EARU Surge Protective

EARU Surge Protective Device (SPD) Instruksi Manual

Model: Surge Protective

Merk: EARU

1. Bubuka

The EARU Surge Protective Device (SPD) is engineered to safeguard electrical systems and connected equipment from damage caused by lightning strikes and instantaneous over-voltage events. This manual provides essential information for the safe and effective installation, operation, and maintenance of your SPD.

This device is available in various configurations for both AC (Alternating Current) and DC (Direct Current) applications, with different pole counts and current ratings to suit diverse electrical environments.

2. Émbaran Kasalametan

PERHATOSAN: Pamasangan alat ieu ngalibatkeun damel nganggo voltase anu luhurtage electricity. Improper installation can lead to serious injury, electric shock, or damage to equipment.

  • It is strongly recommended that installation be performed by a qualified professional electrician.
  • Always ensure the power supply is completely disconnected before attempting any installation, inspection, or maintenance work on the SPD.
  • Verify that the ground line is properly connected as indicated in the wiring diagrams to ensure effective surge protection.
  • Do not operate the device if it appears damaged or if the visual indicator shows a fault.

3. Produk Langkungview

The EARU SPD is a compact, modular device designed for easy integration into electrical panels. Key features include:

3.1 Visual Warning Module

The SPD is equipped with a visual warning module that indicates its operational status:

  • Indikator héjo: Signifies normal working condition. The device is active and providing protection.
  • Indikator Beureum: Indicates a working state failure. The internal protection component has been consumed by a surge event and needs replacement.
Visual Warning Module showing green for normal and red for failure
Figure 1: Visual Warning Module indicating normal (green) and failure (red) states.

3.2 Komponen sareng Diménsi

The SPD features clearly labeled input/output terminals, indicator windows, and a ground wire end. It is designed for 35mm DIN rail mounting.

Labeled diagram of a DC SPD showing input, brand, indicator, model number, nominal discharge current, rated voltage, ayeuna ngurangan maksimum, voltage protection level, CE, and ground wire end.
Figure 2: Labeled components of a DC Surge Protective Device.
Labeled diagram of an AC SPD showing L Input, N Input, brand, indicator, model number, nominal discharge current, rated voltage, ayeuna ngurangan maksimum, voltage protection level, CE, and ground.
Figure 3: Labeled components of an AC Surge Protective Device.
Dimensions of the SPD modules, showing height 91mm, width 18mm (1P), 36mm (2P), 54mm (3P), 72mm (4P), and depth 65mm.
Figure 4: Product dimensions for various pole configurations.

4. Spésifikasi

4.1 AC Surge Protective Device (SPD)

Parameter EASP-40 (Type C) EASP-60 (Type B) EASP-20 (Type D)
Peunteun listrik230/400V, AC50/60Hz, 3-phase
Max. Operasi Kontinyu Voltage (Uc)~385VAC
Nominal Discharge Current (In, 8/20μs)20KA30KA20KA
Max. Discharge Current (Imax, 8/20μs)40KA60KA10KA
Voltage Tingkat Perlindungan (Kaluhur)≤1.8KV≤2.2KV≤1.8KV
Waktu Tanggapan< 25ns
Leakage Ayeuna≤20μA
Suhu Lingkungan Gawé-40°C nepi ka +80°C
Kalembaban rélatif<95%
Deterioration IndicationGreen (normal), Red (malfunction)
Mode panyalindunganL-PE, N-PE (1P, 2P, 3P, 3P+N)
Bahan cangkang luarFlame retardant materials (UL94V0)
SertifikasiCE, IEC/EN 61643-1

4.2 DC Surge Protective Device (SPD)

Parameter Nilai
Nominal Voltage (UN)500V / 800V / 1000V DC
Max. Continuous D.C. Voltage (Uc pv)500V / 800V / 1000V DC
Mode panyalindunganCM/DM
Maximum Discharge Current (Imax, 8/20μs)40kA/60KA
Nominal Discharge Current (In, 8/20μs)20kA/30KA
Voltage Protective Level CM/DM at In (Up)≤2.2kV
Isolation Resistance (Risol)> 102MΩ
Response Time (tA)≤25ns
Kuring / O SambunganBy screw terminal: 10-35mm², By connection bus
PamasanganSymmetrical rail (EN50022/DIN46277-3)
Kisaran Suhu Operasi-40°C nepi ka +85°C
Gelar panyalindunganIP20
Bahan PerumahanUL94V0
Indikator DisconnectionMechanical indicator
Kontak Remote ControlNo
Warnakulawu

5. Setup jeung Instalasi

The EARU SPD is designed for easy installation on a 35mm DIN rail. Follow these general guidelines and refer to the specific wiring diagrams for your AC or DC system.

  1. Kakuatan Disconnection: Before starting any installation, ensure that the main power supply to the electrical system is completely turned off and locked out to prevent accidental re-energization.
  2. Pamasangan: Snap the SPD unit(s) onto a standard 35mm DIN rail within your electrical panel.
  3. Sambungan Wiring:
    • Connect the surge protector directly to the main incoming line, typically after the main air switch or leakage protection device.
    • For AC systems, connect the Line (L) and Neutral (N) wires to the corresponding terminals on the SPD.
    • For DC systems, connect the Positive (+) and Negative (-) input wires to the corresponding terminals on the SPD.
    • Grounding: Crucially, connect the ground wire from the SPD to the main grounding busbar of your electrical system. The ground line should be derived from the incoming line.
    • Ensure all connections are secure and tightened to the specified torque.
  4. Verifikasi: After wiring, double-check all connections for correctness and tightness. Ensure no bare wires are exposed.
  5. Pamulihan Kakuatan: Restore power to the system. Observe the visual warning module on the SPD. It should display a indikator héjo, signifying normal operation.

Important Note: The circuit is dangerous. Please ensure installation is performed by a professional electrician.

5.1 Diagram Wiring

Video 1: Produk leuwihview and installation demonstration.
Wiring diagrams for AC and DC SPD installations, showing connections to main switch, branch lines, and ground.
Gambar 5: Kelample wiring diagrams for AC and DC SPD systems.

6. Parentah Operasi

The EARU SPD operates automatically to protect your electrical system. Once correctly installed and powered, it continuously monitors the voltage and diverts any detected surges to the ground, preventing them from reaching your sensitive equipment.

No manual intervention is required for its protective function during normal operation. The primary operational aspect for the user is to monitor the visual warning module.

  • A indikator héjo confirms the SPD is functioning correctly and providing protection.
  • A indikator beureum signals a fault, meaning the SPD has absorbed a significant surge and its protective element needs attention.

7. Pangropéa

To ensure continuous and effective protection, periodic maintenance of your EARU SPD is recommended:

  • Inspeksi Visual: Regularly check the visual warning module on the SPD. If the indicator is beureum, it signifies a working state failure.
  • Ngagantian modul: In case of a red indicator, the internal lightning protection module (cartridge) needs to be replaced. Ensure the power is off before attempting to replace the module.
  • Ngagantian Unit: If the entire protector unit appears physically damaged or if replacing the module does not resolve the red indicator issue, the entire SPD unit should be replaced directly by a qualified electrician.
  • Kabersihan: Keep the SPD and its surroundings clean and free from dust and debris to ensure proper ventilation and operation.

8. Cara ngungkulan

This section addresses common issues you might encounter with your SPD.

8.1 Red Indicator on Visual Warning Module

Masalah: The visual warning module displays a red indicator.

Cukang lantaranana: The SPD has successfully diverted a surge, and its internal protective component (varistor) has reached its end-of-life or is damaged.

Solusi: The lightning protection module (cartridge) needs to be replaced. If the module is not replaceable or the entire unit is damaged, replace the complete SPD unit. Always disconnect power before replacement.

8.2 No Apparent Protection / Equipment Damage Despite SPD Installation

Masalah: Electrical equipment is still experiencing damage from surges, or the SPD does not seem to be functioning.

Cukang lantaranana: Incorrect installation, improper grounding, or the SPD is not adequately rated for the system's surge levels.

Solusi:

  • Verify all wiring connections, especially the ground connection, according to the provided diagrams and safety guidelines.
  • Ensure the SPD's voltage and current ratings (e.g., Uc, Imax, In) are appropriate for your specific electrical system and the expected surge environment.
  • Consult a qualified electrician to inspect the installation and system compatibility.

9. Tips pamaké

  • Solar Panel Systems (PV): For solar panel installations, ensure you select a DC SPD model with appropriate voltage ratings (e.g., DC 500V, 800V, 1000V) and surge capacities (e.g., 20-40KA or 30-60KA). These devices are suitable for protecting PV systems.
  • Kelas panyalindungan: For AC systems, the devices are available in different protection classes (Type B, C, D, or T1, T2, T3). For DC systems, the models typically correspond to Type 2 (T2) or combined T1+T2 applications, depending on the specific model and installation requirements. Consult relevant electrical standards for your region to choose the correct class.
  • Pamasangan profésional: Given the critical role of SPDs and the dangers of electrical work, always prioritize professional installation to ensure optimal performance and safety.

10. Garansi jeung Rojongan

For technical support, service, or warranty claims, please contact your retailer or the manufacturer directly. Keep your purchase receipt and any installation records for warranty validation. The manufacturer's warranty covers defects in materials and workmanship under normal use conditions.


EARU AC & DC Surge Protective Device (SPD) - Lightning Protection 20-60KA

EARU AC & DC Surge Protective Device (SPD) - Lightning Protection 20-60KA

0:22 • 720 × 720 • visual_overview

Dokumén Patali - EARU-C (AC), EASP-PV-500 (DC)

Praview EAWCB Series Smart Circuit Breaker Pamaké Manual ku Zhejiang Earu Electronics
Manual pamaké pikeun EAWCB Series Smart Circuit Breaker ku Zhejiang Earu Electronics, detil parameter produk, pungsi, wiring, dimensi, sareng léngkah sambungan aplikasi pikeun Tuya, Smart Life, sareng platform eWeLink.
Praview EARU EAATS-A Series ATS Dual Power Switch - English Manual
Comprehensive English manual for the EARU EAATS-A Series Dual Power Automatic Transfer Switch. Covers general information, installation conditions, technical parameters, wiring diagrams, maintenance, and safety precautions for reliable power supply switching.
Praview EAPDX-40/63 Runtuyan Earu Electric Voltage & Manual Pamaké Protéktor Ayeuna
Spésifikasi lengkep sareng pituduh operasi pikeun Earu Electric EAPDX-40/63 séri adjustable voltage jeung pelindung ayeuna. Diajar kumaha nyetél over-voltage, handapeun-voltage, sarta parameter panyalindungan leuwih-ayeuna.
Praview EARU EAKCB & EAYCBM Series Smart Circuit Breaker User Manual
Comprehensive user manual for EARU EAKCB and EAYCBM series smart circuit breakers, detailing product parameters, functions, dimensions, model comparison, and network setup. Includes multilingual support information.
Praview Din Rail ATS EAATS-D Series Instruction Manual - EARU ELECTRIC
Instruction manual for the EARU ELECTRIC EAATS-D Din Rail Automatic Transfer Switch (ATS). Covers safety, product description, and technical specifications for reliable dual-power supply systems in buildings and industrial facilities.
Praview EARU ELECTRIC EAATS-A Series Din Rail ATS Instruction Manual
Instruction manual for the EARU ELECTRIC EAATS-A Series Din Rail Automatic Transfer Switch (ATS). Covers safety, product description, and technical specifications for reliable dual-power supply systems.