation and compliance with local regulations.

Watts LF007M2-QT Double Check Valve Assembly top view

Gambar: Puncak view of the Watts LF007M2-QT Double Check Valve Assembly, showing the access cover and test cocks.

6. Pangropéa sarta ngungkulan

This section addresses the inspection and repair of backflow prevention assemblies. Before beginning any work, please familiarize yourself with these procedures to avoid harming yourself or damaging the valve. These instructions, as well as specification sheets, repair kit ordering information, and additional product resources can be found online at watts.com.

Common Issues and Initial Checks

Two common issues you may encounter are an assembly that spits water from the relief valve vent periodically, or an assembly that drips continually from the relief valve vent. No special tools are required for initial troubleshooting; only a standard screwdriver is needed.

  1. Continuous Dripping from Relief Valve:
    • Close shut-off valve number 2.
    • If the drip stops, it indicates a fouled second check with a backpressure condition.
    • If the drip does not stop, open test cock number 4 to create a downstream flow.
    • If the discharge of water from the relief valve vent becomes less or stops, it most likely indicates a fouled first check.
    • If the discharge of water from the relief valve vent does not stop with shut-off valve number 2 closed and test cock number 4 opened completely, it's most likely the relief valve. On occasion, it may be both a fouled first check and a relief valve issue.

Servicing the Assembly

To service the assembly, follow these steps:

  1. Close shut-off valve number 1.
  2. Close shut-off valve number 2 (it may already be closed if you just performed troubleshooting).
  3. Relieve pressure by opening test cock number 2, test cock number 3, and test cock number 4.
  4. Once all pressure is relieved, remove the valve cover bolts.
  5. Lift the cover straight off. The relief valve stem and diaphragm assembly will normally remain with the cover.
  6. Remove the relief valve spring (it will be free inside the body).
  7. Remove the retainer.
  8. Remove check valve number 2 and check valve number 1.
  9. Remove the relief valve seat.

Inspection and Reassembly

  1. Inspect the seat for any imperfections on its surface. Replace if necessary.
  2. On the disc assembly, check the rubber for any imperfections, tears, rips, or buried debris. Clean or replace as necessary. Use a small screwdriver to remove the silicone disc from the holder for inspection.
  3. Before reassembling, inspect the spring cage to ensure it's in good shape and that the disc holder moves freely.
  4. Reassemble the components. Note that the check seats are attached to the cage with a bayonet-type locking arrangement. Hold the cage in one hand, push the seat inward against the cage, and rotate 1/8 of a turn clockwise (for 1/4" to 2" valves) or counterclockwise (for 2 1/2" and 3" valves) to release/secure components.
  5. Before installing check assemblies, apply an FDA-approved lubricant sparingly to the O-rings.
  6. Reinstall check valve number 1 and check valve number 2. Note that the seats and springs of the two checks are not interchangeable; ensure they are returned to their correct locations for proper function.
  7. Reinstall the retainer.
  8. Reinstall the spring.
  9. Reinstall the relief valve with the cover. Press down on the cover and reinstall the cover bolts.
  10. Once reassembly is complete, refer to the installation start-up procedure to return the valve assembly to service.

Troubleshooting and Service Video (Related Series)

Video: This video demonstrates troubleshooting and service procedures for the Watts LF009 Reduced Pressure Zone Assembly. While the model differs, the general steps for identifying and resolving common issues like relief valve spitting or dripping, and the process for disassembling, inspecting, and reassembling internal components, are applicable to many Watts backflow preventers, including double check valve assemblies.

7. Émbaran jaminan

For detailed warranty information, please refer to the official Watts product warranty documentation included with your purchase or visit the Watts website. General warranty terms typically cover manufacturing defects under normal use and service conditions.

8. Rojongan Palanggan

For technical assistance, replacement parts, or further inquiries, please contact Watts customer support. You can find contact information on the official Watts websitus atawa dina dokuméntasi disadiakeun kalawan produk Anjeun.

Watt Websitus: www.watts.com

Dokumén Patali - LF007M2-QT

Praview Watts Series 709, LF709, 709DCDA Double Check Valve Assemblies: Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 709, LF709, and 709DCDA Double Check Valve Assemblies and Double Check Detector Assemblies, covering sizes 2½" to 10". Includes installation guidelines, servicing procedures, troubleshooting, and information on add-on monitoring kits.
Praview Watts Series 757, 757DCDA, LF757DCDA Double Check Valve Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for installing, maintaining, and repairing Watts Series 757, 757DCDA, and LF757DCDA Double Check Valve and Detector Assemblies, covering procedures, troubleshooting, and warranty information.
Praview Kit GBS Katup Cek Ganda Baja Tahan Karat Watts (007-SS-GBS) - Data Téknis
Spésifikasi téknis, kode produk, diménsi, sareng fitur pikeun Katup Pariksa Ganda Baja Tahan Karat Watts 007-SS-GBS kalayan Katup Kupu-kupu Gir sareng Saringan. Dirancang pikeun pencegahan aliran balik dina pamasangan bahaya sedeng sareng rendah.
Praview Watts Series LF909 Reduced Pressure Zone Assemblies - Technical Specification
Detailed technical specifications for Watts Series LF909 Reduced Pressure Zone Assemblies, including features, operation, dimensions, weights, and capacity. Designed for potable water cross-connection control.
Praview Rakitan Zona Tekanan Ngurangan Watts Series LF919: Manual Pamasangan, Pangropéa, sareng Perbaikan
Pituduh lengkep pikeun masang, ngajaga, sareng ngalereskeun Watts Series LF919 Reduced Pressure Zone Assembly (1/2" - 2"). Ngawengku peringatan kaamanan, prosedur pamasangan, pitunjuk servis, sareng ngungkulan masalah.
Praview Rakitan Pemutus Vakum Tekanan Watts Series 800M4, LF800M4: Manual Pemasangan, Perawatan, sareng Perbaikan
Pituduh lengkep pikeun masang, ngajaga, sareng ngalereskeun Rakitan Pemutus Vakum Tekanan Watts Series 800M4 sareng LF800M4. Ngawengku kaamanan, prosedur pamasangan, perawatan, panyalindungan tina beku, sareng garansi.