OEM DIALOG Wireless Control System
SYSTEM MUST BE INSTALLED IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES
For indoor installations.
Risk of Electric Shock. All servicing should be performed by qualified service personnel. To reduce the risks of electric shock disconnect power supplies before servicing.
IMPORTANT SAFEGUARDS
- READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
- Do not use outdoors.
- Do not mount near gas or electric heaters.
- Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
- The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition.
- Do not use this equipment for other than intended use
- Wireless devices are only for lighting control
- Wireless controls cannot be used with portable heating appliances
Installation Instructions
PART NUMBER | DESCRIPTION | ORDER NUMBER | QTY/CARTON |
BT-IFS-A | Bluetooth® Intelligent Fixture™ Sensor | BT-IFS-A010C | 10 |
BT-IFC-A | Bluetooth® Intelligent Fixture™ Controller | BT-IFC-A010C | 10 |
Design Features
Figure 2.1 shows the Intelligent Fixture™ Sensor on the left and the Intelligent Fixture™ Controller on the right.
Specifications
Functionality
General Description
Each device, when installed in a luminaire with a suitable LED driver having 0-10V dimming, Dim-to-OFF capability and an auxiliary power output, performs the following functions:
- LED status indicator for network status and commissioning. For the Intelligent Fixture™ Sensor, the LED also indicates occupancy detection events.
- ON/OFF control, using the DIM-to-OFF feature of a suitably equipped LED driver
- UP/DOWN dimming control
- On-board Reset (press bezel and hold for 10 seconds)
Intelligent Fixture™ Sensor provides:
- Occupancy Control modes (see table below)
- Primary and Secondary Daylight Harvesting (CLC)
When occupancy is detected | When time-out occurs | |
Occupancy | Auto ON | Auto OFF |
Vacancy | Manual ON required | Auto OFF |
Partial ON | Auto ON to 50%
Manual ON to 100% required |
Auto OFF |
Partial OFF | Auto ON to Zone MAX | Transition to Zone MAX |
Power-up Sequences for Non-Networked Devices
Intelligent Fixture™ Sensor & Intelligent Fixture™ Controller:
When initially powered up or if power is cycled, the unassociated sensor will initiate the following start sequence:
- 3 seconds OFF
- 6 seconds at 100%
- 3 seconds OFF
- 3 seconds at 30%
- Transition to 100%
LED will rapidly blink GREEN to indicate unassociated devices
The power-up sequence will fully test the wiring and functionality of the device. For further occupancy testing, wait 45 seconds for the PIR sensor to warm up and do a motion trigger to start the timer. After 20 minutes, the light will time out to OFF (0%). If the power-up sequence does not ocur, check the wring or if the device is associated. If the device is associated, to remove the association, hold down the bezel button for 10 seconds.
Out-of-Box Functionality for Non-Networked Devices
Intelligent Fixture™ Sensor:
- Occupancy mode (Auto ON/Auto OFF)
- Timeout: 20 minutes
- Local occupancy (independent of other sensors)
- 100% Max output level on both output channels
Intelligent Fixture™ Controller:
- Once it is fully powered, the BT-IFC-A will go to 100%.
Dimensions
Dimensions and markings for the Intelligent Fixture™ Sensor and Intelligent Fixture™ Controller are provided below.
Installation Features
- Mounts into a standard 1/2” electrical knockout
- Push-in connection terminals for #20-#26 AWG solid Copper (twist to remove)
- Silicon retention ring
- Out-of-Box functionality (see section #4)
- Push bezel and hold for 10 seconds to implement factory reset
Installation Dimensions
Knock-out Dimensions
CAUTION
DO NOT enclose the lower housing in metal, the antenna is embedded in the face of the product.
Mounting location on the fixture must take into consideration line of sight installation in the ceiling grid. Anything that prevents line of sight is likely to reduce Bluetooth range.
Spacing
Minimum Spacing Requirements:
- A = 0.85 in (21.5 mm)
- B = 1.18 in (30.0 mm)
- C = 1.41 in (35.9 mm)
- D = 0.24 in (6.0 mm)
- E = 1.38 in (35.0 mm)
- F = 0.09 in (2.4 mm)
- M = 0.055 in (1.4mm)
Installation
CAUTION
Risk of Electric Shock. All servicing should be performed by qualified service personnel. To reduce the risks of electric shock disconnect power supplies before servicing.
Installation Advice
- Install the BT-IFS-A in a location where direct light from the fixture does not enter the sensor
- Install the BT-IFS-A vertically with sensor facing directly to the floor or work surface below
- BT-IFC-A may be installed in non-horizontal location. Mounting location on the fixture must take into consideration line of sight installation in the ceiling grid. Anything that prevents line of sight is likely to reduce Bluetooth range.
- Neither device may be installed in a location surrounded by metal; installation in a metallic enclosure will interfere with Bluetooth communications
- Product must be installed in accordance with local electrical codes
Installation Steps
- Refer to Fig. 8.1
- Remove retention ring
- Push sensor through standard ½ inch electrical knockout
- Affix retention ring over device to secure in place
- Connect wires by pushing stripped conductor firmly into terminal and according the appropriate wiring diagram below
- Use #20 – #26 AWG solid copper conductors, stripped to 4 mm
Wiring
Wire Specifications
- #20-#26 AWG solid wire, stripped to 4mm
- Wire ratings must comply with luminaire listing requirements
- Recommended minimums: 600V / 90°C
Wiring Diagrams
Fig. 9.1: Connections for a single-channel / single-driver system
Fig. 9.2: Connections for a single-channel / multi-driver system
Fig. 9.3: Connections for a dual-channel tunable-white, single driver
Approval
- UL Listed: UL916, UL924 (Emergency Lighting – BT-IFC only)
- Plenum Rated: UL2043
- Meets ASHRAE Standard 90.1 requirements
- Meets CEC Title 24 requirements
- Meets WSEC requirements
FCC Part 15
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
FCC Guidelines for Human Exposure
Douglas Lighting Control products comply with FCC radiation exposure limits set forth for an uncontrolled environment. The equipment should be installed and operated with a minimum distance of 20cm between the radiator and all persons.
- Industry Canada Notifications
This device complies with Industry Canada’s license-exempt RSS. Operation is subject to the following two conditions:
- This device may not cause interference; and
- This device must accept any interference, including interference that may cause undesired operation of the device.
IMPORTANT NOTE: Radiation Exposure Statement
Douglas Lighting Controls products comply with IC radiation exposure limits set forth for an uncontrolled environment.
Douglas Lighting Controls products should be installed and operated with a minimum distance of 20cm between the antenna of the radiator and all persons.
PMN: BT-IFC-A and BT-IFS-A
OEM Setup Procedures
Step 1
Inspection: Confirm product ordered matches the product received. Carefully remove control device from packaging. Inspect housing, wire connection terminals, and lens (if BT-IFS) for defects. Confirm each device comes with a silicon retention ring.
Step 2
Mounting: Remove retention ring from control device. Push device through a standard 1/2” electrical knockout until flush with surface. Slide retention ring back down the neck of the device until it meets the backside of the mounting surface. Make sure silicon ring and device are securely sealed and affixed to the luminaire.
Step 3
Wiring: Insert driver wiring leads into appropriate push-in connection terminals on back of control device using #20-#26 AWG solid copper wires stripped to 4mm.
Step 4
Testing: Verify default programming and operation of control device by providing power to the luminaire and observing the following power-up sequence:
- 3 seconds OFF (minimum level for non-”dim-to-off” drivers)
- 6 seconds at 100%
- 3 seconds OFF (minimum level for non-”dim-to-off” drivers)
- 3 seconds at 30%
- Transition to 100%
NOTE: BT-IFS out-of-box functionality is local occupancy sensing (100% Auto On/Auto Off) independent of other sensors with 20 minute timeout. BT-IFC out-of-box functionality is 100% ON.
Step 5 (Optional)
Advanced Configuration: Download the free Douglas Lighting Controls BTCC Commissioning and User App from Apple App store to edit the control device out-of-box settings.
The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth® SIG, Inc. and any use of such marks by Panasonic is under license. Other trademarks and trade names are those of their respective owners.
Toll Free: 877-873-2797 or Direct 604-873-2797 | lighting@douglaslightingcontrols.com
www.douglaslightingcontrols.com
It’s EASY to REACH US…
DOUGLAS LIGHTING CONTROLS
toll-free: 1-877-873-2797
techsupport@universaldouglas.com
www.universalddouglas.com
UNIVERSAL LIGHTING TECHNOLOGIES, INC.
toll free: 1-800-225-5278
tes@universaldouglas.com
www.universalddouglas.com
Dialog® is a Registered Trademark of Douglas Lighting Controls. January 2017 – Subject to change without notice.
The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth® SIG, Inc. and any use of such marks is under license.
Other trademarks and trade names are those of their respective owners.
LIT#: DRCF011421
Rev. 5/17/22
universaldouglas.com
Documents / Resources
![]() |
OEM DIALOG Wireless Control System [pdf] User Guide DIALOG Wireless Control System, DIALOG, Wireless Control System, Control System, DIALOG System |