zeta ZAIO-MI Fyreye MkII Addressable Input Module

INSTALLATION MANUAL

General

The Fyreye MkII Addressable Input/Output Module is supplied with a backbox for surface mounting.

NOTE: The Input/Output Module is designed for indoor use only.

This product is loop powered and a maximum of 60 devices are allowed on any Zeta detection loop.

Model No: ZAIO-MI

Fyreye MkII Addressable Input/Output Module With Isolator

Surface Mounting

1. Mount the backbox as required and install all cables for termination.
2. Set the address of the unit as shown on page 3.
3. Terminate all cables.
4. Gently push the completed assembly towards the back box until the mounting holes are aligned and secure with the two mounting screws provided.

DO NOT OVERTIGHTEN.

Isolator Module

The ZAIO-MI Module is fitted with a bi-directional short-circuit isolator and will be unaffected by loop short-circuits on either loop input or output.

LED Indications

Status LED Indication
Switch closed Illuminated red when monitored field contact is activated
Relay on Illuminated red when relay is energized
Fault Illuminated yellow when the input is open or short circuit
Polling Flashed green when the device is polled by control panel
Isolating Illuminated yellow when the loop is short or wrong connection circuit

Wiring details

All wiring terminals will accept solid or stranded cables up to 2.5mm2

Interface to 3rd Party Panel

MkII Addressable Input Module

 

MkII Addressable Input Module

Technical Specification

Model ZAIO-MI
Part Number 48-108
Operating Voltage 17-28V DC
Quiescent Current @ 24V 1.0mA
Switch Input Closed (LED OFF) 1.25mA
Relay Operated (LED ON) 2.0mA (Max 2 LEDs on)
Relay Rating SELV @ 1A
Isolating Current 7.3mA
Input End Of Line 20k
Alarm Triggering Resistor 1k
Operating Temperature -10°C to +55°C
Max Humidity 95% RH Non Condensing
IP rating IP21C
Size (mm) 150 x 90 x 45
Weight 220g

 

For information on the short circuit isolator operation see document GLT-224-6-9 available from your distributor.

Address Setting

The address of the Input/Output Module is set using the eight segments of the DIL switch. Each segment of the switch must be set to “0”(ON) or “1”(OFF), using a small screwdriver or similar tool. A complete list of address settings is shown overleaf. The maximum address is 250.

MkII Addressable Input Module

 

Alternative Soft Addressing Option

Using our hand held MkII programmer (Part No: 48-004), the unit can be addressed electronically.

Step 1: Set all addresses to zero 0000000

Step 2: Connect leads to LOOP IN+ and LOOP IN- as shown below

MkII Addressable Input Module

Step 3: Follow the procedure as described in the handheld programmer manual.

NOTE: When a device is soft addressed as above, the address CANNOT BE CHANGED by mechanical setting of the dip-switch. In order to re-enable the dip-switch the unit needs
to be set electronically back to zero first.

Isolator Function

The Isolator Function can be enabled or disabled according to the wiring method.

A. Enabling the Isolator Function

MkII Addressable Input Module

B. By-passing the Isolator Function

MkII Addressable Input Module

Functional Test Data

Command Bit Function Input Bit Function
3 Not Used 3 Not Used
2 ENABLE SWITCH CLOSED LED
0 = Normal
1 = Illuminated Switch Closed LED
2 Not Used
1 Not Used 1 OPTO INPUT
0 = No Input
1 = Voltage On Input
0 OPERATES RELAY
0 = Relay On
1 = Relay Off
0 MONITORED INPUT
0 = Quiescent
1 = Input Received

 

Input Condition and Status

Status Load Input Analogue LED State Input Bit. Bit 0
Short-circuit fault <100Ω 8 Fault LED =0
Indeterminate 100Ω-200Ω 8 or 72 / =0 or 1
Switch closed 200Ω-11kΩ 136 Switch Closed =1
Indeterminate 11kΩ-15kΩ 136 or 72 / =0 or 1
Normal (Switch open) 15kΩ-25kΩ 72 0
Indeterminate 25kΩ-30kΩ 8 or 72 / 0
Open-circuit fault >30kΩ 8 Fault LED 0

 

Analogue Return Back

Voltage Input Analogue Value LED State Input Bit.Bit1
<1V Irrelevant Irrelevant =0
1V-4V Irrelevant Irrelevant =0/1
4V-35V Irrelevant Irrelevant =1
>35V(not allowed) Irrelevant Irrelevant /

 

Troubleshooting

Before investigating individual units for faults, it is very important to check that the system wiring is fault free. Many fault conditions are the result of simple wiring errors. Check all connections to the unit and make sure that the correct value resistors are fitted where necessary.

Faultfinding

Problem Possible Cause
No response or missing Incorrect address setting Incorrect loop wiring
Fault condition reported Incorrect input wiring
Relay fails to operate Control panel has incorrect cause and effect
programming
Incorrect address setting
Relay energized continuously Incorrect loop wiring
Incorrect address setting
Analogue value unstable Dual address
Loop data fault, data corruption
Constant alarm Incorrect wiring
Incorrect end-of-line resistor fitted
Incompatible control panel software

 

CE
Zeta Alarms Limited,
72-78 Morfa Road, Swansea SA1 2EN 14
GLT-233-DoP-1
EN54-18: 2005
EN54-17: 2005
Fire detection and fire alarm systems – Input/Output Devices Fire detection and fire alarm systems – Short Circuit Isolators
Zeta Addressable Input Output Module with Isolator ZAIO-MI
Intended for use in fire detection and fire alarm systems in and around buildings
Response delay (response time) – PASS Performance under fire conditions – PASS Operational reliability – PASS
Durability of operational reliability: temperature resistance – PASS Durability of operational reliability; vibration resistance – PASS Durability of operational reliability; humidity resistance – PASS Durability of operational reliability; corrosion resistance – PASS Durability of operational reliability; electrical stability – PASS

 

Specifications

  • Model: ZAIO-MI
  • Operating Voltage: 24V
  • Quiescent Current: Varies
  • Switch Input Closed (LED OFF): Illuminated red when monitored field contact is activated
  • Relay Operated (LED ON): Illuminated red when relay is energized
  • Relay Rating: Varies
  • Isolating Current: Varies
  • Operating Temperature: Varies
  • Max Humidity: Varies
  • IP Rating: Varies
  • Size (mm): Varies
  • Weight: Varies

FAQ

Q: Can the Input/Output Module be used outdoors?

A: No, the Input/Output Module is designed for indoor use only.

Q: What is the maximum number of devices allowed on the Zeta detection loop?

A: A maximum of 60 devices are allowed on any Zeta detection loop.