SmartGen-LOGO

SmartGen AIN24-2 Analog Input Module

SmartGen-AIN24-2-Analog-Input-Module-FIG- (2)

SmartGen — make your generator smart

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
SmartGen Technology reserves the right to change the contents of this document without prior notice

Table 1 – Software Version

  • Date /Version /Content
  • 2021-10-26 1.0 Original release

Table 2 – Notation Clarification

Symbol Instruction
NOTE Highlights an essential element of a procedure to ensure correctness.
CAUTION Indicates a procedure or practice, which, if not strictly observed, could result in

damage or destruction of equipment.

 

WARNING

Indicates a procedure or practice, which could result in injury to personnel or loss of

life if not followed correctly.

OVERVIEW

AIN24-2 Analog Input Module is a module which has 14-way K-type thermocouple sensor, 5-way resistance type sensor and 5-way (4-20)mA current type sensor. The sampling data are transmitted to the master controller via RS485 port.

PERFORMANCE AND CHARACTERISTICS

  • With 32-bit ARM based SCM, high integration of hardware and more reliable;
  • Must be used with master controller together;
  • RS485 communication baud rate can be set as 9600bps or 19200bps via dial switch;
  • Module address can be set as 1 or 2;
  • Wide power supply range DC(8~35)V, suitable to different battery voltage environment;
  • 35mm guide rail mounting type;
  • Modular design, pluggable terminal, compact structure and easy installation.

TECHNICAL PARAMETERS

Table 3 – Technical Parameters

Item Content
Working Voltage DC(8~35)V, continuous power supply
Power Consumption <0.5W
K-type Thermocouple Measurement

Accuracy

1°C
(4-20)mA        Current       Measurement

Accuracy

Class 1
Case Dimension 161.6mm x 89.7mm x 60.7mm
Rail Dimension 35mm
Working Temperature (-25~+70)°C
Working Humidity (20~93)%RH
Storage Temperature (-40~+80)°C
Weight 0.33kg

WIRE CONNECTIONSmartGen-AIN24-2-Analog-Input-Module-FIG- (3)

Table 4 – Terminal Connection

No. Function Cable Size Description
1 B- 1.0mm2 DC power supply negative input.
2 B+ 1.0mm2 DC power supply positive input.
3 NC   No Contact.
4 TR 0.5mm2 Short connect Terminal 4 and Terminal 5 if the matched

resistance is required.

5 RS485 A(+)  

0.5mm2

The RS485 port for communication with master controller.

120Ω shielding wire with its one end grounded is recommended.

6 RS485 B(-)
7 COM (B+) 1.0mm2 4-20mA current sensor COM terminal (B+)
8 AIN24 0.5mm2 4-20mA current sensor terminal
9 AIN23 0.5mm2 4-20mA current sensor terminal
10 AIN22 0.5mm2 4-20mA current sensor terminal
11 AIN21 0.5mm2 4-20mA current sensor terminal
12 AIN20 0.5mm2 4-20mA current sensor terminal
13 SENSOR COM 0.5mm2 Resistance sensor COM terminal (B+)
14 AUX.SENSOR 19 0.5mm2 Resistance sensor terminal
15 AUX.SENSOR 18 0.5mm2 Resistance sensor terminal
16 AUX.SENSOR 17 0.5mm2 Resistance sensor terminal
17 AUX.SENSOR 16 0.5mm2 Resistance sensor terminal
18 AUX.SENSOR 15 0.5mm2 Resistance sensor terminal
19 KIN14+ 0.5mm2 “K-type” thermocouple sensor
20 KIN14-
No. Function Cable Size Description
21 KIN13+ 0.5mm2 “K-type” thermocouple sensor
22 KIN13-
23 KIN12+ 0.5mm2 “K-type” thermocouple sensor
24 KIN12-
25 KIN1- 0.5mm2 “K-type” thermocouple sensor
26 KIN1+
27 KIN2- 0.5mm2 “K-type” thermocouple sensor
28 KIN2+
29 KIN3- 0.5mm2 “K-type” thermocouple sensor
30 KIN3+
31 KIN4- 0.5mm2 “K-type” thermocouple sensor
32 KIN4+
33 KIN5-  

0.5mm2

 

“K-type” thermocouple sensor

34 KIN5+
35 KIN6- 0.5mm2 “K-type” thermocouple sensor
36 KIN6+
37 KIN7- 0.5mm2 “K-type” thermocouple sensor
38 KIN7+
39 KIN8- 0.5mm2 “K-type” thermocouple sensor
40 KIN8+
41 KIN9- 0.5mm2 “K-type” thermocouple sensor
42 KIN9+
43 KIN10- 0.5mm2 “K-type” thermocouple sensor
44 KIN10+
45 KIN11- 0.5mm2 “K-type” thermocouple sensor
46 KIN11+
   

 

 

SWITCH

The master controller can connect to two AIN24-2 modules at the same time.

Address selection: It is module 1 when the switch 1 is connected to 12 while module 2 when connect to ON position.

Baud rate selection: It is 9600bps when the switch 2 is connected to 12

while 19200bps when connect to ON position.

  POWER Power supply normal indicator;

It is flashing when the communication is abnormal for over 10s.

ELECTRICAL CONNECTION DIAGRAMSmartGen-AIN24-2-Analog-Input-Module-FIG- (4)

CASE DIMENSIONSSmartGen-AIN24-2-Analog-Input-Module-FIG- (5)

TROUBLESHOOTING

Problem Possible Solution
Controller    no    response                    with power Check power voltage;

Check controller connection wirings; Check DC fuse.

RS485 communication failure Check if RS485 wires are connected correctly.

Documents / Resources

SmartGen AIN24-2 Analog Input Module [pdf] User Manual
AIN24-2 Analog Input Module, AIN24-2, AIN24-2 Module, Analog Input Module, Input Module, Analog Module, Module

References