  • Resistant Ex e enclosure, universally usable as connection or junction boxes and/ or to safeguard electric distributors up to 6.3 A
  • IP66 degree of protection
  • With mantle terminals or with a combination of mantle terminals and miniature fuses (optional)

WebCode 8118A

R. STAHL Series 8118 junction boxes are equipped with 4, 5 or 8 mantle terminals depending on their design size. As an option, miniature fuses can still be installed in addition. Junction boxes are therefore also suitable for safeguarding. The robust enclosure made from glass fibre reinforced polyester resin can be equipped with plastic or metal cable glands.

Technical Data

Explosion Protection
Scope of validity European Union (ATEX) IECEx
Application range (zones) 1

2

21

22

IECEx gas certificate IECEx PTB 06.0026
IECEx gas explosion protection Ex ia ib IIC T6 Gb
IECEx dust certificate IECEx PTB 06.0026
IECEx dust explosion protection Ex tb IIIC T80 °C Db
ATEX gas certificate PTB 99 ATEX 3103
ATEX gas explosion protection E II 2 G Ex ia ib IIC T6 Gb
ATEX dust certificate PTB 99 ATEX 3103
ATEX dust explosion protection E II 2 D Ex tb IIIC T80 °C Db
Certificates ATEX (PTB), Brazil (ULB), China (NEPSI), EAC (ENDCE), IECEx (PTB)
Ship approval BVIS
Explosion protection note For product label, see skope of validity.
Electrical Data
Permissible rated operational current with 5 loaded terminals for conductor cross-section 1.5 mm²: 13 A for conductor cross-section 2.5 mm²: 18 A for conductor cross-section 4 mm²: 24 A
Permissible rated operational current with 4 loaded terminals for conductor cross-section 1.5 mm²: 15 A for conductor cross-section 2.5 mm²: 19 A for conductor cross-section 4 mm²: 25 A
Permissible rated operational current with

≤ 3 loaded terminals

for conductor cross-section 1.5 mm²: 16 A for conductor cross-section 2.5 mm²: 20 A for conductor cross-section 4 mm²: 25 A
Ambient Conditions
Ambient temperature -40 °C … +75 °C (T6)
Ambient Conditions
Ambient temperature -40°F … +167°F (T6)
Mechanical Data
IP degree of protection (IEC 60529) IP66
Enclosure material Polyester resin, Glass fibre reinforced
Enclosure colour Dark grey
Flammability according to IEC/EN 60695

UL 94 ASTM D635

Silicone-free No
Connection cross-section 4 mm²
Permissible number of conductors per clamping unit, solid mantle terminal M7 x 0.75

conductor cross-section 1.5 mm²: number of conductors min. 2, max. 4 conductor cross-section 2.5 mm²: number of conductors min. 2, max. 2

Permissible number of conductors per clamping unit, finely stranded prepared, core end sleeve crimped mantle terminal M7 x 0.75

conductor cross-section 1.5 mm²: number of conductors min. 2, max. 3 conductor cross-section 2.5 mm²: number of conductors min. 2, max. 2

Permissible number of conductors per clamping unit, finely stranded unprepared mantle terminal M7 x 0.75

conductor cross-section 1.5 mm²: number of conductors min. 2, max. 3 conductor cross-section 2.5 mm²: number of conductors min. 2, max. 2

Permissible number of conductors per clamping unit note All conductors of a terminal must have identical cross sections and identical material.
Cover Screw-on cover
Cover fixing type M4 stainless steel screws, With captive screws
Width 85 mm
Width, inches 3.35 in
Height 85 mm
Height, inches 3.35 in
Depth 55 mm
Depth, inches 2.17 in
Packaging unit 1
Weight 0.28 kg
Weight 0.62 lb
Mounting / Installation
Tightening torque of cover screw 1 1.4 Nm
Cover screw 1 tightening torque lbf in 12.4 lbf in
Components
Entry 1 2 x 8161/8-M20-1304

(Provided separately)

Entry 1 type Polyamide cable gland, blue
Entry 1 M20 x 1.5
Entry 1 terminal area 4 – 13 mm
Entry 1 clamping range, inch 0.16 – 0.51 in
Metal entry possible 1 No
Entry 2 1 x 8290/3-M20

(Provided separately)

Entry 2 type Polyamide stopping plug
Entry 2 M20 x 1.5

Components

  • Metal entry possible 2 No
  • Entries installation options/ side Size 1: 3x M20 (A+B+D)
  • Type of terminals 1 4 x Mantle terminal 4 mm²

Technical Drawings – Subject to AlterationsSTAHL-133084-Ex-i-Junction-Boxes-FIG 1

Dimensional Drawings (All Dimensions in mm [inches]) – Subject to AlterationsSTAHL-133084-Ex-i-Junction-Boxes-FIG 2

Accessories

Cable gland made of plastic

STAHL-133084-Ex-i-Junction-Boxes-FIG 3 8161/8-M20-1304, Ex i

Plastic, M20 x 1.5, cable outer diameter 4 to 13 mm Lot size 50 pieces

239164

Stopping plug

STAHL-133084-Ex-i-Junction-Boxes-FIG 4 8290/3-M20

Plastic, M20 x 1.5 Lot size 100 pieces

285773

Brass plate with thread

STAHL-133084-Ex-i-Junction-Boxes-FIG 5 8118 size 1, plate 37 x 30 mm [1.46 x 1.18″] 1 x M20 x 1.5 with M4 PE connection (left)

for installation in enclosure size 1, size 2 and size 3

168913
STAHL-133084-Ex-i-Junction-Boxes-FIG 6 8118 size 1, plate 37 x 30 mm [1.46 x 1.18″] 1 x M20 x 1.5 with M4 PE connection (right)

for installation in enclosure size 1, size 2 and size 3

168914

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.

2022-11-25 R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG

Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

Documents / Resources

STAHL 133084 Ex i Junction Boxes [pdf] Installation Guide
133084 Ex i Junction Boxes, 133084, Ex i Junction Boxes, Junction Boxes, Boxes

References

Leave a comment

Your email address will not be published. Required fields are marked *