Solar-Log MOD I-O Module Power Management User Guide
Solar-Log MOD I-O Module Power Management

Introduction

Warning Icon This installation manual is intended for use by solar energy technicians and professional electricians, as well as Solar-Log Base users. It should be noted that the installation and commissioning of the individual components is only to be performed by properly trained specialists.

The Solar-Log™ must only be used by persons who have fully read and understood this manual before installing, operating and/or servicing the device.

Please observe!

Warning Icon Disconnect the power of the Solar-Log Base before plugging in/out the bus connector and before connecting the module with the Solar-Log™.

Assembly

The Solar-Log MOD I/O module is manufactured in accordance with protection  lass IP20 and is designed exclusively for installation in suitable for dry, dust-free
indoor use. The assembly itself can be carried out both via wall mounting as wellas on a DIN rail. Power is supplied via the bus system by the Solar-Log Base, a power supply via pins power + and – is not required for the PM+ function. The need of an external power supply is optional and depends on the output current.

Module Solar-Log MOD I/O connection and mounting

Take one of the 2 bus connectors included in the scope of delivery. The bus connector is plugged into the back of the Solar-Log Base.

Take the second bus connector and plug it into the back of the Solar-Log MOD I/O. To complete the HBus connection, plug the two bus connectors together. Now the connected housings can be snapped into the DIN rail.

Note Icon Follow the short instructions Solar-Log Base.

Connections

Top
Connections

Bottom
Connections

Pin Solar-Log MOD I/O
Signal Indicator COM Functional earthing
Signal Indicator 1 Control signal active power
Signal Indicator 2 Digital_In 1
Signal Indicator 3 Digital_In 2
Signal Indicator 4 Digital_In 3
Signal Indicator 5 Digital_In 4
Signal Indicator 6 Control signal reactive power
Signal Indicator COM Functional earthing

Note Icon For further information on connecting the ripple control receiver, please refer to the installation manual.

Technical Data

Device voltage 24V (+-5 %), in exceptional cases 12V (+-5 %
Total current of the outputs With a power supply via the HBus: 250 mA With an external power supply: 1A
Cable cross-section Solid conductor: 0.2 … 1.5 mm² / 24 … 16 AWG Fine-stranded conductor: 0.2 … 1.5 mm² / 24 … 16 AWG With ferrules: 0.14 … 1 mm²/ 26 … 18 AWG (ferrules – to be used for fine-stranded conductor
Strip length 8.5 … 9.5 mm / 0.33 … 0.37 inch, with ferrules ≧ 6mm / 0,24 inch Please take into account the diameter of the plastic sleeves
Power consumption min. 2 W
Control signal Voltage of the control signal corresponds to Supply voltage of the Solar-Log Base
Dimensions (WxHxD) in mm 53,6×89,7×60,3

Costumer Support

Solar-Log GmbH
 www.solar-log.com
Subject to change without notice
EN | 03.2022 | Version 1.6 | Art.Nr.: 15818