This manual provides essential information for the safe and effective use of the GE SELA36AT0150 Bolt-On Mount Type SEL Molded Case Circuit Breaker. This current-limiting circuit breaker is designed for industrial and commercial applications, providing protection against overcurrents and short circuits.
fitur konci ngawengku:
- Current Limiting Circuit Breaker: Designed to limit the magnitude and duration of short-circuit currents.
- 150 Amps Max | 150 A Rating Plug: Configured for a maximum current of 150 Amps with a corresponding rating plug.
- 3 Pole, 480/600 VAC: Suitable for three-phase alternating current systems up to 600 Volts.
- Spectra RMS Series: Part of the GE Spectra RMS line, known for advanced protection features.
- Pemasangan Baut: Designed for secure bolt-on installation.

Gambar 1: Hareupeun view of the GE SELA36AT0150 Circuit Breaker, showing the ON/OFF switch and product labels.
2. Émbaran Kasalametan
PERHATOSAN: Installation, maintenance, and troubleshooting of electrical equipment should only be performed by qualified and licensed electricians. Failure to follow these instructions can result in serious injury, death, or property damage.
- Always disconnect power before working on electrical circuits or equipment.
- Anggo alat pelindung pribadi (PPE) anu pas, kalebet sarung tangan insulasi sareng panyalindungan panon.
- Verify all connections are secure and properly torqued according to specifications.
- Ensure the circuit breaker's ratings match the system requirements.
3. Setup jeung Instalasi
The GE SELA36AT0150 is a bolt-on mount circuit breaker. Proper installation is crucial for safe and reliable operation.
3.1 Cék Pra-Pamasangan
- Confirm the circuit breaker's voltage, current, and interrupting ratings are compatible with the electrical system.
- Pariksa pemutus sirkuit pikeun karusakan fisik. Ulah masang unit ruksak.
- Pastikeun permukaan pamasangan bersih, garing, sareng kuat sacara struktural.
3.2 Pamasangan Parentah
- De-energize the electrical panel or system where the breaker will be installed. Verify zero voltage kalayan multimeter.
- Position the circuit breaker in the designated slot or mounting location.
- Secure the breaker using appropriate bolts and hardware for bolt-on mounting. Ensure it is firmly seated.
- Connect the load and line conductors to the appropriate terminals. The breaker includes a set of bottom lugs.
- Refer to the product label for specific wire ranges and torque specifications:
- Wire Range: #12 - 3/0 CU, #12 - 3/0 AL
- Torque: #12-#10: 35 lb-in, #8-#3: 100 lb-in, #2-3/0: 150 lb-in
- Double-check all connections for tightness and proper insulation.

Figure 2: Close-up of the circuit breaker's main label, detailing Cat No., Amp rating, Voltage, Pole configuration, Rating Plug Type, Lug Data, Wire Range, and Torque specifications.

Figure 3: Close-up of the circuit breaker's interrupting rating label, showing RMS Symmetrical Amps at various voltages (240V, 480V, 600V) and international standards.

Gambar 4: Tukangeun view of the GE SELA36AT0150 Circuit Breaker, showing the bolt-on mounting points and terminal connections.
4. Parentah Operasi
The GE SELA36AT0150 circuit breaker is designed for simple operation, primarily acting as an ON/OFF switch and an automatic protective device.
4.1 Hurungkeun / Pareum
- Pikeun ngahurungkeun sirkuit ON, firmly push the handle to the "ON" position.
- Pikeun ngahurungkeun sirkuit Pareum, firmly push the handle to the "OFF" position.
4.2 Tripping and Resetting
If an overcurrent or short circuit condition occurs, the breaker will automatically "trip" to the center position (between ON and OFF) to protect the circuit. To reset a tripped breaker:
- First, move the handle completely to the "OFF" position. This resets the internal mechanism.
- Investigate and resolve the cause of the trip (e.g., overloaded circuit, short circuit).
- Once the issue is resolved, firmly push the handle to the "ON" position to restore power.
- If the breaker immediately trips again, do not attempt to reset it repeatedly. Consult a qualified electrician.
5. Pangropéa
Circuit breakers generally require minimal maintenance. However, periodic inspection is recommended to ensure continued safe operation.
- Inspeksi Visual: Unggal taun mariksa breaker pikeun tanda karuksakan fisik, discoloration, atawa sambungan leupas.
- beberesih: Keep the area around the breaker clean and free of dust and debris. Use a dry, non-conductive cloth for cleaning. Do not use liquids.
- Cék sambungan: Periodically (e.g., every 3-5 years, or as per local codes) have a qualified electrician check the tightness of terminal connections.
- Uji coba: For critical applications, periodic testing of the breaker's trip mechanism by a qualified professional may be required.
Catetan: Do not attempt to open or repair the circuit breaker. There are no user-serviceable parts inside.
6. Cara ngungkulan
Bagian ieu alamat masalah umum Anjeun bisa sapatemon kalawan circuit breaker Anjeun.
| Masalah | Mungkin Cukang lantaranana | Solusi |
|---|---|---|
| Breaker lalampahan sering. | Sirkuit kaleuleuwihan, sirkuit pondok, sesar taneuh, atanapi alat anu lepat. | Ngurangan beban dina sirkuit. Cabut parabot. Mariksa kabel pikeun karuksakan. Upami masalah tetep, konsultasi ka tukang listrik anu mumpuni. |
| Breaker moal ngareset. | Persistent fault (short circuit/overload) or internal breaker damage. | Ensure the handle is pushed fully to "OFF" before attempting to reset. If it still won't reset, do not force it. Call a qualified electrician. |
| Taya kakuatan pikeun sirkuit, tapi breaker ON. | Loose connection, wiring issue, or internal breaker failure. | This indicates a serious issue. Immediately turn off the breaker and consult a qualified electrician. Do not attempt to diagnose or fix yourself. |
For any issues not covered here, or if troubleshooting steps do not resolve the problem, always contact a qualified and licensed electrician.
7. Spésifikasi
Detailed technical specifications for the GE SELA36AT0150 Circuit Breaker:
| Atribut | Nilai |
|---|---|
| Nomer modél | SELA36AT0150 |
| merek | Umum Éléktronik |
| Peunteun ayeuna | 150 Amps |
| Voltage Peunteun | 480 / 600 VAC |
| Jumlah kutub | 3 |
| Sirkuit Tipe Breaker | Standard, Current Limiting, Molded Case |
| Tipe Pamasangan | Bolt-Di Gunung |
| Interrupting Rating @ 240 VAC | 100,000 Amps |
| Interrupting Rating @ 480 VAC | 65,000 Amps |
| Interrupting Rating @ 600 VAC | 25,000 Amps |
| Rating Plug Type | SRPE150A |
| Rating Plug Inst. Adjustable Range | 450-1991 A (Lo to Hi) |
| Ukuran produk (D x W x H) | 4" x 4" x 6.5" (kira-kira) |
| Beurat | 4.8 lbs (kira-kira) |
| Tanggal Kahiji Sadia | 11 Oktober 2012 |
8. Garansi jeung Rojongan
For specific warranty information regarding your GE SELA36AT0150 Circuit Breaker, please refer to the documentation provided at the time of purchase or contact General Electric directly. As a general guideline, electrical components typically come with a manufacturer's warranty covering defects in materials and workmanship.
For technical support, service, or to inquire about replacement parts, please contact General Electric customer service or visit their official websitus. Anjeun oge bisa nganjang ka Toko GE di Amazon for more information on GE products.
Always ensure that any work on electrical systems is performed by qualified and licensed professionals.
9. Video Produk Resmi
No official product videos from the seller were found for this specific model in the provided data. For general product information or installation guides, please check the manufacturer's official websitus atanapi distributor otorisasi.