Triconex 3700 Series Analog Input Modules Instructions
Triconex 3700 Series Analog Input Modules

Ana log Input Modules

Ana log Input (AI) Modules includes three independent input channels. Each input channel receives variable voltage signals from each point, converts them to digital values, and transmits the values to the three Main Processor modules on demand. In TMR mode, one value is then selected using a mid value selection algorithm to ensure correct data for every scan.

Sensing of each input point is performed in a manner that prevents a single failure on one channel from effecting another channel. Each Ana log Input Module sustains complete, ongoing diagnostics for each channel.
Failure of any diagnostic on any channel activates the Fault indicator for the module, which in turn activates the chassis alarm signal. The module’s  Fault indicator merely reports a channel fault, not a module failure—the module can operate properly with as many as two faulty channels.

Ana log Input Modules support hot spare capability, which allows online replacement of a faulty module.

Analog Input Modules require a separate external termination panel (ETP) with a cable interface to the Triton back plane. Each module is mechanically keyed for proper installation in a Triton chassis.

Analog Input Module Specifications

Model Number 3700/3700A 3701 3703E
Voltage 0-5V, + 6% (only 3700A) 0-10V 0-5V or 0-10V1, + 6%
Type TMR, AI TMR, AI TMR, AI
No. of Input Points 32, diff, DC coupled 32, diff, DC coupled 16, diff, isolated
Isolated Points No No Yes
Input Update Rate 55 ms 55 ms 50 ms
Resolution 12 bits 12 bits 12 bits
Accuracy < .15% of FSR,from 0° to 60°C < .15% of FSR,from 0° to 60°C < .15% of FSR,from 0° to 60°C
Input Resistance (load) 30 MW (DC), min. 30 MW (DC), min. 30 MW (DC), min.
Power-Off Resistance 30 KW (DC), typical 30 KW (DC), typical 30 MW (DC), min.
Common Mode Rejection -80 dB (DC-100Hz),typical -80 dB (DC-100Hz),typical -90 dB @ 60Hz, min.-100 dB @ DC, min.
Common Mode Range -12V to +12V peak -12V to +12V peak +200V peak
Leg-to-Leg Isolation 200 KW, typical 200 KW, typical 20 KW, typical
Normal Mode Rejection
@ 8Hz -3 dB -3 dB -3 dB
@ 60Hz -17 dB -17 dB -17 dB
@ 120Hz -23 dB -23 dB -23 dB
Input Over range 150 VDC/115 VAC 150 VDC/115 VAC 150 VDC/115 VAC
Protection continuous continuous continuous
Current Range 0-20 mA, 0-20 mA, 0-20 mA,
250 W shunt 500 W shunt 250 W shunt for 5V 500 W shunt for 10V
Diagnostic Indicators
Module Status Pass, Fault, Active Pass, Fault, Active Pass, Fault, Active
Color Code Yellow Light yellow Mustard yellow
  1. The voltage is selected using TriStation 1131.