SIEMENS 200969-4 Reverse Fixings

SIEMENS-200969-4-Reverse-Fixings-product

Product Specifications

  • Brand: Electrium Sales Limited, Siemens Ltd
  • Model: 200969-4 NH SF
  • Country of Origin: England, Ireland

Installation Instructions for Reverse Fixings

Installation and operation must be in accordance with published data, instructions and diagrams and with any relevant national and local regulations.

SIEMENS-200969-4-Reverse-Fixings- (1) SIEMENS-200969-4-Reverse-Fixings- (2)

Fitting Instructions for fuse combination units

SIEMENS-200969-4-Reverse-Fixings- (3)

 INSPECTION ON RECEIPT
The following are supplied with each switch

Size
20A -32A HOUSING C/W SWITCH
63A HOUSING C/W SWITCH
100A HOUSING C/W SWITCH TERMINAL FIXING KIT
125A – 200A HOUSING C/W SWITCH TERMINAL FIXING KIT
315A — 400A HOUSING C/W SWITCH TERMINAL FIXING KIT
630A – 800A HOUSING C/W SWITCH TERMINAL FIXING KIT
  • EARTH FIXING KIT FUSE KIT
  • EARTH FIXING KIT FUSE KIT
  • EARTH FIXING KIT FUSE KIT
  • EARTH FIXING KIT FUSE KIT (125A ONLY)

Storage prior to installation must be in clean dry condition.

 Safety

DANGER HAZARDOUS VOLTAGE

SIEMENS-200969-4-Reverse-Fixings- (4)

Size A B C D E F G H
20A -32A 220 150 210 140 105 200 130 135
63A 420 320 262 162 105 258.5 183 188
100A – 125A 420 320 262 162 105 258.5 183 188
160A – 200A 525 425 315 215 105 305 235 240
250A – 400A 735 645 420 320 210 305 235 240
630A – 800A 850 760 630 430 210 355 285 290

SIEMENS-200969-4-Reverse-Fixings- (5)

FORMED EXTENSION COPPERS MUST BE FITTED TO BOTH UPPER AND LOWER SWITCH TERMINALS

SIEMENS-200969-4-Reverse-Fixings- (6)

INSTALLATION PROCEDURE

INSTALLATION AND OPERATION MUST BE IN ACCORDANCE WITH PUBLISHED DATA, INSTRUCTIONS AND DIAGRAMS AND WITH ANY RELEVANT NATIONAL AND LOCAL REGULATIONS.

  • With the housed switch in the Off position mount as shown on page 2. (for ease of installation the switch can be temporarily removed from the housing)
  • Verify the mechanical operation of the switch.
  • Check the operation of the door interlock (i.e. the door cannot be opened with the switch in the ON position)
  • Fit the required fuse links or isolator links (using the fasteners provided)
  • Check the electrical continuity of the switch.
  • The incoming connection may be made to the terminals at either end of the switch.
  • Terminal shields provided must be fitted after connection to all phases and both sides of the switch.

TERMINAL DATA

Size Phase Width Terminal Width Terminal Hole Size
20A -32A 21.5mm 6.5mm Box Terminals Max 16mm²
63A 32.0mm 7.0mm Box terminals Max 25mm²
100A – 125A 36.0mm 22.0mm M8
160A – 200A 36.0mm 22.0mm M8
250A 60.0mm 32.0mm M10
315A – 400A 66.0mm 50.0mm M10
630A 80.0mm 50.0mm M12
800A 80.0mm 50.0mm 4 x M8 or 1 x M14

FUSE AND TERMINAL TORQUE VALUES

Thread Size Torque Value Thread Size Torque Value
M4 1.35Nm M8 17Nm
M5 5.5Nm M10 28Nm
M6 9.5Nm M12 45Nm

Maintenance

No maintenance of the switch is required except for the periodic checking of the tightness of the terminals and fuse links.
Maintenance must be carried out by competent personnel with the supply isolated.

Fuse Selection Data
Current Rating BS88 Reference Lawson GEC Busman
20A -32A A1 NIT NIT NITD
63A A3, A2 TIS TIS BAO
100A A4 TCP TCP CEO
125A A4 TFP, TCP TFP, TCP DEO
160A A4 TFP, TCP TFP, TCP DEO
200A A4 TFP, TCP TFP, TCP DEO
315A B3 TKF TKF ED
400A B4,B3,B2,B1 TMF TMF ED
630A C2,C1 TTM TTM FF
800A C3,C2,C1 TLM TLM GF

Frequently Asked Questions

  • Q: Is maintenance required for the switch?
    A: No, maintenance is not required except for periodic checks of terminal tightness and fuse links.
  • Q: What should be done in case of hazardous voltage?
    A: Exercise caution and follow safety procedures outlined in the manual to avoid any accidents.

Documents / Resources

SIEMENS 200969-4 Reverse Fixings [pdf] Installation Guide
200969-4 Reverse Fixings, 200969-4, Reverse Fixings, Fixings