PPI Hum iTherm-c Pro Enhanced Temperature Humidity PID Controller User Manual
UTILITY PARAMETERS : PAGE-33
Parameters | Settings (Default Value) |
Compressor Control Strategy![]() |
Dry Bulb SP Dry Bulb PV (Default : Dry Bulb SP)![]() |
Input Type For Temperature![]() |
Refer Table 1 (Default : RTD) |
Signal Low For Temperature![]() |
|
Signal High For Temperature![]() |
|
DC Range Low For Temperature![]() |
199.9 to 999.9 (Default : 100.0) |
DC Range High For Temperature | 25.0 to +25.0°C (Default : 0.0) |
Input Type For %RH![]() |
The above parameters are for %RH input and the descriptions are the same as their temperature counterparts.
Notes
|
Signal High For %RH![]() |
|
DC Range Low For %RH![]() |
|
DC Range High For %RH![]() |
|
Offset For %RH![]() |
TEMPERATURE PARAMETERS : PAGE-10
Parameters | Settings (Default Value) |
Temperature Alarm Band![]() |
0.3 to 25.0°C (Default : 0.5 °C) |
Temperature Alarm Hysteresis![]() |
0.2 to 10.0°C (Default : 0.2 °C) |
Temperature Proportional Band![]() |
0.1 to 999.9°C (Default : 5.0 °C) |
Temperature Integral Time![]() |
0 to 1000 Seconds (Default : 100) |
Temperature Derivative Time![]() |
0 to 250 Seconds (Default : 25) |
Temperature Cycle Time![]() |
0.5 to 25.0 Seconds (in steps of 0.5 secs.) |
RELATIVE HUMIDITY (% RH) PARAMETERS : PAGE-11
Parameters | Settings (Default Value) |
%RH Alarm Band![]() |
0.3 to 25.0% (Default : 2.0) |
%RH Alarm Hysteresis![]() |
0.2 to 10.0% (Default : 2.0) |
%RH Proportional Band![]() |
0.1 to 999.9% (Default : 10.0) |
%RH Integral Time![]() |
0 to 1000 Seconds (Default : 100 |
%RH Derivative Time![]() |
0 to 250 Seconds (Default : 25) |
%RH Cycle Time![]() |
0.5 to 25.0 Seconds (in steps of 0.5 secs.) |
OP3 FUNCTION PARAMETERS : PAGE-13
Parameters | Settings (Default Value) |
Compressor Output Type![]() Alarm Output Type |
Default: For Compressor O/P Type : SSR For Alarm O/P type : None)![]() |
Compressor Setpoint![]() |
0.0 to 50.0°C or 0.0 to 25.0°C |
Compressor Hysteresis![]() |
0.1 to 25.0°C (Default : 0.2) |
Compressor Time Delay![]() |
0.00 to 10.00 Min. Sec (in steps of 5 Seconds) (Default : 00.00) |
SUPERVISORY PARAMETERS : PAGE-12
Parameters | Settings (Default Value) |
SP Adjustment on PAGE-0![]() |
(Default : Enable)![]() |
Self-Tune Command![]() |
(Default : No)![]() |
Water Level-low Detection Logic![]() |
(Default : Open)![]() |
Slave Id![]() |
1 to 127 (Default : 1)![]() |
Baud Rate![]() |
4800 9600 19200 (Default : 9600)![]() |
Parity![]() |
None Even Odd (Default : Even)![]() |
COMPRESSOR OPERATION & POWER INDICATION : PAGE-1
Parameters | Settings (Default Value) |
Compressor Operation Mode![]() |
(Default : Auto)![]() |
Output Power for Temperature Loop![]() |
0 to 100.0% (View Only – Non editable) |
Output Power for %RH Loop![]() |
0 to 100.0% (View Only – Non editable) |
Table 1
Option | What it means | Range (Min. to Max.) |
![]() |
3-wire, RTD Pt100 | -199.9 to 600.0°C / -199.9 to 999.9°F |
![]() |
0 to 20mA DC current | Refer Parameters Signal Low Signal High Range Low Range High |
![]() |
4 to 20mA DC current | |
![]() |
Reserved (Don’t Select) | |
![]() |
0 to 1.25V DC voltage | |
![]() |
0 to 5.0V DC voltage | |
![]() |
0 to 10.0V DC voltage | |
![]() |
1 to 5.0V DC voltage |
FRONT PANEL LAYOUT ELECTRICAL CONNECTIONS
Front Panel
Keys Operation
Symbol | Key | Function |
![]() |
PAGE | Press to enter or exit set-up mode. |
![]() |
DOWN | Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change. |
![]() |
UP | Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change. |
![]() |
ENTER | Press to store the set parameter value and to scroll to the next parameter on the PAGE. |
PV Error Indications
Message | PV Error Type |
![]() |
Over-range(Dry-Bulb Temp. above Max. Range) |
![]() |
Under-range(Dry-Bulb Temp. below Min. Range) |
![]() |
Open(Sensor open / broken) |
ELECTRICAL CONNECTIONS
WIRING CONNECTION
RH SENSORS
R= Red
G= Green
B= Black
- (Humirel RH sensor)
- (IST RH sensor)
- (Capacitance RH sensor)
Enhanced ‘Temperature + Humidity’ PID Controller
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net