The GEYA GRD9L-R Auto Recloser is an advanced electrical safety device designed to automatically restore power after an electrical fault, specifically earth leakage currents. This device integrates with a Residual Current Circuit Breaker (RCCB), Residual Current Device (RCD), or Earth Leakage Circuit Breaker (ELCB) to provide continuous protection and minimize downtime caused by nuisance tripping. It is suitable for various applications including power grid terminal lines, meter boxes, new energy circuit management, PV solar control boxes, smart electricity systems, smart homes, and electric vehicle charging piles.

This manual provides essential information for the safe and effective installation, operation, and maintenance of your GRD9L-R Auto Recloser.

GEYA GRD9L-R Auto Recloser with A Type RCCB
Figure 1: GEYA GRD9L-R Auto Recloser (A Type RCCB Recloser).

spésifikasi

The GEYA GRD9L-R Auto Recloser is available in various configurations, including 2-pole and 4-pole versions with different rated currents and sensitivities (30mA, 100mA, 300mA).

spésifikasi umum

  • Ngaran Brand: GEYA
  • Jumlah modél: GYL9 RCCB Recloser (GRD9L-R series)
  • Tipe: Earth Leakage, RCD
  • Dipeunteun Voltage: 220/380V
  • Modeu kontrol: Auto Recloser
  • Sertifikasi: CE
  • Asal: Daratan Cina

Technical Parameters (GRD9L-R)

ParameterNilai
Modeu kontrolOtomatis Reclosing
terminal suplaiA1-A2
Voltagrentang e (DC)DC12V or DC24-48V (model dependent)
Input kakuatan (DC)DC max.1W (standby) max.20W (action)
Voltagrentang e (AC)AC 220V (50-60Hz)
Pasokan voltage kasabaran± 10%
Input daya (AC)AC max.1VA (standby) max.20VA (action)
indikasi suplaiLED beureum
waktos Peta≤1s
Auto reclosing times3
Auto reclosing interval time10s-60s-300s
Reset the closing timesNo trip or manual reset within 15 minutes after successful closing
Kahirupan mékanis10000 siklus
Electrical life (AC1)4000 siklus
Suhu operasi-20°C nepi ka +55°C (-4°F nepi ka 131°F)
Suhu neundeun-35°C nepi ka +75°C (-22°F nepi ka 158°F)
PamasanganDIN rail EN/IEC 60715
Gelar panyalindunganIP20
Overvoltage kategoriIII
Gelar polusi2
Max. cable size (mm²)Solid wire max.1×2.5 or 2×1.5 / with sleeve max.1×2.5 (AWG 12)
Dimensions (GRD9L-R module)82×18×78mm (H×W×D)
Dimensions (GRD9L + GYL9 2P)53mm width (combined unit)
Dimensions (GRD9L + GYL9 4P)88mm width (combined unit)
Technical parameters table for GEYA GRD9L-R Auto Recloser
Figure 2: Technical Parameters of GRD9L-R Auto Recloser.
Dimensions of GEYA GRD9L-R Auto Recloser and combined units
Figure 3: Dimensions of GRD9L-R (single module) and combined with GYL9 2P/4P RCCB.

Instalasi jeung Wiring

WARNING: Installation should only be performed by a qualified electrician. Ensure power is disconnected before installation to prevent electric shock.

Dipasang dina DIN Rail

The GRD9L-R is designed for DIN rail mounting (EN/IEC 60715).

Cooperation with RCCB/MCB

The GRD9L-R Auto Recloser is designed to cooperate with an RCCB (Residual Current Circuit Breaker) or MCB (Miniature Circuit Breaker).

Diagrams showing how to cooperate with RCCB and MCB, closing lock, and accessories installing
Figure 4: Installation and Use Diagrams.
  1. Cooperate with RCCB:
    • Align the recloser with the RCCB.
    • Connect the recloser to the RCCB using the provided accessories.
    • Ensure a secure mechanical and electrical connection.
  2. Cooperate with MCB:
    • Align the recloser with the MCB.
    • Connect the recloser to the MCB using the provided accessories.
    • Ensure a secure mechanical and electrical connection.
  3. konci nutup: When checking the circuit, the RCCB/MCB cannot close when the lock function is activated. This prevents accidental reclosing during maintenance.
  4. Accessories Installing: The diagram shows how to install additional accessories (e.g., ARD) alongside the MCB/RCCB and recloser.

Diagram Wiring

Connect the GRD9L-R according to the following diagram. Ensure correct polarity and voltage for the control circuit (A1, A2, COM, NO, NC, AUX) and the main power circuit (L, N, Load).

Detailed wiring diagram for GEYA GRD9L-R Auto Recloser with alarm lamp and loads
Gambar 5: Kelample Application Wiring Diagram for GRD9L-R with RCCB and loads, including an alarm lamp sambungan.

The wiring diagram illustrates a typical application where the GRD9L-R is connected to an RCCB, protecting multiple loads. An alarm lamp can be connected to the AUX contacts (COM, NO, NC) to indicate the status of the recloser or a persistent fault.

  • L: Input kawat langsung
  • N: Input kawat nétral
  • A1, A2: Control power input (DC12V or AC220V depending on model)
  • COM, NO, NC: Auxiliary contacts for alarm or remote indication.
  • Beban: Devices protected by the RCCB/Recloser combination.

Parentah Operasi

Pamilihan Mode

The GRD9L-R features a selector switch for operating modes:

Diagram showing AUTO and MANU modes, and PWR indicator behavior
Figure 6: Mode Selection and PWR Indicator.
  • Mode otomatis: The auto reclosing function is enabled. The device will attempt to reclose the circuit breaker automatically after a trip.
  • Mode MANU: The auto reclosing function is disabled. The MCB/RCCB can only be opened and closed manually. This mode is typically used for maintenance or when automatic reclosing is not desired.

Power Indicator (PWR LED)

  • When powered on, the green indicator will flash for 2 seconds to wait for the power supply to stabilize.
  • After stabilization, the green indicator light will stay on.
  • If the MCB/RCCB fails to trip, the red indicator light will be on.
  • During auto reclosing delay, the red indicator light will flash.
  • After a successful reclose, the green light will be on.

Automatic Reclosing Logic (AUTO Mode)

The GRD9L-R attempts to reclose the circuit breaker up to 3 times after a trip, with specific time intervals. If reclosing is successful, the counter resets. If all 3 attempts fail within 15 minutes, the device will lock out and require manual intervention.

Functions diagram showing reclosing logic and timing
Figure 7: Functions Diagram and Auto Reclosing Logic.

Reclosing Sequence:

  1. 1st Trip: If the MCB/RCCB trips, the recloser waits 10 seconds, then attempts to switch ON.
  2. 2nd Trip: If it trips again within 15 minutes, it waits 60 seconds, then attempts to switch ON.
  3. 3rd Trip: If it trips a third time within 15 minutes, it waits 300 seconds, then attempts to switch ON.
  4. Konci kaluar: If the third attempt fails, or if there are continuous closing failures within 15 minutes, the device enters a locked-out state (LOCK) and will not attempt further reclosing until manually reset or the 15-minute timer expires after a successful reclose.

The closing times are reset if no trip occurs or if a manual reset is performed within 15 minutes after a successful closing.

Pangropéa

The GEYA GRD9L-R Auto Recloser is designed for minimal maintenance. However, regular checks are recommended to ensure optimal performance and safety.

  • Inspeksi Visual: Mariksa périodik alat pikeun tanda-tanda karusakan fisik, robahan warna, atanapi sambungan anu leupas.
  • Uji fungsionalitas: It is recommended to periodically test the RCCB/RCD functionality as per its own manual. The "Test Monthly" button on the RCCB/RCD should be pressed to ensure it trips correctly.
  • Kabersihan: Keep the device free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.
  • Pariksa profésional: For any concerns or suspected malfunctions, consult a qualified electrician.

Always ensure power is disconnected before performing any inspection or cleaning.

Pamérésan masalah

This section provides guidance on common issues you might encounter with the GRD9L-R Auto Recloser.

MasalahMungkin Cukang lantarananaSolusi
Device does not reclose after a trip.
  • Recloser is in MANU mode.
  • Persistent fault in the circuit.
  • Maximum reclosing attempts (3) reached, device is locked out.
  • Control power (A1-A2) issue.
  • Switch to AUTO mode.
  • Identify and clear the fault in the circuit.
  • Manually reset the recloser or wait for the 15-minute lockout timer to expire after a successful reclose.
  • Check control power supply and connections.
Red PWR LED is continuously ON.MCB/RCCB failed to trip, indicating a potential issue with the circuit breaker itself or a very high fault current.Immediately disconnect power and have a qualified electrician inspect the MCB/RCCB and the electrical system.
Red PWR LED is flashing.Device is in an auto reclosing delay period.This is normal operation. Wait for the reclosing attempt. If it fails, refer to "Device does not reclose" above.
Green PWR LED is OFF.No power supply to the recloser.Check the main power supply and the control power connections (A1-A2).
Closing lock prevents manual operation.Fungsi konci diaktipkeun.Deactivate the lock function as shown in the installation diagram (Figure 4).

If the problem persists after attempting these solutions, contact a qualified electrician or the manufacturer for assistance.

Tip pamaké

  • Always ensure that the GRD9L-R is correctly paired with a compatible RCCB/MCB for optimal performance and safety.
  • Regularly test your RCCB/RCD by pressing its test button to confirm it is functioning correctly. This ensures the entire protection system is reliable.
  • For critical circuits where continuous power is paramount, consider understanding the reclosing delay times to anticipate power restoration.
  • If frequent tripping occurs, it indicates an underlying electrical issue that needs to be addressed by a professional, rather than relying solely on the auto-reclose function.

Garansi sareng Rojongan

For warranty information, technical support, or service inquiries, please contact your point of purchase or the manufacturer directly. Ensure you have your product model number (GRD9L-R) and any relevant purchase details available when seeking support.

Manufacturer: GEYA

Dokumén Patali - GRD9L-R

Praview Katalog Alat Listrik GEYA - Pemutus Sirkuit, Kontaktor, sareng seueur deui
Katalog komprehensif produk listrik GEYA kaasup pemutus sirkuit miniatur, kontaktor, saklar transfer, sareng alat-alat kaamanan anu sanés, detil spésifikasi, aplikasi, sareng standar patuh.
Praview GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide
Comprehensive instruction manual and technical guide for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications, features, technical specifications, installation, networking, troubleshooting, and dimension details for intelligent electrical systems.
Praview GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide
Detailed instruction manual for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications in intelligent household electricity management and photovoltaic systems, function features, technical parameters, panel and wiring diagrams, installation, networking setup with Tuya Smart app, common faults, and dimensions. Essential guide for safe and efficient electrical control.
Praview GEYA WiFi Series Intelligent Miniature Circuit Breaker - Parentah Operasi
Parentah operasi lengkep sareng FAQ pikeun GEYA WiFi Series Intelligent Miniature Circuit Breaker (seri ZJSB9). Diajar ngeunaan pamasangan, setelan, ngungkulan masalah, kaamanan, jeung aplikasi pikeun panyalindungan listrik imah pinter.
Praview GEYA Miniature Circuit Breakers, Contactors, and Transfer Switches Catalog | Technical Specifications
Comprehensive catalog from GEYA detailing Miniature Circuit Breakers (MCB), Residual Current Circuit Breakers (RCCB), Residual Current Circuit Breakers with Overcurrent Protection (RCBO), Molded Case Circuit Breakers (MCCB), AC Contactors, Automatic Transfer Switches, and Intelligent Circuit Breakers. Includes technical specifications, scope of application, product features, and compliance information for various models, serving industrial, commercial, and residential applications.
Praview Zhejiang Geya Eléktro Uninterruptible Millisecond Ngalihkeun Dual Otomatis Transfer Pindah Manual
Buku manual ieu nyayogikeun inpormasi lengkep ngeunaan Zhejiang Geya Electrical Co., Ltd.