ACREL ACR10R-D36TE4

Acrel ACR10R KWh 3 Phase Energy Meter Instruction Manual

Model: ACR10R-D36TE4 | Brand: ACREL

1. Bubuka

The Acrel ACR10R KWh 3 Phase Energy Meter is designed for bidirectional energy monitoring, particularly suitable for solar power applications. It accurately measures active and reactive power, current, voltage, frequency, and power factor in three-phase systems. This meter supports communication via RS485 (MODBUS-RTU) and can be paired with external split-core current transformers (CTs) or Rogowski coils for flexible installation. Its compact design allows for 35mm DIN rail mounting, making it ideal for energy-saving renovation projects and power monitoring in distributed photovoltaic grid-connected systems.

Acrel ACR10R Energy Meter with three split-core current transformers
Figure 1: Acrel ACR10R Energy Meter with three split-core current transformers.

2. Fitur Produk

  • Kamampuhan pangukuran: Measures 3-phase active power, reactive power, current, voltage, frékuénsi, jeung faktor daya.
  • Current Rating Options: Supports various current ratings up to 300A with external split-core CTs (10mm/80A, 16mm/120A, 24mm/200A, 36mm/300A) or up to 20000A with Rogowski coils.
  • Komunikasi: RS485 interface with MODBUS-RTU protocol for data exchange.
  • Aplikasi: Ideal for distributed solar PV systems and anti-reflux inverter applications.
  • tampilan: Clear LCD for parameter display and programming.
  • Pamasangan: Designed for easy 35mm DIN rail mounting.
  • Sasayogian tanaga: Wide range AC (85~265V) or DC (100~350V) power supply.
  • Sertifikasi: Certified CE.
  • Fungsi Pilihan: Harmonic Monitoring.
  • Bidirectional Metering: Supports both active and reactive energy metering.
  • Keypad HMI: Integrated keypads for parameter display setting and communication configuration.
Key features of the ACR10R energy meter
Gambar 2: Leuwihview of ACR10R Energy Meter features.

3. Spésifikasi

KategoriParameterRincian
UmumNomer modélACR10R-D36TE4
Diménsi85 * 64 * 54 mm
PangukuranNet Work3-fase 3-kawat, 3-fase 4-kawat
Frékuénsi45~65Hz
Dipeunteun VoltageAC 57.7V/100V (100V), 220V/380V (400V)
Max Operasi Ayeuna150A & Above (up to 300A with CTs, 20000A with Rogowski Coil)
Ngukur Rentang Énergi0-99999.9kwh
Parameter pangukuranU, I, P, Q, S, PF, F (Voltage, Current, Active Power, Reactive Power, Apparent Power, Power Factor, Frequency)
AkurasiKelas akurasi1
Ketepatan Frékuénsi0.05Hz
KakuatanSasayogian tanagaAC 85~265V or DC 100~350V; DC 24V(±10%); DC 48V(±10%)
Konsumsi10VA
Batré KaasupSumuhun
KomunikasiPanganteurRS485
ProtokolMODBUS-RTU
tampilanTipeLCD
Modeu tampilanField LCD
LingkunganSuhu Operasi-10 ℃ ~ 55 ℃
Suhu Panyimpenan-20 ℃ ~ 70 ℃
Kalembaban rélatif5% ~ 95% (Euweuh kondensasi)
KasalametanKakuatan-frékuénsi tahan voltageAC2kV/1min (Auxiliary power, switch volume output, current input, voltage input, communication, pulse output, switch volume input)
Résistansi insulasi>100MΩ (Input, Output terminal to housing)
Dimensional drawing of the Acrel ACR10R energy meter
Figure 3: Dimensional drawing of the ACR10R Energy Meter.

4. Eusi Paket

The standard package for the ACR10R Energy Meter includes:

  • 1 x Acrel ACR10R 3 Phase Energy Meter
  • 3 x External Split-Core Current Transformers (CTs) - Specific current rating depends on the selected model (e.g., 80A, 120A, 200A, 300A)
  • Manual pangguna (dokumén ieu)
Acrel ACR10R Energy Meter and three split-core current transformers
Figure 4: Contents of the ACR10R package.

5. Setup & Instalasi

5.1. DIN Rail Installation

  1. Push off the buckle on the back side of the meter.
  2. Install the meter onto a 35mm DIN rail by aligning the slot behind the meter with the rail.
  3. Buckle up the meter to fix it securely on the DIN rail.
  4. Ensure the meter is successfully installed and stable.
Steps for DIN rail installation of the energy meter
Figure 5: DIN Rail Installation Steps.

5.2. Current Transformer (CT) Installation

The ACR10R meter can be paired with either split-core CTs or Rogowski coils. Ensure correct polarity and secure connection for accurate measurements.

  • Split Core CT Installation: Open the CT, place the conductor through the center, and close it securely. Ensure the direction of current flow matches the CT's arrow for correct measurement.
  • Rogowski Coil Installation: Wrap the Rogowski coil around the conductor.
External CT dimensions and installation of split core CT and Rogowski coil
Figure 6: External CT dimensions and installation methods.

Video 1: Demonstration of energy meter and Rogowski coils.

6. Diagram Kabel

Proper wiring is critical for the safe and accurate operation of the ACR10R energy meter. Refer to the following diagrams for common configurations.

6.1. General System Connection

Diagram showing solar panel, inverter, reflux monitoring meter, and grid connection
Figure 7: General system diagram for solar PV monitoring.

6.2. Detailed Wiring for 3-Phase Systems

Detailed wiring diagram for 3-phase, 4-wire 3CT, 3PT, 2CT, accessory power, and RS485 communication
Figure 8: Detailed wiring diagram for various 3-phase configurations, accessory power, and RS485 communication. Note: For CT secondary side short connection, ensure proper terminal connection. The fuse in the wiring diagram is recommended 0.5A or 3A. When the instrument is installed on site, it must correspond to the supporting open and closed transformer or Rogowski coil one by one, otherwise the measurement accuracy will be affected, and the connection between the two must be reliable.

6.3. Bidirectional Metering Diagram

Diagram illustrating bidirectional metering (power consumption vs. redundant power generation)
Figure 9: Bidirectional metering concept showing power consumption and redundant power generation.

6.4. Distributed Solar PV Application Diagram

Diagram of a house with solar panels and energy meter setup
Gambar 10: Kelample of ACR10R integration in a distributed solar PV system.

7. Parentah Operasi

The ACR10R meter features an LCD display and keypad HMI for user interaction.

7.1. LCD Paparan

The LCD provides real-time readings of various electrical parameters such as voltage, current, power, frequency, and energy consumption. It also serves as the interface for programming and configuration.

Close-up of the LCD display on the energy meter
Figure 11: LCD Display for parameter viewing.

7.2. Keypad HMI

Use the integrated keypads (FN, Set, and arrow buttons) to navigate through menus, view different parameters, and configure settings such as communication parameters (address, baud rate) and wiring modes (3P3W, 3P4W).

Close-up of the keypad HMI for programming
Figure 12: Keypad HMI for navigation and programming.

8. Pangropéa

  • beberesih: Jaga méter tetep bersih sareng bébas tina lebu. Anggo lawon anu lemes sareng garing pikeun ngabersihkeun. Entong nganggo pembersih atanapi pangleyur anu abrasif.
  • Kaayaan Lingkungan: Ensure the operating environment adheres to the specified temperature and humidity ranges to prevent damage.
  • Cék sambungan: Pariksa sadaya sambungan kabel sacara berkala pikeun mastikeun éta aman sareng bébas tina korosi.
  • Pembaruan firmware: Pariksa produsén urang websitus pikeun sagala apdet firmware sadia pikeun mastikeun kinerja optimal sarta aksés ka fitur anyar.

9. Cara ngungkulan

  • Henteu aya tampilan/kakuatan: Check the power supply connections (AC 85~265V or DC 100~350V) and ensure they are within the specified range. Verify that the power source is active.
  • Bacaan anu salah: Double-check all CT and voltage wiring connections for correct polarity and phase sequence. Ensure the CTs are correctly installed around the conductors. Verify the meter's configuration settings match your system.
  • Communication Issues (RS485): Confirm the RS485 wiring is correct (A to A, B to B). Check the communication parameters (baud rate, address) on the meter and the connected device (e.g., inverter, gateway). Ensure termination resistors are correctly used if necessary.
  • Meter Not Responding: If the meter becomes unresponsive, try power cycling it (turn off, wait a few seconds, then turn on). If the issue persists, consult the warranty and support section.

10. Tips pamaké

  • Data logging: For applications requiring detailed historical data, such as measurement profiles every 15 minutes, ensure the optional data logging feature is enabled and configured. Refer to the programming interface for setup.
  • CT Selection: Always choose CTs with a current rating appropriate for your application to ensure accuracy and prevent damage.
  • Anti-Reflux Function: When using the meter with an inverter for anti-reflux, ensure the RS485 communication is correctly established and configured according to both the meter and inverter manuals.

11. Jaminan & Dukungan

The Acrel ACR10R Energy Meter comes with a garansi 2 taun ti tanggal beuli. Garansi ieu nyertakeun cacad dina bahan sareng pagawean dina panggunaan normal.

For technical support, troubleshooting assistance, or warranty claims, please contact the ACREL Official Store or your authorized dealer. Provide your product model number (ACR10R-D36TE4) and a detailed description of the issue when seeking support.

CE Certification document for ACR series multi-functional power meters
Figure 13: CE Certification for ACR series multi-functional power meters.

Dokumén Patali - ACR10R-D36TE4

Praview Acrel D317 Rail-type Multifunction Electrical Instrument with External Split Core Current Transformer: Use and Installation Manual
Comprehensive use and installation manual for the Acrel D317 Rail-type Multifunction Electrical Instrument, featuring an external split-core current transformer. Details technical specifications, product functions, installation procedures, and communication protocols for industrial energy monitoring applications.
Praview Acrel ACR10R Rail-type Multifunction Electrical Instrument with External Split Core Current Transformer - Use and Installation Manual
This manual provides comprehensive instructions for the Acrel ACR10R series rail-type multifunction electrical instrument, including its specifications, functions, installation, programming, and RS485 MODBUS-RTU communication. It details technical parameters, connection modes, operation procedures, and troubleshooting guidance for industrial and commercial power monitoring applications.
Praview ADL100-ET Single-Phase Electric Méter Instalasi jeung Manual Instruksi Operasi
Pamasangan lengkep sareng pituduh operasi pikeun méteran listrik Acrel ADL100-ET fase tunggal. Manual ieu ngajéntrékeun spésifikasi téknis, déskripsi fungsional, parentah kabel, ménu tampilan, prosedur program, sareng protokol komunikasi (Modbus RTU).
Praview Acrel D318 Harmonic Meter Operation Instruction Manual
Operation instruction manual for the Acrel D318 External Roche Coil and Switched Transformer Harmonic Meter. Details features, technical specifications, and connection methods for energy saving and power monitoring applications.
Praview Acrel ADL3000-E Smart Méter: Instalasi sareng Manual Operasi
Pamasangan lengkep sareng parentah operasi pikeun méter pinter Acrel ADL3000-E, ngawengku spésifikasi teknis, wiring, fungsi tampilan, jeung protokol komunikasi.
Praview DJSF1352-RN Rail-Mounted DC Power Meter Installation and Operation Manual
This document provides comprehensive installation and operation instructions for the Acrel DJSF1352-RN rail-mounted DC power meter. It covers product specifications, technical parameters, wiring diagrams, operational guidance, menu settings, and communication protocols (Modbus-RTU, DLT645-07).