LILYTECH ZL-7816A Humidity and Temperature Controller
Introduction
- Easy to set.
- Professional sensor.
- Sensor cable can be extended to 50 meters.
Specification
- Sensor precision: Humidity ±3%, Temperature ±
- Set and display range: Temperature 0.0 ~ 80.0 °C C, humidity 0 ~ 99.9%RH
- Working environment: 10 ~ 45 °C C, 5 ~ 95%RH without dew P
- power consumption: 2 watts P
- power supply: 12Vac, or 12Vdc
- Outputs: 7A / 250Vac each
- Sensor option: ZL SHr04 or ZL SHr05
Setting
- Keep 〖S 〗depressed for 2 seconds, and enter into setting status:
- The up window displays the parameter code.
- The bottom window displays the value of the code.
- Press〖S 〗to select the code. See the parameter table below for codes.
- Press〖▲ 〗or 〖▼ 〗 to set the value (keeping depressed could fast set).
- Keep〖S 〗depressed for 2 seconds to exit, and the settings are saved.
- Note: The status will exit if no key operation for 30 seconds, and the settings will be saved.
Parameter table:
Code | Function | Range | Remark | Factory set |
tC | Cooling or heating | Co/HE | Co: cooling, HE: heating | HE |
tSP | Setpoint | 0.0 ~ 99.9°C | °C | 37.5 |
td | Hysteresis | 0.0 ~ 30.0°C | 0.1 | |
tCA | Calibration | -5.0 ~ 5.0°C | 0.0: no calibration | 0.0 |
tHA | Too high alarm | 0.0 ~ 30.0°C | 0.0: disable alarm | 0.5 |
tLA | Too low alarm | 0.0 ~ 30.0°C | 0.0: disable alarm | 1.5 |
HC | Humidify or dehumidify | H/P | H: humidify, P: dehumidify | H |
HSP | Setpoint | 0.0 ~ 99.9%RH | 52.0 | |
Hd | Hysteresis | 0.0 ~ 30.0%RH | 0.2 | |
HCA | Calibration | -5.0 ~ 5.0%RH | 0.0: no calibration | 0.0 |
HAHA | Too wet alarm | 0.0 ~ 30.0%RH | 0.0: disable alarm | 10.0 |
HLA | Too dry alarm | 0.0 ~ 30.0%RH | 0.0: disable alarm | 5.0 |
SHr | Sensor option | 4/5 | 4: ZL-SHR04, 5: ZL-SHR05 | 5 |
Control
Temperature control
- Heating control
- When parameter tC = HE, heating control.
- When temperature ≤ tSP – td, temperature output is energized.
- When temperature ≥ tSP, temperature output de-energized.
- Cooling control
- When parameter tC = CO, cooling control.
- When temperature ≥ tSP + td, temperature output is energized.
- When temperature ≤ tSP, temperature output de-energized.
Humidity control
- Humidify
- When parameter HC = H, humidifying control.
- When humidity ≤ HSP – Hd, humidity output is energized.
- When humidity ≥ HSP, humidity output de-energized.
- Dehumidify
- When parameter HC = p, dehumidifying control.
- When humidity ≥ HSP + Hd, humidity output is energized.
- When humidity ≤ HSP, humidity output de-energized.
Alarming
- Over temperature alarm
- When temperature ≥ tSP + tHA, high-temperature alarms, the up window displays ”tHi”.
- When temperature ≤ tSP – tLA, low-temperature alarms, the up window displays ”tLo”.
- Over wet alarm
- When humidity ≥ HSP + HHA, high humidity alarms, the bottom window displays ”HHi”.
- When humidity ≤ HSP – HLA, low humidity alarms, the bottom window displays ”HLo”.
- Calibration
- The sensed temperature and humidity can be calibrated by set parameter TCA for temperature error,
HCA for humidity error
- Display
- When the sensor has a problem or is not connected the display ”–.”.
- When the temperature output is energized, its output lamp is on. When it is de-energized, the lamp is off.
- When humidity output is energized, its output lamp is on. When it is de-energized, the lamp is off.
- Restore Setting
- Keep 〖▲ 〗and 〖▼ 〗depressed simultaneously for 2 seconds, and display ”UnL”. Then press 〖▼ 〗3 times, there will be a long beep, and the settings will be restored to factory default settings.
- Attention
- Install by a certified technician. The outputs are not allowed to drive heavier loads than their specification.
- The PCB voids are to be exposed to super wet conditions.
Wiring
Installation
Suzhou Lily Tech. Co., Ltd.
Documents / Resources
![]() |