Specifications

  • Model: CMMB106
  • Input Voltage: 24 Vac or 27-33 Vdc
  • Consumption: 5VA (331mA @ 24 Vac)
  • Universal Inputs: 8 [0.00-10.00Vdc, 10K/20K/30K, on/off (dry contact), 4.00-20.00mA]
  • Digital Inputs: 2 [normally open/closed or direct/reverse]
  • Universal Outputs: 2 [0-10Vdc, pulsed signal (20mA drive), on/off, 4-20mA]
  • Analog Outputs: 2 [0-10Vdc]
  • Digital Relay Outputs: 4
  • BACnet and Modbus Communication
  • Operational Temperature: A = 6.30 / 160 mm, B = 5.00 / 126 mm, C = 2.25 / 57 mm

Product Usage Instructions
Connections and Configurations
Please follow the below instructions for setting up the connections and configurations of the CMMB106:

  • MAC Address (DS2): Set the DIP switches to calculate the MAC address.
  • End of Line (JP3/JP4): Set to 120 Ohms.
  • Network Port (TB10): A+: BACnet/Modbus A+, B-: BACnet/Modbus B-.
  • Universal Inputs (TB12-15): Selectable inputs from AI1 to AI8.
  • Digital Inputs (TB16): Configurable inputs DI1 and DI2.
  • Voltage Input (TB17): COM: Common, 24V: 24 Vac or 27-33 Vdc.

FAQ
How do I configure the MAC address?
To configure the MAC address, set the DIP switches representing binary logic to calculate the MAC address. The default setting is all switches OFF.

Models
CMMB106

Description
The CMMB extends your BACnet or Modbus network when your application requires additional inputs and outputs on a physical  controller. Combining the 20 inputs and outputs of the CMMB with  your Building Automation System provides simple expansion of a new or existing controller and reduces unnecessary costs of additional components.

Features

Power & Communication

  • 24Vac or 30Vdc supply
  • BACnet® MS/TP or Modbus communication port (selectable)

Inputs & Outputs

  • 8 universal inputs
  • 2 digital inputs
  • 2 universal outputs (supervised)
  • 2 analog outputs (supervised)
  • 6 digital outputs (supervised)

Installation

  • 10 override switches to manually control each output
  • LED status indication of each input and output
  • DIN rail mounting
  • Removable, non-strip, raising clamp terminals

neptronic-CMMB106-Remote-I-and-O-Communication-Module- (2)

Network Communication

  • BACnet® MS/TP or Modbus communication port (selectable via DIP switch)
  • Select MAC address via DIP switch or via network BACnet®
  • MS/TP @ 9600, 19200, 38400 or 76800 bps
  • Automatic baud rate detection
  • Automatic device instance configuration
  • Copy & broadcast configuration to other CMMB modules

Modbus

  • Modbus @ 9600, 19200, 38400 or 57600 bps
  • RTU Slave, 8 bits (configurable parity and stop bits)
  • Connects to any Modbus master

Technical Specifications

Connections and Configurations

Specifications CMMB106
Input Voltage 24 Vac or 27-33 Vdc
Consumption 5VA (331mA @ 24 Vac)
Universal Inputs 8 [0.00-10.00Vdc, 10KΩ/20KΩ/30KΩ, on/off (dry contact), 4.00-20.00mA] / 12b hardware resolution with oversampling
Digital Inputs 2 [normally open/closed or direct/reverse]
Universal Outputs 2 [0-10Vdc, pulsed signal (20mA drive), on/off, 4-20mA] / 1mV resolution
Analog Outputs 2 [0-10Vdc] / 1mV resolution
Digital Relay Outputs 6 [normally open/closed, independent common per relay, 5A resistive]
BACnet BACnet® MS/TP @ 9600, 19200, 38400 or 76800 bps (BAS-C)
Modbus Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration:
  • No parity, 2 stop bit
  • Even parity, 1 stop bit
  • Odd parity, 1 stop bit
Communication Connections 24 AWG twisted-shield cable (Belden 9841 or equivalent)
Electrical Connections 0.8 mm2 [18 AWG] minimum
Operational Temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage Temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 to 95% non condensed
Weight 0.4 kg [0.9 lb]
Dimensions neptronic-CMMB106-Remote-I-and-O-Communication-Module- (2)
A = 6.30” / 160 mm
B = 5.00” / 126 mm
C = 2.25” / 57 mm       

Please note that all jumper settings must also be set to the same value through BACnet. Some additional configurations are only available through BACnet (see Network Conditions on page 4).

neptronic-CMMB106-Remote-I-and-O-Communication-Module- (4)MAC Address DIP Switch (DS2)
MAC address for BACnet and Modbus communication, are selectable by DIP switch DS2 using binary logic. BACnet

  • Highest MAC address is 254.
  • Default is all switches OFF = MAC address 0
  • If you do not change device instance in program mode, it will be automatically modified according to the MAC address.
MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance
0 OFF OFF OFF OFF OFF OFF OFF OFF 153000
1 ON OFF OFF OFF OFF OFF OFF OFF 153001
2 OFF ON OFF OFF OFF OFF OFF OFF 153002
3 ON ON OFF OFF OFF OFF OFF OFF 153003
4 OFF OFF ON OFF OFF OFF OFF OFF 153004
126 OFF ON ON ON ON ON ON OFF 153126
254 OFF ON ON ON ON ON ON ON 153254

Modbus

  • Highest MAC address is 247.
  • Default is all switches OFF = MAC address 1
  • MAC address is binary value +1
  • There is no device instance for Modbus.
MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128
0+1 = 1 OFF OFF OFF OFF OFF OFF OFF OFF
1+1 = 2 ON OFF OFF OFF OFF OFF OFF OFF
2+1 = 3 OFF ON OFF OFF OFF OFF OFF OFF
3+1 = 4 ON ON OFF OFF OFF OFF OFF OFF
4+1 = 5 OFF OFF ON OFF OFF OFF OFF OFF
126+1 = 127 OFF ON ON ON ON ON ON OFF
246+1 = 247 OFF ON ON OFF ON ON ON ON

LEDs

  • Power
  • On = Input voltage normal
  • Off = No power

Status

  • Flashing = Normal operation (watchdog)

RX/TX (BACnet)

  • Flashing = Receiving (RX) and/or transmitting (TX) data.

RX/TX (Modbus)

  • Flashing = Receiving (RX) and/or transmitting (TX) data.

Input Status

  • On = Input on
  • Off = Input off
  • Flashing = Input not connected (thermistor setting only)
  • Analog = When Universal Inputs are set to analog values (Vdc, mA, or 10KΩ); the LED intensity corresponds to the input value.
  • For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off.

neptronic-CMMB106-Remote-I-and-O-Communication-Module- (5)

Output Status

  • On = Activated
  • Off = Deactivated
  • Flashing = Output pulsed
  • Analog = When Universal and Analog outputs are set to analog values (Vdc or mA); the LED intensity corresponds to the output value. For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off.

Network Conditions
Please note that all jumper settings must also be set to the same value through BACnet or Modbus. The following is a list of conditions and additional BACnet or Modbus objects.
Universal Inputs (AI1-AI8)

  • When the jumper is set to Thermistor, you can select either °C or °F or you can set the input as a digital on/off input.
  • If the universal input is set as a digital on/off input, you can also set the polarity to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal.
  • When the jumper is set to 0-10 Vdc, you can also set the range to 0-5 Vdc.

Digital Inputs (DI1-DI2)

  • You can set the polarity to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal.

Universal/Analog Outputs (AO1-AO4)

  • You can set the polarity to direct or reverse. For example, in reverse the output range would be 10-0 Vdc instead of 0-10 Vdc.

The polarity applies to all settings 0-10Vdc, 4-20mA, on/off and pulsed.

  • You can also set the outputs to pulsed or digital on/off.
  • A fixed output value can only be modified via BACnet when the override switch is in the “Automatic” position.

Digital Outputs (DO1-DO6)

  • A fixed output (open/closed) can only be modified via BACnet when the override switch is in the “Automatic” position.
  • The displayed text can be set to either Open/Closed, On/Off, or Alarm/Normal (BACnet only).

Supervised Outputs

  • All outputs are fully supervised via BACnet. This provides the actual state of the output including any manual overrides done using the on-board switches.

Pulse Counting Feature
The pulse counting feature enables counting the number of pulses detected by the universal or digital inputs.

  • When an active edge is detected, the Pulse Count is incremented by 1 up to the Prescaler value. When the Prescaler value is reached, the Accumulator is incremented by 1 and the Pulse Count is reset to 0.
  • For digital inputs, there is a 1ms debouncing for the detection of the edge.
  • For universal inputs, a value that is higher than 80% of the input’s saturation confirms a high level. A value that is lower than 20% of the input’s saturation confirms a low level.
  • On both types of inputs, the maximum frequency is 100Hz and the minimum pulse length is 5ms/50%D.C.

neptronic-CMMB106-Remote-I-and-O-Communication-Module- (1)

 

BACnet Objects Table

ID1 Name Description Writable? Notes (* = default)

(= only when UniversalInputxFunction is set to 10K_Type3/G)

 

AI.1

 

UniversalInput1

 

Universal input 1

mode selected by MSV.1

 

Out of service

0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 AI.2  UniversalInput2  Universal input 2

mode selected by MSV.12

 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 AI.3  UniversalInput3  Universal input 3

mode selected by MSV.15

 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 AI.4  UniversalInput4  Universal input 4

mode selected by MSV.48

 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 AI.5  UniversaInput5  Universal input 5

mode selected by MSV.57

 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 AI.6  UniversalInput6  Universal input 6

mode selected by MSV.58

 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 AI.7  UniversalInput7  Universal input 7

mode selected by MSV.59

 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 AI.8  UniversalInput8  Universal input 8

mode selected by MSV.60

 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)or

-40 to 212ºF (302ºF)or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

AV.1 UI1PulseCount Universal input 1 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.2 UI2PulseCount Universal input 2 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.3 UI3PulseCount Universal input 3 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.4 UI4PulseCount Universal input 4 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.5 UI5PulseCount Universal input 5 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.6 UI6PulseCount Universal input 6 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.7 UI7PulseCount Universal input 7 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.8 UI8PulseCount Universal input 8 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.9 DI1PulseCount Digital input 1 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.10 DI2PulseCount Digital input 2 pulse count. Present Value 0 to 16777216, Resolution: 1
AV.11 UI1Accumulator Universal input 1 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.12 UI2Accumulator Universal input 2 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.13 UI3Accumulator Universal input 3 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.14 UI4Accumulator Universal input 4 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.15 UI5Accumulator Universal input 5 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.16 UI6Accumulator Universal input 6 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.17 UI7Accumulator Universal input 7 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.18 UI8Accumulator Universal input 8 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.19 DI1Accumulator Digital input 1 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
AV.20 DI2Accumulator Digital input 2 pulse counter rollovers. Present Value 0 to 16777216, Resolution: 1
ID1 Name Description Writable? Notes (* = default)

(= only when UniversalInputxFunction is set to 10K_Type3/G)

AV.52 AnalogOutput1Min Min. voltage of analog output 1 Present Value 0* Volt to AV.54 | Resolution 0.1 Volt
AV.53 AnalogOutput2Min Min. voltage of analog output 2 Present Value 0* Volt to AV.55 | Resolution 0.1 Volt
AV.54 AnalogOutput1Max Max. voltage of analog output 1 Present Value AV.52 to 10.0* Volt | Resolution 0.1 Volt
AV.55 AnalogOutput2Max Max. voltage of analog output 2 Present Value AV.53 to 10.0* Volt | Resolution 0.1 Volt
AV.72 AnalogOutput1 Analog output 1 value Present Value 0-100% | Resolution 0.1%
AV.73 AnalogOutput2 Analog output 2 value Present Value 0-100% | Resolution 0.1%
AV.118 AnalogOutput3Min Min. voltage of analog output 3 Present Value 0* Volt to AV.120 | Resolution 0.1 Volt
AV.119 AnalogOutput4Min Min. voltage of analog output 4 Present Value 0* Volt to AV.121 | Resolution 0.1 Volt
AV.120 AnalogOutput3Max Max. voltage of analog output 3 Present Value AV.118 to 10.0* Volt | Resolution 0.1 Volt
AV.121 AnalogOutput4Max Max. voltage of analog output 4 Present Value AV.119 to 10.0* Volt | Resolution 0.1 Volt
AV.124 AnalogOutput3 Analog output 3 value Present Value 0-100% | Resolution 1%
AV.125 AnalogOutput4 Analog output 4 value Present Value 0-100% | Resolution 1%
AV.226 UniversalInput1Offset Universal input 1 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.227 UniversalInput2Offset Universal input 2 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.228 UniversalInput3Offset Universal input 3 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.229 UniversalInput4Offset Universal input 4 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.230 UniversalInput5Offset Universal input 5 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.231 UniversalInput6Offset Universal input 6 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.232 UniversalInput7Offset Universal input 7 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.233 UniversalInput8Offset Universal input 8 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.01 ºC/ºF/Volt/mA

AV.468 CopyCfgStartAdd Copy configuration start address Present Value 0-254 Address of first CMMB to copy Available only if BV.101 is set to No
 

AV.469

 

CopyCfgEndAdd

 

Copy configuration end address

 

Present Value

AV.468 – (AV.468 + 64)

Address of last CMMB to copy Available only if BV.101 is set to No

AV.470 CopyCfgResult2 Copy configuration result Present Value AV.468 – AV.469

Result of copy is available on Description property and is available only if BV.101 is set to Yes. Results: Succeed, Prog_Error, Type_Error, Model_Error, FW_Error, Mem_Error, Size_Error, Comm_Error, SlaveDevice, InProgress, AllSucceed

AV.500 U1_MinInputValue Universal input 1 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.501 U1_MaxInputValue Universal input 1 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.502 U1_MinValue Universal input 1 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.503 U1_MaxValue Universal input 1 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.504 U2_MinInputValue Universal input 2 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.505 U2_MaxInputValue Universal input 2 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.506 U2_MinValue Universal input 2 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.507 U2_MaxValue Universal input 2 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.508 U3_MinInputValue Universal input 3 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.509 U3_MaxInputValue Universal input 3 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.510 U3_MinValue Universal input 3 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01

Write 526address in present value, result will be available in description.

ID1 Name Description Writable? Notes (* = default)

(= only when UniversalInputxFunction is set to 10K_Type3/G)

AV.511 U3_MaxValue Universal input 3 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.512 U4_MinInputValue Universal input 4 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.513 U4_MaxInputValue Universal input 4 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.514 U4_MinValue Universal input 4 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.515 U4_MaxValue Universal input 4 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.516 U5_MinInputValue Universal input 5 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.517 U5_MaxInputValue Universal input 5 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.518 U5_MinValue Universal input 5 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.519 U5_MaxValue Universal input 5 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.520 U6_MinInputValue Universal input 6 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.521 U6_MaxInputValue Universal input 6 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.522 U6_MinValue Universal input 6 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.523 U6_MaxValue Universal input 6 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.524 U7_MinInputValue Universal input 7 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.525 U7_MaxInputValue Universal input 7 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.526 U7_MinValue Universal input 7 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.527 U7_MaxValue Universal input 7 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.528 U8_MinInputValue Universal input 8 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.529 U8_MaxInputValue Universal input 8 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.530 U8_MinValue Universal input 8 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.531 U8_MaxValue Universal input 8 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01
AV.532 AO1FailsafePreset Analog output 1 failsafe preset value Present Value 0 to 100%, Resolution: 0.1%
AV.533 AO2FailsafePreset Analog output 2 failsafe preset value Present Value 0 to 100%, Resolution: 0.1%
AV.534 AO3FailsafePreset Analog output 3 failsafe preset value Present Value 0 to 100%, Resolution: 0.1%
AV.535 AO4FailsafePreset Analog output 4 failsafe preset value Present Value 0 to 100%, Resolution: 0.1%
AV.536 TimeoutValue Network Timeout value Present Value 5 to 600 sec, Resolution: 5 sec
AV.537 UI1_PulsePrescaler Universal input 1 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.538 UI2_PulsePrescaler Universal input 2 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.539 UI3_PulsePrescaler Universal input 3 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.540 UI4_PulsePrescaler Universal input 4 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.541 UI5_PulsePrescaler Universal input 5 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.542 UI6_PulsePrescaler Universal input 6 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
ID1 Name Description Writable? Notes (* = default)

(= only when UniversalInputxFunction is set to 10K_Type3/G)

AV.543 UI7_PulsePrescaler Universal input 7 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.544 UI8_PulsePrescaler Universal input 8 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.545 DI1_PulsePrescaler Digital input 1 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
AV.546 DI2_PulsePrescaler Digital input 2 pulse counter rollover threshold. Present Value 0 to 16777216, Resolution: 1
 

BI.1

 

DigitalInput1

 

Digital input 1 status

 

Out of service

0= Open / Ouvert * 1= Close / Fermé

Text depends of selection in MSV.76

 

BI.2

 

DigitalInput2

 

Digital input 2 status

 

Out of service

0= Open / Ouvert * 1= Close / Fermé

Text depends of selection in MSV.77

 

BV.22

 

ContactOutput1

 

Digital output 1 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.66
 

BV.23

 

ContactOutput2

 

Digital output 2 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.67
 

BV.24

 

ContactOutput3

 

Digital output 3 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.68
 

BV.25

 

ContactOutput4

 

Digital output 4 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.69
 

BV.26

 

ContactOutput5

 

Digital output 5 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.70
 

BV.27

 

ContactOutput6

 

Digital output 6 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.71
BV.33 DigitalInput1Polarity Polarity of digital input 1 Present Value 0= Direct *

1= Reverse

BV.34 DigitalInput2Polarity Polarity of digital input 2 Present Value 0= Direct *

1= Reverse

BV.66 AnalogOutput1Direction Polarity of analog output 1 Present Value 0= Direct *

1= Reverse

BV.67 AnalogOutput2Direction Polarity of analog output 2 Present Value 0= Direct *

1= Reverse

BV.68 AnalogOutput3Direction Polarity of analog output 3 Present Value 0= Direct *

1= Reverse

BV.69 AnalogOutput4Direction Polarity of analog output 4 Present Value 0= Direct *

1= Reverse

BV.93 UI1_DI_Polarity Polarity of universal input 1 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.94 UI2_DI_Polarity Polarity of universal input 2 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.95 UI3_DI_Polarity Polarity of universal input 3 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.96 UI4_DI_Polarity Polarity of universal input 4 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.97 UI5_DI_Polarity Polarity of universal input 5 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.98 UI6_DI_Polarity Polarity of universal input 6 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.99 UI7_DI_Polarity Polarity of universal input 7 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.100 UI8_DI_Polarity Polarity of universal input 8 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.101 CopyCfgExecute Start or stop copy configuration  

Present Value

0= No *

1= Yes

Start copy and give results, must be reset by user.

BV.102 SystemUnit Select the unit system to use on the device Present Value 0= Celsius *

1= Fahrenheit

D1 Name Description Writable? Notes (* = default)

(= only when UniversalInputxFunction is set to 10K_Type3/G)

BV.103 Inhibit Output Override Inhibit the override of the outputs Present Value 0= Off *

1= On

BV.104 TimeoutStatus Network timeout status 0= Inactive *

1= Active

MSV.1 UniversalInput1Function Selected analog input 1 mode Present Value 1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

 

 

 

 

 

MSV.12

 

 

 

 

 

UniversalInput2Function

 

 

 

 

 

Selected analog input 2 mode

 

 

 

 

 

Present Value

1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

MSV.15 UniversalInput3Function Selected analog input 3 mode  

Present Value

1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

MSV.48 UniversalInput4Function Selected analog input 4 mode Present Value 1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

MSV.54 AnalogOutput1Mode Select analog output 1 mode Present Value 1= Analog *

2= On_Off

3= Pulsing

MSV.55 AnalogOutput2Mode Select analog output 2 mode Present Value 1= Analog *

2= On_Off

3= Pulsing

MSV.57 UniversalInput5Function Selected analog input 5 mode Present Value 1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

ID1 Name Description Writable? Notes (* = default)

(= only when UniversalInputxFunction is set to 10K_Type3/G)

 

MSV.58

 

UniversalInput6unction

Selected analog input 6 mode  

 

 

 

 

Present Value

1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

 

 

 

 

 

MSV.59

 

 

 

 

 

UniversalInput7Function

 

 

 

 

 

Selected analog input 7 mode

 

 

 

 

 

Present Value

1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

 

 

 

 

 

MSV.60

 

 

 

 

 

UniversalInput8Function

 

 

 

 

 

Selected analog input 8 mode

 

 

 

 

 

Present Value

1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= DigitalInput

10= ScaledValue_Volt

11= ScaledValue_mA

12= 10K_NTC_Carel

 

 

MSV.66

 

 

ContactOutput1Text

 

Contact output 1 inactive & active text

 

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

 

MSV.67

 

 

ContactOutput2Text

 

Contact output 2 inactive & active text

 

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

 

MSV.68

 

 

ContactOutput3Text

 

Contact output 3 inactive & active text

 

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

 

MSV.69

 

 

ContactOutput4Text

 

Contact output 4 inactive & active text

 

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

 

MSV.70

 

 

ContactOutput5Text

 

Contact output 5 inactive & active text

 

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

 

MSV.71

 

 

ContactOutput6Text

 

Contact output 6 inactive & active text

 

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

MSV.76

 

DigitalInput1Text

 

Digital input 1 inactive & active text

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

ID1 Name Description Writable? Notes (* = default)

(= only when UniversalInputxFunction is set to 10K_Type3/G)

 

MSV.77

 

DigitalInput2Text

 

Digital input 2 inactive & active text

 

Present Value

1= Open_Close *

2= Ouvert_Fermé

 

MSV.81

 

AnalogOutput3Mode

 

Select analog output 3 mode

 

Present Value

1= Analog *

2= On_Off

3= Pulsing

4= 4_20mA

 

MSV.82

 

AnalogOutput4Mode

 

Select analog output 4 mode

 

Present Value

1= Analog *

2= On_Off

3= Pulsing

4= 4_20mA

 

MSV.83

 

CfgBO1FailsafeMode

Configuration of the binary output 1 failsafe mode  

Present Value

1= LastState *

2= Open

3= Close

 

MSV.84

 

CfgBO2FailsafeMode

Configuration of the binary output 2 failsafe mode  

Present Value

1= LastState *

2= Open

3= Close

 

MSV.85

 

CfgBO3FailsafeMode

Configuration of the binary output 3 failsafe mode  

Present Value

1= LastState *

2= Open

3= Close

 

MSV.86

 

CfgBO4FailsafeMode

Configuration of the binary output 4 failsafe mode  

Present Value

1= LastState *

2= Open

3= Close

 

MSV.87

 

CfgBO5FailsafeMode

Configuration of the binary output 5 failsafe mode  

Present Value

1= LastState *

2= Open

3= Close

 

MSV.88

 

CfgBO6FailsafeMode

Configuration of the binary output 6 failsafe mode  

Present Value

1= LastState *

2= Open

3= Close

 

MSV.89

 

CfgAO1FailsafeMode

Configuration of the analog output 1 failsafe mode  

Present Value

1= LastState *

2= Preset

 

MSV.90

 

CfgAO2FailsafeMode

Configuration of the analog output 2 failsafe mode  

Present Value

1= LastState *

2= Preset

 

MSV.91

 

CfgAO3FailsafeMode

Configuration of the analog output 3 failsafe mode  

Present Value

1= LastState *

2= Preset

 

MSV.92

 

CfgAO4FailsafeMode

Configuration of the analog output 4 failsafe mode  

Present Value

1= LastState *

2= Preset

Modbus Registers

  • Register address
    • As per protocol base (base 0); for PLC add 1 to protocol base.
    • As per holding register (base 40001)
  • Functions :
    • 03 Read Holding Register
    • 06 Write Single Register
    • 16 Write Multiple Registers
  • Error Codes :
    • 02 Illegal Data Address
    • 03 Illegal Value
    • 06 Slave Device Busy
  • W = Writable register, [blank] = read only.
    No Real number in modbus register, use scale to calculate real number. Register = Real number * Scale => Real number = Register / Scale. Scale could be 1, 10 or 100
    Attention when writing a register that contains a bit string. If bit is writable (conditional or not), the write will always be accepted. If bit is reserved or not writable, the write will be ignored and will keep its actual state.
  • Use READ-MODIFY-WRITE sequence.
Protocol Base  

Holding Register

Description Data Type MSB/LSB Units/Values Writable Default Value
MB LB
0 40001 MSB = Neptronic Device ID LSB = MAC Address Unsigned 105 (69h) [1..247]

(1h- F7h)

* MAC address is writable if all DIP switches of DS2 are OFF. W* 69h 1h
 

 

1

 

 

40002

 

 

Device Baud Rate

 

Unsigned Scale 0.01

[96] [192] [384] [576] 9,600

19,200

38,400

57,600

 

 

96

 

 

2

 

 

40003

COM Port Configuration

IMPORTANT: The default value is “no parity, 2 stop bits”. To change the value, you must set DIP switch DS1-3 to OFF. If set to ON, it will always remain at the default value. Refer to Connections and

Configurations on page 2.

 

 

Unsigned

[0..2] 0 = no parity, 2 stop bits 1 = even parity, 1 stop bit 2 = odd parity, 1 stop bit  

 

W

 

 

0

3 40004 Product Name (characters 8 & 7) 2 x ASCII char 8 char 7 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 43h [C] 40h [M]
4 40005 Product Name (characters 6 & 5) 2 x ASCII char 6 char 5 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 40h [M] 42h [B]
5 40006 Product Name (characters 4 & 3) 2 x ASCII char 4 char 3 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 31h [1] 30h [0]
6 40007 Product Name (characters 2 & 1) 2 x ASCII char 2 char 1 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 36h [6] 20h [ ]
7 40008 Firmware Version Unsigned Scale 100 115 1.15 115
8 40009 Application Version Unsigned Scale 100 103 1.03 103
Protocol Base  

Holding Register

Description Data Type MSB/LSB Units/Values Writable Default Value
MB LB
 

9

 

40010

 

System Status 1

 

Bit String

  [B0..B15] 0 = Normal

1 = Fault

– – – – – – – – – – – – – – – – – – –

B0 = System operation

 

0000, 0001, 1111, 1110b

10 40011 System Status 2 Bit String [B0..B15] Always 0 0000, 0000, 0000, 0000b
11 40012 Analog Input 1 0-10V:     Type: Unsigned,   Scale:100,     Unit: Volt,   Range: 0.00-10.00V,                                                                                                                                 Resolution: 0.01 4-20mA:  Type: Unsigned,   Scale:100,   Unit: mA,   Range: 4.00-20.00 mA,    Resolution: 0.01 10K Type 3A1, 10K Type 4AI, 10K Type 2, 20K Type 6AI, 30K Type 6AI:

Type: Signed,     Scale:100,     Unit: ºC,     Range: -40.00 – 100.00 ºC, Resolution: 0.01 Type: Signed, Scale:100, Unit: ºF,            Range: -40.00 – 212.00 ºF, Resolution: 0.02

10K Type 3/G:

Type: Signed,     Scale:100,     Unit: ºC,     Range: -40.00 – 150.00 ºC, Resolution: 0.01 Type: Signed, Scale:100, Unit: ºF,            Range: -40.00 – 302.00 ºF, Resolution: 0.02

DI:           Type: Unsigned,  Scale:1,         No Unit,     Range: 0-1,                Resolution: 1 Scaled Input (Volt), Scaled Input (mA):

Type: Unsigned, Scale:1 ,       No Unit,    Range: Ux_MinValue – Ux_MaxValue, Resolution: 1

32767
12 40013 Analog Input 2 32767
13 40014 Analog Input 3 32767
14 40015 Analog Input 4 32767
15 40016 Analog Input 5 32767
16 40017 Analog Input 6 32767
17 40018 Analog Input 7 32767
18 40019 Analog Input 8 32767
19 40020 Digital Input Bit String [B0..B1] B0 = DI1 B1 = DI2 0000, 0000, 0000, 0000b
20 40021 Analog Output 1  

 

Unsigned Scale 10

 

 

[0..1000]
 

 

Unit: %,      Range: 0-100.0%,           Resolution: 0.1

 

 

W

0
21 40022 Analog Output 2 0
22 40023 Analog Output 3 0
23 40024 Analog Output 4 0
 

24

 

40025

 

Relay Output

 

Bit String

  [B0..B5] B0 = Relay 1  B1 = Relay 2

B2 = Relay 3 B3 = Relay 4 B4 = Relay 5  B5 = Relay 6

 

W

 

0000, 0000, 0000, 0000b

 

 

25

 

 

40026

 

Output Overwrite Status

Indicates that the output is overridden by the hardware switch (SW5-SW10).

 

 

Bit String

 

 

[B0..B9]
B0 = Relay 1 B1 = Relay 2 B2 = Relay 3 B3 = Relay 4 B4 = Relay 5 B5 = Relay 6 B6 = AO1 B7 = AO2

B8 = AO3   B9 = AO4

 

 

0000, 0000, 0000, 0000b

26 40027 Universal Input 1 Function  

 

 

Unsigned

 

 

 

[1..12]
1= 0_10Volt

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

 

 

 

W

3
27 40028 Universal Input 2 Function 3
28 40029 Universal Input 3 Function 3
29 40030 Universal Input 4 Function 3
30 40031 Universal Input 5 Function 3
 

Protocol Base

 

Holding Register

Description Data Type MSB/LSB Units/Values Writable Default Value
MB LB
 

4

 

 

 

40055

System Options

 

* = digital input mode only

it String  

 

[B0..B15]
0 = Direct                                    0 = Off

1 = Reverse                                1 = On

– – – – – – – – – – – – – – – – – – –            – – – – – – – – – – – – – – – – – – –

B0 =     AO1 polarity                  B14 = Inhibit Output Override B1 =     AO2 polarity                  – – – – – – – – – – – – – – – – – – –

B2 =     AO3 polarity                  0 = Celsius

B3 =     AO4 polarity                  1 = Fahrenheit

B4 =     AI1 polarity *                  – – – – – – – – – – – – – – – – – – –

B5 =     AI2 polarity *                  B15 = System Unit B6 =     AI3 polarity *

B7 = AI4 polarity * B8 = AI5 polarity * B9 = AI6 polarity * B10 = AI7 polarity * B11 = AI8 polarity * B12 = DI1 polarity

B13 =   DI2 polarity

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

0000, 0000, 0000, 0000b

55 40056 Universal Input 1 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 56, Resolution: 0.01 Unit: mA, Range: 4.00 mA – Register 56, Resolution: 0.01 W 0
56 40057 Universal Input 1 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 55 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 55 – 20.00 mA, Resolution: 0.01 W 1000
57 40058 Universal Input 1 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 58, Resolution: 0.01 W 0
58 40059 Universal Input 1 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 57 – 32767, Resolution: 0.01 W 1000
59 40060 Universal Input 2 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 60, Resolution: 0.01 Unit: mA, Range: 4.00 mA – Register 60, Resolution: 0.01 W 0
60 40061 Universal Input 2 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 59 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 59 – 20.00 mA, Resolution: 0.01 W 1000
61 40062 Universal Input 2 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 62, Resolution: 0.01 W 0
62 40063 Universal Input 2 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 61 – 32767, Resolution: 0.01 W 1000
63 40064 Universal Input 3 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 64, Resolution: 0.01 Unit: mA, Range: 4.00 mA – Register 64, Resolution: 0.01 W 0
64 40065 Universal Input 3 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 63 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 63 – 20.00 mA, Resolution: 0.01 W 1000
65 40066 Universal Input 3 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 66, Resolution: 0.01 W 0
66 40067 Universal Input 3 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 65 – 32767, Resolution: 0.01 W 1000
67 40068 Universal Input 4 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 68, Resolution: 0.01 Unit: mA, Range: 4.00 mA – Register 68, Resolution: 0.01 W 0
Protocol Base Holding Register Description Data Type MSB/LSB Units/Values Writable Default Value
MB LB
68 40069 Universal Input 4 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 67 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 67 – 20.00 mA, Resolution: 0.01 W 1000
69 40070 Universal Input 4 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 70, Resolution: 0.01 W 0
70 40071 Universal Input 4 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 69 – 32767, Resolution: 0.01 W 1000
71 40072 Universal Input 5 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 72, Resolution: 0.01 Unit: mA, Range: 4.00 mA – Register 72, Resolution: 0.01 W 0
72 40073 Universal Input 5 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 71 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 71 – 20.00 mA, Resolution: 0.01 W 1000
73 40074 Universal Input 5 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 66, Resolution: 0.01 W 0
74 40075 Universal Input 5 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 65 – 32767, Resolution: 0.01 W 1000
75 40076 Universal Input 6 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 64, Resolution: 0.01 Unit: mA, Range : 4.00 mA – Register 64, Resolution: 0.01 W 0
76 40077 Universal Input 6 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 63 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 63 – 20.00 mA, Resolution: 0.01 W 1000
77 40078 Universal Input 6 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 78, Resolution: 0.01 W 0
78 40079 Universal Input 6 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 77 – 32767, Resolution: 0.01 W 1000
79 40080 Universal Input 7 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 80, Resolution: 0.01 Unit: mA, Range: 4.00 mA – Register 80, Resolution: 0.01 W 0
80 40081 Universal Input 7 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 79 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 79 – 20.00 mA, Resolution: 0.01 W 1000
81 40082 Universal Input 7 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 82, Resolution: 0.01 W 0
82 40083 Universal Input 7 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 81 – 32767, Resolution: 0.01 W 1000
83 40084 Universal Input 8 Minimum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: 0.00 V – Register 84, Resolution: 0.01 Unit: mA, Range: 4.00 mA – Register 84, Resolution: 0.01 W 0
84 40085 Universal Input 8 Maximum Input Value Unsigned Scale 100 [0..100] Unit: Volt, Range: Register 83 – 10.00 V, Resolution: 0.01 Unit: mA, Range: Register 83 – 20.00 mA, Resolution: 0.01 W 1000
85 40086 Universal Input 8 Minimum Value Signed Scale 1 [-32768…32767] No Unit, Range: -32768 – Register 86, Resolution: 0.01 W 0
86 40087 Universal Input 8 Maximum Value Signed Scale 1 [-32768…32767] No Unit, Range: Register 85 – 32767, Resolution: 0.01 W 1000
 

87

 

40088

 

Binary Output 1 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

Protocol Base

 

Holding Register

Description Data Type MSB/LSB Units/Values Writable Default Value
MB LB
 

88

 

40089

 

Binary Output 2 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

89

 

40090

 

Binary Output 3 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

90

 

40091

 

Binary Output 4 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

91

 

40092

 

Binary Output 5 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

92

 

40093

 

Binary Output 6 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

93 40094 Analog Output 1 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
94 40095 Analog Output 1 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
95 40096 Analog Output 2 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
96 40097 Analog Output 2 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
97 40098 Analog Output 3 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
98 40099 Analog Output 3 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
99 40100 Analog Output 4 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
100 40101 Analog Output 4 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
101 40102 Timeout Status Unsigned [0,1] 0= Inactive

1= Active

0
102 40103 Network Timeout Value Unsigned Scale 1 [5..600] Unit: Seconds (sec), Range: 5 – 600 sec, Resolution: 5 sec W 30
103 40104 UI1 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
104 40105 UI1 Pulse Prescaler (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
105 40106 UI2 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
106 40107 UI2 Pulse Prescaler (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
107 40108 UI3 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
108 40109 UI3 Pulse Prescaler (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
109 40110 UI4 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
 

Protocol Base

 

Holding Register

Description  

Data Type

 

MSB/LSB

 

Units/Values

 

Writable

Default Value
MB LB
 

88

 

40089

 

Binary Output 2 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

89

 

40090

 

Binary Output 3 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

90

 

40091

 

Binary Output 4 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

91

 

40092

 

Binary Output 5 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

 

92

 

40093

 

Binary Output 6 Fail Safe Mode

 

Unsigned

  [1..3] 1= LastState

2= Open

3= Close

 

W

 

1

93 40094 Analog Output 1 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
94 40095 Analog Output 1 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
95 40096 Analog Output 2 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
96 40097 Analog Output 2 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
97 40098 Analog Output 3 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
98 40099 Analog Output 3 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
99 40100 Analog Output 4 Fail Safe Mode Unsigned [1,2] 1= LastState

2= Preset

W 1
100 40101 Analog Output 4 Fail Safe Preset Value Unsigned Scale 10 [0..1000] Unit: %, Range: 0 – 100.00 %, Resolution: 0.1 W 100
101 40102 Timeout Status Unsigned [0,1] 0= Inactive

1= Active

0
102 40103 Network Timeout Value Unsigned Scale 1 [5..600] Unit: Seconds (sec), Range: 5 – 600 sec, Resolution: 5 sec W 30
103 40104 UI1 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
104 40105 UI1 Pulse Prescaler (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
105 40106 UI2 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
106 40107 UI2 Pulse Prescaler (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
107 40108 UI3 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
108 40109 UI3 Pulse Prescaler (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
109 40110 UI4 Pulse Prescaler (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
Protocol Base Holding Register Description Data Type MSB/LSB Units/Values Writable Default Value
MB LB
139 40140 DI1 Pulse Count (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
140 40141 DI1 Pulse Count (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
141 40142 DI2 Pulse Count (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
142 40143 DI1 Pulse Count (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
143 40144 UI1 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
144 40145 UI1 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
145 40146 UI2 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
146 40147 UI2 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
147 40148 UI3 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
148 40149 UI3 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
149 40150 UI4 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
150 40151 UI4 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
151 40152 UI5 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
152 40153 UI5 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
153 40154 UI6 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
154 40155 UI6 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
155 40156 UI7 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
156 40157 UI7 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
157 40158 UI8 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
158 40159 UI8 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
159 40160 DI1 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
160 40161 DI1 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1
161 40162 DI2 Accumulator (0) Unsigned Scale 1 [0…16777216] Range: 0 to 16777216, Resolution: 1 W 0
162 40163 DI2 Accumulator (1) [0…16777216] Range: 0 to 16777216, Resolution: 1

Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic
authorized distributor, please consult www.neptronic.com.
400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com

Toll free in North America: 1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)

Documents / Resources

neptronic CMMB106 Remote I and O Communication Module [pdf] Instruction Manual
CMMB106 Remote I and O Communication Module, CMMB106, Remote I and O Communication Module, I and O Communication Module, Communication Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *