LILYTECH-LOGO

LILYTECH ZL-7816A Humidity and Temperature Controller

LILYTECH-ZL-7816A-Humidity-and-Temperature-Controller-PRODUCT

Introduction

  • Easy to set.
  • Professional sensor.
  • Sensor cable can be extended to 50 meters.

Specification

  • Sensor precision: Humidity ±3%, Temperature ±
  • Set and display range: Temperature 0.0 ~ 80.0 °C C, humidity 0 ~ 99.9%RH
  • Working environment: 10 ~ 45 °C C, 5 ~ 95%RH without dew P
  • power consumption: 2 watts P
  • power supply: 12Vac, or 12Vdc
  • Outputs: 7A / 250Vac each
  • Sensor option: ZL SHr04 or ZL SHr05

Setting

LILYTECH-ZL-7816A-Humidity-and-Temperature-Controller-FIG-1 (1)

  • Keep 〖S 〗depressed for 2 seconds, and enter into setting status:
  • The up window displays the parameter code.
  • The bottom window displays the value of the code.
  • Press〖S 〗to select the code. See the parameter table below for codes.
  • Press〖▲ 〗or 〖▼ 〗 to set the value (keeping depressed could fast set).
  • Keep〖S 〗depressed for 2 seconds to exit, and the settings are saved.
    • Note: The status will exit if no key operation for 30 seconds, and the settings will be saved.

Parameter table:

Code Function Range Remark Factory set
tC Cooling or heating Co/HE Co: cooling, HE: heating HE
tSP Setpoint 0.0 ~ 99.9°C °C 37.5
td Hysteresis 0.0 ~ 30.0°C   0.1
tCA Calibration -5.0 ~ 5.0°C 0.0: no calibration 0.0
tHA Too high alarm 0.0 ~ 30.0°C 0.0: disable alarm 0.5
tLA Too low alarm 0.0 ~ 30.0°C 0.0: disable alarm 1.5
HC Humidify or dehumidify H/P H: humidify, P: dehumidify H
HSP Setpoint 0.0 ~ 99.9%RH   52.0
Hd Hysteresis 0.0 ~ 30.0%RH   0.2
HCA Calibration -5.0 ~ 5.0%RH 0.0: no calibration 0.0
HAHA Too wet alarm 0.0 ~ 30.0%RH 0.0: disable alarm 10.0
HLA Too dry alarm 0.0 ~ 30.0%RH 0.0: disable alarm 5.0
SHr Sensor option 4/5 4: ZL-SHR04, 5: ZL-SHR05 5

Control

Temperature control

  • Heating control
    • When parameter tC = HE, heating control.
    • When temperature ≤ tSP – td, temperature output is energized.
    • When temperature ≥ tSP, temperature output de-energized.
  • Cooling control
    • When parameter tC = CO, cooling control.
    • When temperature ≥ tSP + td, temperature output is energized.
    • When temperature ≤ tSP, temperature output de-energized.

Humidity control

  • Humidify
    • When parameter HC = H, humidifying control.
    • When humidity ≤ HSP – Hd, humidity output is energized.
    • When humidity ≥ HSP, humidity output de-energized.
  • Dehumidify
    • When parameter HC = p, dehumidifying control.
    • When humidity ≥ HSP + Hd, humidity output is energized.
    • When humidity ≤ HSP, humidity output de-energized.

Alarming

  • Over temperature alarm
    • When temperature ≥ tSP + tHA, high-temperature alarms, the up window displays ”tHi”.
    • When temperature ≤ tSP – tLA, low-temperature alarms, the up window displays ”tLo”.
  • Over wet alarm
    • When humidity ≥ HSP + HHA, high humidity alarms, the bottom window displays ”HHi”.
    • When humidity ≤ HSP – HLA, low humidity alarms, the bottom window displays ”HLo”.
  • Calibration
    • The sensed temperature and humidity can be calibrated by set parameter TCA for temperature error,

HCA for humidity error

  • Display
    • When the sensor has a problem or is not connected the display ”–.”.
    • When the temperature output is energized, its output lamp is on. When it is de-energized, the lamp is off.
    • When humidity output is energized, its output lamp is on. When it is de-energized, the lamp is off.
  • Restore Setting
    • Keep 〖▲ 〗and 〖▼ 〗depressed simultaneously for 2 seconds, and display ”UnL”. Then press 〖▼ 〗3 times, there will be a long beep, and the settings will be restored to factory default settings.
  • Attention
    • Install by a certified technician. The outputs are not allowed to drive heavier loads than their specification.
    • The PCB voids are to be exposed to super wet conditions.

Wiring

LILYTECH-ZL-7816A-Humidity-and-Temperature-Controller-FIG-1 (2)

Installation

LILYTECH-ZL-7816A-Humidity-and-Temperature-Controller-FIG-1 (3)

Suzhou Lily Tech. Co., Ltd.

Documents / Resources

LILYTECH ZL-7816A Humidity and Temperature Controller [pdf] Installation Guide
ZL-7816A Humidity and Temperature Controller, ZL-7816A, Humidity and Temperature Controller, Temperature Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *