This manual provides detailed instructions for the installation, operation, and maintenance of the Beckett BK171UL Condensate Pump. This pump is designed for automatic removal of condensate from HVAC equipment, including air conditioners, furnaces, boilers, dehumidifiers, and high-efficiency oil or gas-fired furnaces. It is suitable for condensate water temperatures up to 150°F and acidic condensate.

Beckett BK171UL Condensate Pump

Image 1.1: Beckett BK171UL Condensate Pump, front view.

2. Émbaran Kasalametan

PERHATOSAN: Résiko Sengatan Listrik. Cabut daya sateuacan diservis.

  • Baca sagala parentah taliti saméméh instalasi tur operasi.
  • Pastikeun catu daya cocog sareng vol pompatage (115V).
  • Entong ngoperasikeun pompa nganggo kabel atanapi colokan anu rusak.
  • Ulah ngalelepkeun pompa kana cai.
  • Pompa ieu dirancang kanggo dianggo di jero ruangan hungkul.
  • Tetep leungeun bersih tina bagian nu pindah salila operasi.
  • Mastikeun grounding ditangtoskeun sakumaha per kode listrik lokal.
  • The pump is equipped with a safety switch. Ensure it is correctly wired to prevent overflow.

3. Eusi Paket

Pariksa yén sadaya komponén aya sateuacan ngamimitian pamasangan:

  • Beckett BK171UL Condensate Pump unit
  • 3/8" O.D. barbed check valve
  • Integrated 6-ft grounded power cord
  • Manual Pitunjuk (dokumén ieu)
Ngabeledug view of Beckett BK171UL Condensate Pump components

Gambar 3.1: Ngabeledug view showing pump components including cover, check valve, motor, fan, automatic switches, lift-to-test tab, bullseye level, floats, impeller, multi-slot metal mount tabs, 6 ft. grounded power cord, and collection tank.

4. Instalasi jeung Setup

4.1 Pasang Pompa

The pump features stainless steel multi-slot mounting tabs for secure installation. Ensure the pump is placed on a level surface. Use the integrated bullseye level on the lid to confirm proper horizontal alignment.

Beckett BK171UL Condensate Pump installation features

Image 4.1: Close-up of pump showing bullseye level, twist lock check valve, and lift-to-test tab for easy installation and maintenance.

4.2 Condensate Inlet Connections

The pump is equipped with four 1-1/8-inch diameter inlet holes for connecting condensate drain lines from your HVAC equipment. Connect the drain line(s) to any available inlet(s).

4.3 Sambungan Saluran Pembuangan

Connect a 3/8" I.D. vinyl tubing (not included) to the 3/8" O.D. barbed check valve. The check valve twists to lock into place on the pump, preventing backflow of discharged water. Route the discharge line to an appropriate drain, ensuring it has a continuous downward slope and is free from kinks or obstructions. The pump can lift water up to 17 feet vertically.

4.4 Sambungan Listrik

Plug the 6-ft grounded power cord into a standard 115V electrical outlet. Ensure the outlet is properly grounded and protected by a ground fault circuit interrupter (GFCI) if required by local codes.

4.5 Safety Switch Wiring

The integrated safety switch is designed to shut down the HVAC equipment or trigger an alarm in case of a pump malfunction or high water level, preventing overflow. Consult your HVAC equipment manual for proper wiring of the safety switch. Typically, the safety switch wires are connected in series with the low-voltage thermostat circuit of the HVAC unit.

5. Operasi

5.1 Automatic On/Off Operation

The Beckett BK171UL pump operates automatically. When condensate water in the collection tank reaches a predetermined level, the pump will activate, remove the water, and then shut off once the water level drops. This automatic cycle ensures efficient condensate removal without constant monitoring.

Beckett BK171UL Condensate Pump performance chart

Image 5.1: Diagram illustrating automatic ON/OFF operation and average performance at various lift heights (e.g., 95 GPH at 5 ft lift, 64 GPH at 10 ft lift, 17 ft shut-off).

5.2 Lift-to-Test Function

A "lift-to-test" tab is provided on the pump lid. Lifting this tab manually raises the float, simulating a high water level and activating the pump. This feature allows for quick testing of the pump's functionality and can also be used to drain the tank for servicing.

6. Pangropéa

Pangropéa rutin mastikeun kinerja anu optimal sareng manjangkeun umur pompa kondensat anjeun.

  • Inspeksi Bulanan: Visually inspect the pump, inlet, and discharge lines for any blockages, leaks, or damage. Ensure the discharge line is free of kinks.
  • Beberesih Triwulanan:
    1. Disconnect power to the pump and the HVAC unit.
    2. Use the lift-to-test tab to drain the tank, or manually remove any remaining water.
    3. Carefully remove the pump cover.
    4. Clean the collection tank, floats, and impeller area to remove any sludge, debris, or mineral deposits. A mild detergent and soft brush can be used.
    5. Bilas sadaya komponén sacara saksama ku cai bersih.
    6. Reassemble the pump, ensuring the cover is securely in place.
    7. Reconnect power and test the pump using the lift-to-test tab.
  • Jalur Discharge: Periodically check the discharge line for algae or mineral buildup, especially if the pump is handling acidic condensate. Clean or replace the tubing as necessary.

7. Cara ngungkulan

MasalahMungkin Cukang lantarananaSolusi
Pompa henteu lumpatHenteu aya kakuatan pikeun pompaCheck power cord connection, circuit breaker, and GFCI.
Float switch stuck or obstructedDisconnect power, remove cover, clean floats and tank.
Pump runs but does not discharge waterDischarge line clogged or kinkedInspect and clear the discharge line. Ensure no kinks.
Check valve obstructedDisconnect power, remove and clean the check valve.
Impeller mampetDisconnect power, remove cover, clean impeller area.
Pompa ngalir terusFloat switch stuck in "on" positionDisconnect power, remove cover, clean floats and tank.
Leak in discharge line or check valveInspect all connections and the discharge line for leaks. Tighten or replace as needed.
Pompa ributDebris in impeller or motorDisconnect power, remove cover, clean impeller area.
Pump not levelAdjust pump placement using the bullseye level.

8. Spésifikasi

  • model: BK171UL
  • Voltage: 115V
  • Angkat Maksimum: 17 ft
  • Laju aliran: 112 GPH @ 1 ft lift
  • Amperage: 1.1 Amps
  • Wattage: 60 Watt
  • Frékuénsi: 60 HZ
  • Kapasitas Tangki Koléksi: 2.5 Kwartir
  • Sambungan Discharge: 3/8" O.D. barbed check valve
  • Sambungan Inlet: Four 1-1/8" diameter holes
  • Kabel listrik: 6 ft grounded with plug
  • Maximum Condensate Water Temperature: 150°F
  • Bahan: Acrylonitrile Butadiene Styrene (ABS), Plastik
  • Ukuran (L x W x H): 11.2" x 5.2" x 6.6"
  • Beurat barang: 3.7 pon
  • Fitur kaamanan: Integrated safety switch, Thermally protected motor
  • Sertifikasi: UL/cUL listed in U.S./Canada
Beckett BK171UL Condensate Pump dimensions

Image 8.1: Dimensions of the Beckett BK171UL Condensate Pump.

9. Garansi jeung Rojongan

The Beckett BK171UL Condensate Pump comes with a 3-taun jaminan produsén. For warranty claims, technical assistance, or replacement parts, please contact Beckett Corporation customer support. Keep your purchase receipt as proof of purchase.

For further assistance, please refer to the official Beckett Corporation websitus atanapi ngahubungan departemén layanan palanggan maranéhna.

Dokumén Patali - BK171UL

Praview Beckett CB22 pompa condensate otomatis: instalasi, operasi & Manual Kasalametan
Pamilik komprehensif manual pikeun Beckett CB22 Unit Condensate Otomatis. Ngawengku parentah lengkep pikeun instalasi, operasi aman, wiring, pangropéa, ngungkulan, sarta informasi jaminan kawates.
Praview Beckett BK17 / BK22 Condensate Lengser Pompa Instalasi jeung Guide pangropéa
Pituduh ieu nyadiakeun rinci instalasi, pangropéa, jeung parentah kaamanan pikeun Beckett BK17 na BK22 condensate pompa ngaleupaskeun, kaasup informasi jaminan na spésifikasi kinerja.
Praview Beckett Automatic Condensate Removal Pump Installation and Operation Manual
This manual provides comprehensive installation, operation, wiring, testing, and troubleshooting guidance for Beckett Automatic Condensate Removal Pumps, including models CL201UL, CL202UL, CL202ULHT, and CL202CE. It details warranty information and maintenance procedures.
Praview Beckett AquaSmart 7600 Boiler Control Quick Reference Guide
A concise quick reference guide for the Beckett AquaSmart 7600 Series boiler control, covering technical specifications, installation, basic programming, and wiring diagrams, along with warranty information.
Praview Beckett PowerLight 24Vdc Igniter Installation Instructions
Comprehensive installation guide for the Beckett PowerLight 24Vdc Igniter. This document provides essential application information, detailed specifications, critical safety warnings, and step-by-step instructions for models 5272001U, 5272002U, and 5272005U, ensuring proper setup for oil burner systems.
Praview Beckett AquaSmart Modél 7600 Advanced Boiler Control Instalasi jeung Manual Operasi
Pituduh komprehensif pikeun sistem kontrol boiler Beckett AquaSmart Model 7600, ngawengku pamasangan, wiring, program, fitur kawas HeatManager™, jeung ngungkulan pikeun aplikasi komérsial padumukan jeung lampu.