solis Export Limit Settings Using Export Power Manager

solis Export Limit Settings Using Export Power Manager fig (2)

INSTALLATION STEPS

  • STEP 1: Press Enter on the EPM.
  • STEP 2: Scroll down to ‘Advanced Settings’ using the Up/Down keys. Press Enter.
    Type the password – <0010> and click Ent.
    You will see the following options.solis Export Limit Settings Using Export Power Manager fig 3
  • STEP 3: Set the inverter quantity by selecting the ‘Inverter Qty’ option. Press Ent to save.
  • STEP 4: Select ‘Backflow Power’ and Press Enter.
    Define the Backflow power as per your requirement using the Up/Down keys. Press Enter to select and save.
  • STEP 5: Select ‘Set Meter CT’ to define the CT ratio parameter. For example, if your CT clamp rating is 100A/5A then the ratio is 20:1. Press Enter to select and save.
  • STEP 6: Press ESC twice to exit.

‘ALL DONE’ HAVE A GOOD DAY!