928-035-02A Dome Controller General Purpose
“
Product Information
Specifications
- Manufacturer: KMC Controls
- Product Name: DOME Building Automation System
- Components: DOME User PanelTM (DUP), DOME DashboardTM, DOME
Interface ApplianceTM (DIA), DOME SentryTM devices, DOME Mobile
AppTM - Website: www.kmccontrols.com
Product Usage Instructions
1. Pre-Installation Planning
Before installing the DOME system, it is essential to complete
the following steps:
1.1 DOME Account Registration
A DOME account must be created for the installing organization
before setting up the DIA. Follow these steps:
- The first person in a new system integrator organization should
register a new account. - Technicians, engineers, facility managers, and owners
associated with the installation will receive an email invitation
to create an account. - Log in to the DOME Account to verify the setup is complete at
here.
2. Information Requirements
Gather Network Address information for the DIA as per Sections
1.2 and 2.4 of the installation guide.
FAQ
Q: Where can I find third-party notices, terms, and conditions
for software and hardware?
A: You can find third-party notices, terms, and conditions at
here.
“`
DOME Installation Guide
928-035-02A Do you find this document helpful? Click here to share feedback and help us improve:
Give Feedback
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 / 877-444-5622 / Fax: 574-831-5252 / www.kmccontrols.com
Proprietary Notices
1. Legal Disclaimer The use of DOME is subject to Veridify’s standard license terms and conditions as set forth in the DOME Building Automation Starter Kit – Proprietary Notices; License Terms and Conditions (“Standard Terms”), as well as the Software-as-a-Service Agreement. This documentation does not expand or otherwise modify Veridify’s Standard Terms or mutually, in writing, agreed upon terms, including, but not limited to, the disclaimers and warranties expressed therein.
2. Copyright Notice Copyright © 2019 – 2024 Veridify Security Inc. All rights reserved.
Third-Party notices, terms, and conditions pertaining to third-party software and hardware can be found at:
3. Trademark Notice The KMC Dome Cybersecurity Powered by Veridify logo is the trademark or service mark of KMC Controls. Device Ownership and Management Enrollment, and DOME are trademarks or service marks (individually and collectively, “Marks”) of Veridify Security Inc. (“Veridify”). The Marks displayed in this documentation or on any hardware or in any software represent some of the proprietary rights currently owned or controlled by Veridify and are not intended to be a comprehensive compilation of all Veridify’s worldwide proprietary ownership rights. See, https://www.veridify.com/terms-of-use/ for representations of additional Marks owned or controlled by Veridify and additional guidance with respect to Veridify Marks. All other trademarks and service marks, which may be registered in certain jurisdictions, belong to the holder or holders of such marks.
4. Patent Notice DOME is protected by certain patents. In accordance with the virtual marking provisions of the American Invents Act, 335 USC 287(a), See, https://www.veridify.com/terms-of-use/, which enumerates the list of products and components that may be protected by one or more patents, or patents pending in the US and elsewhere. Certain third-party components embedded in DOME may be protected by certain patents of such third party; reference should be made to the third-party documentation.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 2
Contents
1. Pre-Installation Planning ……………………………………………………………………………………………………5 1.1 DOME Account Registration …………………………………………………………………………………………5 1.2 Information Requirements ……………………………………………………………………………………………5
2. DOME Interface Appliance …………………………………………………………………………………………………7 2.1 Create Installation Process…………………………………………………………………………………………..7 2.2 Installation and Configuration Requirements…………………………………………………………………7 2.3 DOME Interface Appliance ……………………………………………………………………………………………7 2.4 DIA Installation Steps …………………………………………………………………………………………………..8 2.5 DIA Operation…………………………………………………………………………………………………………….12
3. Sentry Device ………………………………………………………………………………………………………………….13 3.1 Sentry Device …………………………………………………………………………………………………………….13 3.2 Sentry Device Registration ………………………………………………………………………………………….13 3.3 Sentry Device Installation……………………………………………………………………………………………14 3.4 Device Configuration Connecting to the Console Port……………………………………………….15 3.5 Device Configuration Sentry Device Commands ……………………………………………………….15 3.6 Sentry Device Installation Validation……………………………………………………………………………17 3.7 Sentry Device Reconfiguration or Changing the Protected Device(s) …………………………….18 3.8 Sentry Device Replacement or Relocation……………………………………………………………………18 3.9 Sentry Device Troubleshooting……………………………………………………………………………………18
4. DOME Network Requirements ………………………………………………………………………………………….21 4.1 Multicast DNS (mDNS)……………………………………………………………………………………………….21 4.2 Multicast Time …………………………………………………………………………………………………………..21 4.3 IP Addresses for Devices to be Protected ……………………………………………………………………21 4.4 802.1x ……………………………………………………………………………………………………………………….21 4.5 BACnet Broadcast Management Device (BBMD) …………………………………………………………21 4.6 Ports and DOME Data Directionality ……………………………………………………………………………21 4.6.1 DIA to DOME Server……………………………………………………………………………………………..21 4.6.2 DIA to Sentry Devices …………………………………………………………………………………………..22 4.6.3 Sentry Devices to DIA …………………………………………………………………………………………..22 4.6.4 Sentry Device to Sentry Device ……………………………………………………………………………..22
5. Technical Support……………………………………………………………………………………………………………22
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 3
DOME Components DOME User PanelTM (DUP)
System for installation set-up and device management
DOME DashboardTM
Dashboard for system information, analytics, and alerts.
DOME Interface ApplianceTM (DIA) Local management device at an installation being
protected
DOME SentryTM devices
Security appliance that protects edge devices
DOME Mobile AppTM
Mobile app for registering DOME Sentry devices
Installation Checklist Planning for these item will help to quicken the installation of DOME. Please visit the sections below for each action prior to installation.
Action Complete a Site Survey for each building (Section 1.2) It is recommend to use Veridify’s site survey document “DD-0028 Site Survey Form”
Register for a DOME Account (Section 1.1) https://dome.veridify.com/signup See “DD-0036 DOME Account Reference Guide” for screen details Note – This applies only to the first person in a new system integrator organization, everyone else will receive an email invitation to create an account. Log-in to your DOME Account to verify set-up is compete https://dome.veridify.com/manage
Gather Network Address information for DIA (Sections 1.2 and 2.4)
Gather the following items for installing the DIA (Sections 2.2 and 2.4) · HDMI monitor and cable · USB keyboard and mouse · Power and network connectivity (10/100/1000Mbps) · One or two Ethernet cables (depending on configuration)
Install the DOME Mobile App (Section 3.2) available for iOS and Android https://www.veridify.com/apps
Ensure that devices are discoverable on the network · Power on if not operating due to seasonal-use only · Enable BACnet on JACE controllers and ensure the BACnet driver is associated with the active network interface
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 4
1. Pre-Installation Planning
1.1 DOME Account Registration
A DOME account for the installing organization must be set up and approved prior to installation of the DIA. The first person in a new system integrator organization installing DOME will register a new account as listed in the following steps. Everyone else associated with the installation, including technicians, engineers, facility managers, and facility owners, will receive an email invitation to create an account.
Step 1 Register for a DOME account at https://www.veridify.com/install Step 2 Verify your email address from an email the system will send to you Step 3 Notification of approval will be sent by email after Veridify approves the account
See document “DD-0036 DOME Account Reference Guide” for registration process and screen details.
Note – Approval by Veridify is not a real-time process. It is recommended that you register for your account several days prior to installation of DOME. Once an account is approved, all subsequent users invited from that account are automatically approved.
1.2 Information Requirements
A DOME Site Survey records information on the networks and devices installed in buildings that will become a DOME site. To accommodate larger DOME installations, Sentry devices will likely be installed in `pass-through mode’ (Not Secure). Once all Sentry devices are physically in place and online, the site configuration will be updated to turn off `pass-through mode’ via the DOME Interface Appliance (DIA), making the site “Secure.”
To plan for the installation of DOME, after the site surveys are completed, additional information from the customer may be needed. Below is the list of additional information that will be needed, why it is needed, and how to use it.
Information for the following items is needed: · DIA IP Address(es) and configuration method (static or DHCP) o LAN-A o LAN-B · DIA Console Access Mechanisms · OT Network Address(es) · IP Gateway Addresses or Rules for Sentry network(s)
The Sentry device can determine its IP Address and MAC Address from the device it protects, however it cannot determine the Network Size (CIDR / Netmask) nor IP Gateway/Router on its own. To solve this issue, the Sentry device was designed to use mDNS (Multicast DNS) to
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 5
request this information from the DIA. The DIA is configured with the network/CIDR and gateway information in order to respond to the Sentry device requests.
Note – When a Sentry device cannot reach the DIA via mDNS, the information it would acquire from mDNS can be pre-programmed in. Please see section 3.5 for instructions on how to preconfigure a Sentry device for an environment where mDNS is unavailable.
DIA IP Address(es): This information is needed in order to configure the DIA. It must have a stable address that the Sentry device can reach, regardless of whether that address is acquired via DHCP or statically configured. If the DIA is being installed with two network addresses, only the OT network needs to be static. Record the DIA IP address the Sentry devices will use to talk to the DIA.
DIA Console Access: The DIA is the management console for the DOME Installation and is used to reconfigure and push out provisioning changes to the Sentry devices. An authorized User will need to access and log into the DIA to perform these tasks. Typically, a User will log in via the DIA device console (using an attached keyboard, mouse, and monitor). However, if the DIA is installed in a Data Center, the User may need to use a remotely accessible KVM that will then give them access to the console.
OT Network Addresses(es): This is the list of network addresses of the devices the Sentries will protect. This information is part of the DOME site surveys. The DIA will need to be configured with the list of all networks in CIDR format.
Example 1 – If an existing device is at 192.168.5.23/24, then that is one of the networks for the list (the “24” is the CIDR size, and the DIA will convert this IP Address to the proper network address, 192.168.5.0/24). Example 2 – If the device address is: 10.20.30.40 netmask: 255.255.252.0, this pair translates to a CIDR size of 22 (10.20.30.40/22). A website like https://dnschecker.org/netmask-cidr.php can help translate from netmask to CIDR size. Go through all the site surveys to determine the full list of networks and CIDR size(s).
IP Gateway Addresses: There will be multiple routed networks connecting devices except in smaller installations. Each Sentry device needs to learn (or be told) its router address, and each OT network input into the DIA can be individually configured with its gateway. This will enable the DIA to announce the gateway to the Sentry device.
IP Gateway Rules: In the case where mDNS is not usable, the Sentry device can be preprogrammed with an IP Gateway Rule. The Sentry device currently supports two Router Rules: “.1” and “.254” and the appropriate rule to use is determined by the installation environment:
· The “.1” rule tells the Sentry device to compute the lowest IP Address on the network and use that as the router. For example, if the network is 192.168.5.0/24, the “.1” router will be 192.168.5.1. If the device IP is 10.40.80.100/29, the network is 10.40.80.96/29, then the router will be computed as 10.40.80.97.
· The .254 rule tells the Sentry device to compute the highest IP Address on the network and use that as the router. For example, if the network is 192.168.5.0/24, the “.254”
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 6
router will be 192.168.5.254. If the device is 10.40.80.100/29, the network is 10.40.80.96/29, then the router will be computed as 10.40.80.102.
2. DOME Interface Appliance
An “Installation” needs to be created for each DIA. An Installation can be a single building or a collection of buildings.
2.1 Create Installation Process
1. Log in to your DOME account at https://dome.veridify.com/manage 2. Register the Installation by providing details about the location. The following information will be required:
· Owner (organization) name and address · Contact information for at least one owner representative (name, title, email, phone) · Site name and address 3. Proceed to the installation location for the remaining steps.
2.2 Installation and Configuration Requirements
Installation and configuration of a DIA requires the following items: · DOME account · HDMI monitor and cable · USB keyboard and mouse · Power and network connectivity (10/100/1000Mbps) · One or two Ethernet cables (depending on configuration)
2.3 DOME Interface Appliance
DM-ADVT-2271
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 7
2.4 DIA Installation Steps
Pre-Installation The DIA should operate whenever power is applied without the need to push the power button. This is enabled by a hardware jumper setting and should be adjusted, verified, or tested before installation. Remove the bottom cover and look for the jumper pin header labeled PSON1. Set the jumper to connect pins 1 and 2. When the jumper is set to connect pins 2 and 3, the power button must be used to turn on the device, including after a power outage.
All steps are summarized here with screenshots for steps 6-13 below: 1. Mount the DIA. 2. Connect the network to DIA port LAN A, and optionally LAN B if being used. 3. Connect monitor, keyboard, and mouse. 4. Connect power to the DIA and monitor. 5. Turn on the monitor and the DIA (if it does not automatically turn on check the jumper if
needed). 6. Follow the on-screen instructions to get the DIA onto the network by selecting DHCP or
Static IP (network information required). 7. Log in to your DOME account *. 8. Select the installation and select “OK” when prompted. 9. The DIA will reboot. 10. Log in to your DOME account again to finish set-up. 11. Go to tab “Network Configuration” to configure the network settings. 12. If two networks are being used, go to tab “OT Configuration” to configure the list of available
OT Networks available to the Sentry devices. 13. Go to tab “Sentry Configuration” to set the Sentry device firewall configuration.
Step 6 Network Setup
Step 7a – Login
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 8
Step 7b Sparklr page if the DIA log-in screen is left active for an extended period of time, the system may timeout and provide the page above when trying to log in. Please use Ctl-W to reboot the browser and continue to log-in.
Step 8a
– Select Installation
Step 8b Confirm Selection
Step 9 – Reboot
Step 10 – Login
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 9
Step 11 – DIA Network Configuration The DIA supports connectivity to two networks one for internet access and one for OT devices. If these are both on the same network, then only LAN A is needed. At least one interface must be configured as a static IP address.
Network Design Single network for Internet access and OT devices Separate network for Internet access and OT devices
Configuration Settings Use LAN A port (must select “Static IP” and provide the required network address information)
LAN A for network with Internet access (DHCP or Static IP is acceptable) LAN B OT network (must select “Static IP” and provide the required network address information)
Step 11a DIA DHCP Network Configuration Configuration
Step 11b DIA Static Network
Step 12 OT Network Configuration This page controls the OT network configurations when Sentry devices will be installed on a network without internet access. For each possible Sentry OT Network, the IP address, network size are required, while the network gateway address is optional. In smaller installations, the Sentry device will acquire this data directly from the DIA during its auto-configuration step, which is why this data must be in place. The DIA also uses this information to ensure the routing table enables the DIA to reach the Sentry device networks through the appropriate Network Interface configured in the previous step.
Saving changes is required after adding or deleting a configuration for those changes to take effect.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 10
Step 12a OT Network Configuration
Step 12b Add OT Network
Step 13 Sentry Device Configuration This page controls the settings that are provisioned onto every Sentry device managed by the DIA. You must explicitly save any changes for them to take effect. Once saved, these settings will be applied to any Sentry device that comes online after the settings are made. To push the changes to deployed Sentry devices, use the “Reprovision All Devices” button after saving the configuration.
There are three settings for configuring the capability of a Sentry device.
Allow All
This is for BACnet devices and allows for non-BACnet traffic to
also pass to the protected device.
Enable Pass-through
This allows for installing Sentry devices and letting the network
Mode
operate without security.
Enable Permanent
This permanently activates the security function of the Sentry
Mode
device and Pass-through Mode will no longer be allowed to be
selected.
Step 13
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 11
Peripheral Devices After configuration is complete, the monitor, keyboard, and mouse can be disconnected if desired, but they can remain as part of the DIA installation. They will be needed again to change the settings (e.g. to convert from Pass-through to Secure mode).
Sentry devices can now be registered through the DOME Mobile App and then installed.
2.5 DIA Operation
After installation and set-up, the DIA is not involved in the continuous operation of security. DOME-enabled devices, including Sentry devices, communicate between themselves without the DIA.
After DOME-enabled devices are provisioned onto a network, the DIA is required for the following functions: · log aggregation · alerts and notifications · Sentry device management · Certificate and Key management & Refresh · Sentry device software updates · Firewall and whitelist updates · Protected device maintenance/modifications (e.g. replacing BACnet IP hardware)
The DIA automatically refreshes Sentry Certificates so they do not expire. If a certificate is left to expire (e.g. DIA not available), the Sentry device and other DOME-enabled devices will be unable to communicate.
At this time, if a DIA fails, a replacement DIA will need to be created by Veridify and then it can be physically deployed to replace the failed DIA.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 12
3. Sentry Device
3.1 Sentry Device
DM-SENTRY-NANO-BAC or DM-SENTRY-NANO-TCP
Port Assignment
Network Port(s) LAN1, LAN2
Device Port
WAN
USB Port(s)
Config only
HDMI port
Not used
SD slot
Not used
SIM slot
N/A
Antenna port(s)
N/A
RST (Reset)
Not used
Mask
Not used
Note The Sentry device has three network ports. LAN1 and LAN2 can be used for
deployment in a daisy-chain configuration. The WAN port is connected to the device to
be protected.
Sentry Device Power Connections
USB with USB-C connector (5V DC)
Pin Label Description
+Vs
PWR V+ DC power input PIN
GND
PWR V- DC power input PIN
GND
3.2 Sentry Device Registration
The Sentry devices must be registered in order to operate. Only registered Sentry devices can communicate with the DIA and other registered Sentry devices.
Before Registration 1. Install the DIA as described above. Sentry device registration cannot proceed without the DIA registered to an Installation as described in section 2.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 13
2. Install the DOME Mobile AppTM on your mobile device (Internet connectivity is required when using the app). The app is available for Android and iOS. (https://www.veridify.com/apps) Register devices with the DOME mobile app 1. Open the DOME mobile app. 2. Log in with your DOME account. 3. Select “Register Devices”. 4. Select an Installation. 5. Scan the QR code on the Sentry device from the label that has the Veridify Security logo. 6. Add optional device and location information into the app and submit the data. 7. Repeat as needed until all Sentry devices are registered.
Register devices online 1. Log in to your DOME account at
https://dome.veridify.com/manage. 2. Click on “Register Device” on the Home screen. 3. Enter the manufacturer’s Serial Number of the device (not Veridify S/N). 4. Repeat as needed until all Sentry devices are registered.
You can log in to your DOME account to verify if the Sentry devices are registered.
3.3 Sentry Device Installation
The Sentry device is designed to auto-configure itself when it is connected. It requires the DIA to already be online and running, and it depends on the DIA to provide some network configuration information as well as the required security information the Sentry device needs to connect to the network.
1. Ensure the device to be protected is installed, powered on, and operational before the Sentry device is connected and powered on.
2. Mount the Sentry device (DIN rail, wall, etc.) as close as possible to the device to be protected.
3. Remove the network cable from the device to be protected and plug it in to the Network Port on the Sentry device.
4. Add a cable to connect from the Device Port on the Sentry device to the ethernet port on the device to be protected.
5. Attach the power connection to the Sentry device.
The Sentry device will auto-configure itself to the network and there is nothing further to do. The tables below show the states the Sentry device goes through for configuration and the corresponding LED indicators.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 14
Sentry device Configuration States and LED Indicators
LED State Power On
SYS Flash
Ready to Provision Found Device / Getting Network Parameters Failed to Get Network Parameters Got Network Parameters / Contacting DIA Communicating to DIA Provisioned / Running Insecurely (Protection OFF) Provisioned / Running (Protection ON)
Flash Flash Flash Flash Flash Flash Flash
WAN Off On Flash Flash On Off Flash On
LAN Off Off Off Flash Flash Flash On On
3.4 Device Configuration Connecting to the Console Port
Certain limited Sentry device configurations can be made through a connection to a USB port or console port on the Sentry device. The commands are described in the next section.
DOME Sentry Devices
A crossover USB cable is needed to connect from your computer to the Sentry device. The cable is part of the KMC Dome Sentry Starter Kits (DM-START-NANO-BAC and DM-START-NANO-TCP) and can also be purchased separately (DM-SENTRY-USB).
Connect the crossover USB cable to any USB port on your computer and any USB port on the Sentry device.
The terminal emulator should be set to: 115200 bps, 8 data bits, 1 stop bit, no parity, no flow control.
3.5 Device Configuration Sentry Device Commands
Configuring a Sentry device can be automatic or manual depending on certain models or network configurations.
Sentry Mode DM-SENTRYNANO-BAC:
BACnet/IP
DM-SENTRYNANO-TCP:
TCP/IP
Device Discovery
The BACnet Sentry device will automatically discover the IP device behind it and contact the DIA for its provisioning information, including network keys, operational certificates, and firewall settings. For this automated discovery, the Sentry device requires the BACnet/IP device to respond to a Who-Is request with an I-Am response on every configured BACnet port.
The TCP/IP Sentry device may not automatically find the IP Address of the IP Device behind it. To manually enter the IP address the installer can connect the serial port and login to the user “config” and supply the IP Address of the device behind the Sentry device. The Sentry device will then probe that device and, if it’s found, it will finish its configuration process.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 15
Note: The Sentry device, by default, will use Multicast DNS (mDNS) to request network information from the DIA in order to fully come online. In situations where mDNS discovery does not work, the configuration process allows the installer to also supply the information that would be discovered automatically. This manual configuration of network parameters can happen prior to installation (whereas the IP address input for a TCP/IP Sentry device can only happen in real-time during deployment). Once you confirm your entries, the Sentry device will take these settings in lieu of discovering them from the DIA.
Sentry device commands are initiated by logging in from the command prompt with commandspecific usernames and passwords as show in the table below.
Username config
Password [none]
Description
For TCP/IP Mode only The Sentry device will automatically configure parameters from the protected device if possible or prompt for manual configuration as follows:
Veridify DOME Sentry Configuration. Device connected. Enter device IP Address (a.b.c.d):
If the entered IP address is found, it will continue to the main menu (below); if not found the prompt for an IP address will be repeated. Entering a blank IP address will exit configuration.
For All Modes After entering config mode, the following main configuration menu will appear:
1. (D)isplay Configuration 2. (E)dit Configuratiion 3. (C)lear Confirguration 4. (Q)uit Configurator
[Selecting the number or corresponding first letter of each option will work]
2. Edit Configuration
1. Network Configuration 2. BACnet Port Configuration * D. Display config Q. Quit Editor
* menu option only available with a BACnet-capable Sentry device
2. Edit Configuration >> 1. Network Configuration
Enter the CIDR Size (0-31)
[this is followed by Gateway Configuration]
1. Use the .1 address (e.g. x.y.z.1) 2. Use the .254 address (e.g. x.y.z.254) 3. Enter an explicit address (Note: may not work a priori) 4. No Gateway
[after selection, there is a prompt for the DIA IP Address]
Enter DIA IP Address (a.b.c.d):
[this is followed by a display of configuration parameters and a confirmation prompt]
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 16
reset
Reset
showconfig [none] showlogs [none]
2. Edit Configuration >> 2. BACnet Port Configuration
Port Configuration: portA[-portB][,…]
Enter Port Configuration:
[after entry the prompt returns to the Edit Configuration menu]
NOTE: The config mode only works for Sentry devices that are not already provisioned by the DIA. Attempting to run this command with a provisioned Sentry device will result in the following message:
Sentry already configured. Reset Sentry to reconfigure.
The Sentry device will clear all provisioning and reboot, probing for a new protected device. Any previously-configured manual configuration data is re-used for the probe; the reset will not clear out any manually configured data. To clear out manual configuration data, reset the Sentry device and then re-run the configuration option and use the “Clear Configuration” option.” The Sentry device will display information including the software version, device UUID, current IP Address information, and the list of protected devices. After a few seconds the system will return to the login screen. The Sentry device will display the real-time logs of the device, starting from a dozen entries before you logged in. The logs will continue to display for as long as you remain logged in. To exit log-viewing mode, enter a Control-C character, and the system will return to the login screen.
3.6 Sentry Device Installation Validation
The Sentry device is designed to auto-configure itself, discovering the device connected behind it and bringing itself onto the network with minimal user intervention. Follow these steps to determine if the Sentry device was installed correctly and is operating properly.
Step 1: Connect the Sentry device and power it on as per the instructions, and watch the LEDs on the device. See the table in section 3.3 for the configuration states and LED indicators.
Step 2: Once the LED sequence becomes Flashing/On/On (or Flashing/Flashing/On) the device is operating normally. You will see the Sentry device as “online” in the DIA Device Inventory List, and the Sentry device will show up into the DOME Dashboard. The DOME Mobile App will also show the device as online and whether it is in Secure or Insecure (Pass-through) mode.
Step 3: Once the Sentry device is online in Secure mode (Flash/On/On), you can run Wireshark on the network to see the encrypted data.
Note – If the Sentry device does not reach the online state and stays in any other state for over 60 seconds, please see the Troubleshooting Guide.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 17
3.7 Sentry Device Reconfiguration or Changing the Protected Device(s)
Sometimes end devices need to be replaced. Because the Sentry device is tied to the IP device behind it, if the protected device needs to be changed, the Sentry device will need to be reconfigured to allow that change by using the “reset” user account. Similarly, if the protected device is a BACnet/IP router and a device is added or removed behind the router, the Sentry device will need to be reconfigured to allow those devices to communicate.
When a Sentry device is reconfigured, it will not lose its name/mapping in the DOME Server. It will just obtain new security credentials locally, re-discover the IP device behind it, and if device is a BACnet Sentry device and the device is a BACnet router, it will find all the BACnet devices that the Sentry device is protecting.
If the IP address needed to be manually entered, it will need to be done again now. However, any manual network settings (CIDR, Router, DIA) will be saved across a reset.
3.8 Sentry Device Replacement or Relocation
When a Sentry device is replaced, or relocated to protect a different device, certain parameters need to be updated. There are two methods to force this update: 1. Power cycle the protected device. 2. Wait 15 minutes from the time the new Sentry device is connected to the network and protected device.
3.9 Sentry Device Troubleshooting
Issue No LEDs light up
Remediation The Sentry device does not have power. Check the connections, power sources, and ensure the power connection is connected securely to the Sentry device and the power supply source is turned on.
LEDs show Flash/On/Off
LEDs show 928-035-02A
Next, test whether the issue is the Sentry device or the power supply. Take the Sentry device and use the enclosed USB Cable and plug it into a standard USB Power supply. If the Sentry deivce lights up after a couple of seconds, the issue is the power supply. If the Sentry device does not light up, the unit may be defective. Contact KMC Controls support.
The Sentry device is waiting for a link from the protected device. Ensure the Sentry device is plugged into the network and ensure the protected device is both plugged into the Sentry device and powered on.
If this stage lasts for more than 15 seconds, the Sentry device may not be able to find the device, most likely because the device is quiet, has not emitted any data, and has not responded to any probes from the Sentry device. First ensure that the protected device is powered up and online. Check the LEDs on the Ethernet ports to ensure they are lighting up. Finally, try connecting to the Sentry device console and login as “config” to manually configure the IP Address.
The Sentry device is trying to determine the additional network parameters
DOME Installation Guide
Feedback? Give yours here.
Page 18
Issue Flash/Flash/Off
Remediation for the protected device required for the Sentry device to come online. If this stage lasts more than 60 seconds, it means that the Sentry device cannot reach the DIA via mDNS, and that has not been pre-configured. Check that the DIA is reachable or connect to the Sentry device console as “config” and manually configure the parameters. This state can also occur if the network cables are swapped and the Sentry device heard and attached itself to a device on the network instead of the protected device. If this is the case, fix the cabling and then power-cycle the Sentry device.
LEDs show
This is an error condition, which means the Sentry device has failed to find
Flash/Flash/Flash valid network parameters. This condition occurs in the following cases:
· The Sentry device reached the DIA via mDNS but the data returned did
not include any network configuration data. Go to the DIA and ensure at
least one OT Network is configured.
· The Sentry device reached the DIA via mDNS, but the DIA did not return
OT Network Configuration data that matched the IP Address the Sentry
device discovered. Go to the DIA and ensure the proper OT networks are
configured.
LEDs show Flash/Off/Flash
The Sentry device is trying to communicate to the DIA to obtain its provisioning data. If this state lasts for more than 60 seconds, there could be one of several reasons:
· This is a BACnet Sentry device, and the protected device does not respond to a BACnet Who-Is command. There is no remedy to this situation except getting the device to respond to a Who-Is when the Sentry device asks, which is required by the BACnet standard.
· The Sentry device cannot reach the DIA. There are several possible reasons: o The Network configuration is incorrect (incorrect CIDR setting for the network). o The Sentry device requires a default gateway, but none was configured. o The configured default gateway is incorrect. o There is a firewall rule preventing the Sentry device from reaching the DIA. o For all of these cases, check and correct the configuration.
· The DIA refuses to provision the Sentry device because the Sentry device is not registered to this installation. Verify that this Sentry device is listed in the DIA’s Device Inventory.
· This state could also occur if you manually configured the Sentry device (to bypass mDNS) but wired the Sentry device backwards (connecting cables to the wrong ports). If so, swap the cables and power-cycle the Sentry device.
· To determine the cause of the issue, connect to the Sentry device console and login as “showlogs” to get more information about what is failing.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 19
Issue
Remediation
LEDs show Flash/On/On
This means the Sentry device is online and successfully provisioned. It should be operating correctly. Check the DOME Mobile App and DOME Dashboard for additional status.
LEDs show
This means the Sentry device is online and successfully provisioned into
Flash/Flash/On INSECURE (pass-through) mode. If should be operating correctly. You can
Check in the DOME Mobile App and DOME Dashboard for additional status.
Cannot reach By design, the Sentry device will block access to the protected device from
protected device unauthentic sources. Reaching the device varies based on the type of Sentry
management device:
service
· In the case of a TCP/IP Sentry device, the only way to reach the
(e.g. webui)
protected device is to use another Sentry device and become part of the
secure enclave.
· In the case of a BACnet Sentry device, a firewall rule can be configured to
allow non-BACnet access to the protected device. Go to the DIA and
ensure the Firewall setting in the Sentry Configuration Page is set to
allow packets through. Then push the configuration down to the Sentry
device to gain access.
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 20
4. DOME Network Requirements
This section provides the requirements for preparing a network for a DOME installation.
4.1 Multicast DNS (mDNS)
Sentry devices make an mDNS request on port 5353 to the Multicast DNS group, 224.0.0.251 as part of auto-configuration. The DIA needs to be able to hear and respond to it, and the Sentry device needs to receive the response. Note that the initial request is made from a source address of 0.0.0.0, and this packet needs to reach the DIA. The DIA will respond back to the multicast group.
Note that in environments where mDNS is known not to work, the Sentry device can be manually pre-configured with the information it would acquire from the DIA via mDNS.
4.2 Multicast Time
The DIA broadcasts NTP messages on the Multicast Time group, 224.0.1.1. All Sentry devices must be able to subscribe to the multicast group to hear those announcements. After the Sentry device gets online, it will reach out to the DIA via Unicast to set and maintain its time.
4.3 IP Addresses for Devices to be Protected
The device to be protected must have a static IP address as DHCP is not supported by Sentry devices. As part of the auto-discovery process, Sentry devices will discover and assume the IP and MAC address of the protected device.
4.4 802.1x
Sentry devices do not support 802.1x authentication. 802.1x must not be enabled on the target network.
4.5 BACnet Broadcast Management Device (BBMD)
DOME does not support the use of a BBMD on the OT network.
4.6 Ports and DOME Data Directionality
4.6.1 DIA to DOME Server The DIA communicates to the DOME Server using multiple TCP and UDP ports at the following hostnames:
· dome.veridify.com · domeserver.veridify.com · log-server.securerf.com · dp-log-server.securerf.com · veridifystaging.securerf.com · Various Ubuntu Update Servers · ppa.launchpad.net · swupdate.openvpn.net
928-035-02A
DOME Installation Guide
Feedback? Give yours here.
Page 21
All connections to the DOME Server are outbound-only, initiated by the DIA.
Port
Protocol
Comment
53
DNS
123
NTP
443
TCP
DOME
1194
TCP/UDP
DOME
6514
TCP
DOME
8443
TCP
DOME
4.6.2 DIA to Sentry Devices
Port
Protocol
22
TCP
123
4123
Comment SSH NTP NTP
4.6.3 Sentry Devices to DIA All Sentries in the Installation must be able to reach the DIA using the following ports:
Port
Protocol
Comment
123
NTP
4123
NTP
5353
mDNS
6514
TCP
DOME
9999
TCP
DOME
4.6.4 Sentry Device to Sentry Device All Sentry devices in the installation must be able to reach the BMS.
BACNet
Port
Protocol
Comment
47808
UDP
(or as configured)
DOME
TCP/IP Port 9000
Protocol UDP
Comment DOME
5. Technical Support
Please direct all technical support inquiries to info@kmccontrols.com, or by phone at 1.574.831.5250 or 877.444.5622. Secondarily, contact Veridify Security at support@veridify.com, or by phone at 1.203.227.3151 (Option 6).