sprecher schuh logoType E Self-Protected Manual Motor Controller
Enclosed Series KTA9

KTA9 Type E Self-Protected Manual Motor Controller

Amp / Horsepower Rating Non-metallic (IP65) Enclosuresprecher schuh KTA9 Type E Self Protected Manual Motor Controller
Max. Horsepower 000 0/L Relay Ampere
Range 0.10…0.16
1Magnetic Res.
r..) Current
Catalog Number 0
KTA9-32S-0.16A-CG
1 Dimension Code
Three Phase
200V
230V
460V
575V
0.16…0.25 4. KTA9-32S-0.25A-CG AY
0.25…0.40 6. KTA9-32S-0.4A-CG AY
0.40…0.63 9. KTA9-32S-0.63A-CG AY
1/2 1/2 0.63…1.0 14 KTA9-32S-1.0A-CG AY
3/4 1.0…1.6 22 KTA9-32S-1.6A-CG AY
1/2 1/2 1 1-1/2 1.6…2.5 35 KTA9-32S-2.5A-CG AY
3/4 3/4 2 3 2.5…4.0 52 KTA9-32S-4.0A-CG AY
1 1-1/2 3 5➍ 4.0…6.3 88 KTA9-32S-6.3A-CG AY
2 2 5 7/1/2➍ 6.3…10 140 KTA9-32S-10A-CG AY
3 5 10 10➍ 10…16 224 KTA9-32S-16A-CG AY
5➍ 5➍ 10➍ 15➍ 14.520 280 KTA9-32S-20A-CG AY
5➍ 7/1/2➍ 15➍ 20➍ 18…25 330 KTA9-32S-25A-CG AY
7/1/2➍ 10➍ 20➍ 25➍ 24…29 406 KTA9-32S-29A-CG AY
7/1/2➍ 10➍ 20➍ 30➍ 27…32 448 KTA9-32S-32A-CG AY
  1. Horsepower ratings shown in the table above are for reference. The final selection of the controller depends on the actual motor full load current and service factor.
    • For motor with service factor less than 1.15. Use motor nameplate full load current times 0.9 and choose the motor starter with the appropriate current range.  Example: Motor FLC = 4.2A; S.F. = 1.0. 4.2A x 0.9 = 3.78A. Select catalog number KTA9-32S-4.0A.
  2. Magnetic trip is fixed at 14x the maximum value of the current adjustment range. Refer to page F5 for applied KAIC ratings.
  3. KTA9 may be applied to single phase loads if 3 poles of device are wired in series. See footnote 1 for device selection criteria.
  4. A red and yellow handle may be selected instead of the standard gray and black handle. Change “CG” suffix to “CJ”. Ex: Change KTA9-32S-0.16A-CG to KTA9-32S- 0.16A-CJ.
  5. Handles are built-in to the enclosure and are not available as components.
  6. Catalog numbers with specific voltages (i.e. @ 575V) shaded in gray are suitable for use as a manual motor starter only because they are not Type E rated. See page F5 for ratings.

Includes:

  • Non-metallic (IP65) enclosure with integrated IP65 operator – watertight, dusttight
  • KTA9-32S (Standard Interrupting Capacity) “Type E” Self-protected Combination Manual Controller ➎
  • Terminal Adaptor for Type E Applications (Cat.# KT9-40-TE)
  • Gray and black IP65 handle ➍➎

Enclosure Only

Description Catalog Number Price
Gray/Black handle KT9-ENN
Red/Yellow handle KT9-ENRY

Modifications (Factory Assembled)

Description Add Suffix to Cat.
Number
KT9 Auxiliaries & Trip Contacts,
Front Mount 250V max.
1 NO Auxiliary
1 NC Auxiliary
1 NO + 1 NC Auxiliary
2 NO Auxiliaries
1 NO SC+OL + 1 NC
Auxiliary
1 NO SC+OL + 1 NO
Auxiliary
Side Mount 600V max.
2 NC Auxiliaries
2 NO Auxiliaries
1 NO + 1 NC Auxiliary
-B
-A
-C
-D
-R
-S
-AS02
-AS20
-AS11
Additional KT9 Trip Contacts,Side Mount 600V max.
1 NO SC+OL+1 NO SC
1 NO SC+OL+1 NC SC
1 NC SC+OL+1 NO SC
-R00
-R01
-R10
Accessories
Undervoltage Release Module Shunt Release Module
-UA-✱
-AA-✱

-UA..-AA Coil Codes (✱)

AC Coil Code Voltage Range
50 Hz 60 Hz
24V 21V 24V
28V 24V 28V
120V 105V 120V
127V 110V 127V
230V 220…230V
240V 240…260V
277V 240V 277V
460V 380…400V 400…460V
480V 415V 480V
600V 550V 600V

SSNA2018
visit www.sprecherschuh.com/ecatalog for pricing and the most up to date information
Discount Schedule B7
www.sprecherschuh.com/ecatalog – All pricing shown in US dollars – FY20

Documents / Resources

sprecher schuh KTA9 Type E Self-Protected Manual Motor Controller [pdf] User Guide
KTA9 Type E Self-Protected Manual Motor Controller, KTA9, Type E Self-Protected Manual Motor Controller, Motor Controller, Controller

References