PPI Hum iTherm-c Pro Enhanced Temperature Humidity PID Controller User Manual
PPI HumiTherm-c Pro Enhanced Temperature Humidity PID Controller

UTILITY PARAMETERS : PAGE-33

Parameters Settings (Default Value)
Compressor Control Strategyscreen Display Dry Bulb SP Dry Bulb PV (Default : Dry Bulb SP)
screen Display
Input Type For Temperature
screen Display
Refer Table 1 (Default : RTD)
Signal Low For Temperature
Signal High For Temperature
DC Range Low For Temperature
199.9 to 999.9 (Default : 100.0)
DC Range High For Temperature 25.0 to +25.0°C (Default : 0.0)
Input Type For %RH
The above parameters are for %RH input and the descriptions are the same as their temperature counterparts.

Notes

  1. RTD Pt100 input selection is not available for %RH.
  2. The factory default input type is 0 -5 VDC with corresponding signal low, signal high, range low & range high default values.
Signal High For %RH
screen Display
DC Range Low For %RH
DC Range High For %RH
Offset For %RH

TEMPERATURE PARAMETERS : PAGE-10

Parameters Settings (Default Value)
Temperature Alarm Band
0.3 to 25.0°C (Default : 0.5 °C)
Temperature Alarm Hysteresis
screen Display
0.2 to 10.0°C (Default : 0.2 °C)
Temperature Proportional Band
screen Display
0.1 to 999.9°C (Default : 5.0 °C)
Temperature Integral Time
screen Display
0 to 1000 Seconds (Default : 100)
Temperature Derivative Time
screen Display
0 to 250 Seconds (Default : 25)
Temperature Cycle Time
screen Display
0.5 to 25.0 Seconds (in steps of 0.5 secs.)

RELATIVE HUMIDITY (% RH) PARAMETERS : PAGE-11

Parameters Settings (Default Value)
%RH Alarm Band
screen Display
0.3 to 25.0% (Default : 2.0)
%RH Alarm Hysteresis
screen Display
0.2 to 10.0% (Default : 2.0)
%RH Proportional Band
screen Display
0.1 to 999.9% (Default : 10.0)
%RH Integral Time
screen Display
0 to 1000 Seconds (Default : 100
%RH Derivative Time
screen Display
0 to 250 Seconds (Default : 25)
%RH Cycle Time
screen Display
0.5 to 25.0 Seconds (in steps of 0.5 secs.)

OP3 FUNCTION PARAMETERS : PAGE-13

Parameters Settings (Default Value)
Compressor Output Type
screen Display

Alarm Output Type
screen Display

Default: For Compressor O/P Type : SSR For Alarm O/P type : None)
Compressor Setpoint
screen Display
0.0 to 50.0°C or 0.0 to 25.0°C
Compressor Hysteresis
screen Display
0.1 to 25.0°C (Default : 0.2)
Compressor Time Delay
screen Display
0.00 to 10.00 Min. Sec (in steps of 5 Seconds) (Default : 00.00)

SUPERVISORY PARAMETERS : PAGE-12

Parameters Settings (Default Value)
SP Adjustment on PAGE-0
screen Display
(Default : Enable)
screen Display
Self-Tune Command
screen Display
(Default : No)
screen Display
Water Level-low Detection Logic
screen Display
(Default : Open)
screen Display
Slave Id
screen Display
1 to 127 (Default : 1)
screen Display
Baud Rate
screen Display
4800 9600 19200 (Default : 9600)
screen Display
Parity
screen Display
None Even Odd (Default : Even)
screen Display

COMPRESSOR OPERATION & POWER INDICATION : PAGE-1

Parameters Settings (Default Value)
Compressor Operation Mode
screen Display
(Default : Auto)
screen Display
Output Power for Temperature Loop
screen Display
0 to 100.0% (View Only – Non editable)
Output Power for %RH Loop
screen Display
0 to 100.0% (View Only – Non editable)

Table 1

Option What it means Range (Min. to Max.)
screen Display 3-wire, RTD Pt100 -199.9 to 600.0°C / -199.9 to 999.9°F
screen Display 0 to 20mA DC current Refer Parameters Signal Low Signal High Range Low Range High
screen Display 4 to 20mA DC current
screen Display Reserved (Don’t Select)
screen Display 0 to 1.25V DC voltage
screen Display 0 to 5.0V DC voltage
screen Display 0 to 10.0V DC voltage
screen Display 1 to 5.0V DC voltage

FRONT PANEL LAYOUT ELECTRICAL CONNECTIONS

Front Panel
Front Panel

Keys Operation

Symbol Key Function
Symbol PAGE Press to enter or exit set-up mode.
Symbol DOWN Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
Symbol UP Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
Symbol ENTER Press to store the set parameter value and to scroll to the next parameter on the PAGE.

PV Error Indications

Message PV Error Type
screen Display Over-range(Dry-Bulb Temp. above Max. Range)
screen Display Under-range(Dry-Bulb Temp. below Min. Range)
screen Display Open(Sensor open / broken)

ELECTRICAL CONNECTIONS

Electrical Connections

WIRING CONNECTION

RH SENSORS

R= Red
G= Green
B= Black

  • (Humirel RH sensor)
    Wiring Connection
  • (IST RH sensor)
    Wiring Connection
  • (Capacitance RH sensor)
    Wiring Connection

Enhanced ‘Temperature + Humidity’ PID Controller

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net