STEGO logoRC 016 PTC Enclosure Heater
User GuideSTEGO RC 016 PTC Enclosure Heater

Type RC 016
Store for use at a later date.
IP40

RC 016 PTC Enclosure Heater

STEGO RC 016 PTC Enclosure Heater - feager

L1 35 mm 35 mm 65 mm
L2 30 mm 30 mm 60 mm
L3 18 mm 18 mm 40 mm
Ø 3,2 mm 3,2 mm 4,5 mm

STEGO RC 016 PTC Enclosure Heater - feager1

L1 [mm] P [W]*
35 8
55 10
65 13

* at +20 °C (+68 °F) ambient temperature STEGO RC 016 PTC Enclosure Heater - feager2

L1 [mm] P [W]**
35 14
55 18
65 25

** at +20 °C (+68 °F) ambient temperature, mounted on board (Al, 100 x 100 x 3 mm)

STEGO RC 016 PTC Enclosure Heater - icon 8W – 2A
>10W – 4A
STEGO RC 016 PTC Enclosure Heater - icon1 AC/DC 120 – 240V
STEGO RC 016 PTC Enclosure Heater - icon2 max. 90%rH
STEGO RC 016 PTC Enclosure Heater - icon3 max. 3000m
STEGO RC 016 PTC Enclosure Heater - icon4 VDE: -45 … +70°C (-49 … +158°F)
UL: -45 bus +40°C (-49 bus 104°F)
STEGO RC 016 PTC Enclosure Heater - icon5 20-40g

Translation of the original instructions

USAGE

Heating units are used to prevent the development of condensation and drops in temperature in control cabinets. The heaters must only be used in stationary, sealed housings for electrical devices. Heating units without an integrated thermostat should be connected in series to a suitable thermostat for temperature control. The heaters can be used as convection or contact heaters. The maximum surface temperature depends on use and on the installation situation. Heating units must not be used for the heating of rooms.

Safety considerations

  • Installation must only be performed by qualified electrical technicians in observation of the respective national power-supply guidelines (IEC 60364).
  • The safety measures according to VDE 0100 are to be ensured.
  • The technical specifications on the type plate must be strictly observed!
  • The person using the heater must ensure through the installation that no damage is incurred to the components installed in the immediate vicinity by the hot surfaces (thermal energy).
  • The device must be connected to mains via an all-pole disconnecting device (with contact gap of at least 3 mm in the switched-off state).
  • The device must only be operated in an environment that ensures contamination class 2 (or better) in accordance with IEC 61010. Contamination class 2 means that only non-conductive contra amination may occur. However, it is likely that there will occasionally be temporary conductivity caused by condensation.
  • The device must not be operated in environments with aggressive atmospheres.
  • No changes or modifications must be made to the device.
  • In the event of any damage to or malfunction of the heating unit, the device must not be repaired or put into operation (dispose of the heating unit).
  • Dismantle the heater only after it has cooled down.

Attention! The heater must not be mounted on flammable materials (e.g. wood, plastic etc.).
Notice
The manufacturer accepts no liability in the case of failure to observe this brief instruction, improper use and changes or damage to the device.

Caution icon BLAUPUNKT MS46BT Bluetooth CD-MP3 player with FM and USB - icon 3WARNING There is a risk of personal injury and equipment damage if the connection values  are not observed or polarity is incorrect!
caution icon BLAUPUNKT MS46BT Bluetooth CD-MP3 player with FM and USB - icon 3WARNING Hot surfaces following commissioning!
Risk of injury!

STEGO logo

STEGO Electrotechnics GmbH – Kolpingstrasse 21
– 74523 Schwaebisch Hall Germany – www.stego.dSTEGO RC 016 PTC Enclosure Heater - icon6

Documents / Resources

STEGO RC 016 PTC Enclosure Heater [pdf] User Guide
RC 016 PTC Enclosure Heater, RC 016, PTC Enclosure Heater, Enclosure Heater, Heater

References