Itron Axonic Flow Meter
Specifications
- Operating Parameters: Maximal pressure (PMA), Operating temperature
- CE Marks: Approved in environmental class C (Industrial applications)
- Compliance: DIN EN 1434, MID environmental class E2 and M2 (MID 2014/32/EU)
- Body Length: 200mm – 400mm
- Electronic Height: 124mm
- Bolt Circle Diameter: 145mm – 190mm
- Weight: 8.0kg – 20.0kg
Product Usage Instructions
Safety Advice
Ensure that the hot water circuits and power supplies are protected by valves or pressure limiting systems to maintain safe operating conditions.
Mounting the Flow Meter
Operating Conditions: Ensure that the operating parameters of the circuit do not exceed the specified maximal pressure and operating temperature.
Materials and Dimensions
- Type DN65: Body Length L1 – 200mm, Electronic Height L2 – 124mm, Weight – 8.0kg (200mm)
- Type DN80: Body Length L1 – 300mm, Electronic Height L2 – 124mm, Weight – 9.0kg (300mm)
- Type DN100: Body Length L1 – 300mm, Electronic Height L2 – 124mm, Weight – 9.0kg (300mm)
- For complete technical data, refer to the provided table for specific dimensions and weights.
FAQ
- Q: What should I do if the operating parameters exceed the specified maximal pressure or temperature?
- A: If the operating parameters exceed the specified limits, immediate action should be taken to reduce pressure or temperature to avoid damage to the flow meter.
- Q: Can the Axonic flow meter be used in both horizontal and vertical positions?
- A: Yes, the Axonic flow meter is designed to be used in either horizontal or vertical positions for measuring thermal energy accurately.
Axonic
User guide
DELIVERY AXONIC
- Check completeness before installation
- 1 flow meter incl. connecting cable (l = 3 m or 10 m)
- Moving flanges. (PN16 and PN25 versions only)
- 1 set of gaskets
- 1 mounting and operation instructions
- Calibration Report and CE-Declaration (depending on country)
GENERAL INDICATIONS
Flow meter AXONIC is a sophisticated electronic measuring instrument for measurement of thermal energy in either hori-zontal or vertical position. Axonic can be connected to any calculator with compatible signal-input. The following instructions must be carefully observed in order to ensure correct mounting and to fulfill all safety and guarantee conditions.
Advise concerning safety
Hot water circuits and mains power supplies run under high temperatures and pressure as well as under high voltages.
When operated incorrectly, these may cause serious injuries. Due to this, measuring units may only be installed by qualified and trained personnel. Prior to any installation / de-installation of Axonic it is mandatory to close and empty the concerned network section. The casings of the heat meters are designed for cold, warm and hot water, with the characteristic values specified for each case, excluding any other liquid. If the flow meter casing is submitted to strong shocks, impacts, drops from more than 60 cm height or similar stresses, the heat meter must be replaced. Pipes must be earthed.
The complete system or global installation which will use this equipment must be protected by valve or a pressure limiting system in order to respect the maximal pressure of the equipment.
CE marks and protective classes
Metering unit AXONIC fulfills all requirements of applicable EC guidelines, and is approved in environmental class C (Indus-trial applications), according to DIN EN 1434, MID environmental class E2 and M2 (MID 2014/32/EU)
- Ambient temperature: -25°C … +60°C (indoors installation)
- Storage temperature
- Permanent: T°MIN = -25°C T°MAX = 60°C
- Max +70°C (< 24 hours continuous)
- Flow sensor IP 68 (7 days under 1.2 meter of water at ambient)
- Axonic is conform to DIRECTIVE 2014/68/EU (Heat version only), fluid group 2 (Approved for water only).
- Discarded electronic devices contained within must not be put in normal house hold waste. Dispose in accordance to local government regulations.
- The metrological class of a complete thermal energy meter, made of subassemblies (flow meter, calculator and temperature sensors pair), assembled and installed according to the manufacturers installations instructions, meets the metrological class that is indicated on the flow meter type plate.
- Cooling meter versions meet the requirements of MessEV.
Further important indications
- The flow meter must never be lifted or carried by its connecting cable.
- Mounting position shall be selected so that the connecting cable of the flow meter and the temperature probe cables will not be near mains cables or other sources of electromagnetic disturbances (minimum distance 50 cm).
- Cables must not be installed along pipes reaching temperatures above 60 °C.
- Opening of calibration seals will cause the loss of calibration validation and of guarantee.
- Unsealing the device is excluding the guarantee of conformity to directive PED 2014/68/EU. (Heat version only)
- The casing may only be cleaned on the outside, with a soft, damp cloth. Do not use detergents.
- Installation must be carried out according to EN 1434.
- There may be local rules that must be followed but not covered with this manual. Please check with the experts of the country in which the meter will be installed.
- In Bi-Functional applications, the durability of the flow sensor is limited to 5 years.
Application
The flow meter Axonic is a sub-assembly for a thermal energy measurement systems that consists of flow meter, calculator (e.g. Itron CF51, CF55, CF800) and a pair of temperature sensors. Calculator input specifications and flow meter output specification must be compliant in order to ensure correct energy measurement, this concerns in particular flow meter pulse-weight (L/pulse) and flow meter position (return or supply pipe).
Information on the appropriate disposal of products
The crossed-out garbage container symbol on the device or on the packaging indicates that the old product must be disposed of separately from household waste so that it can be handled and disposed of properly. Please observe the laws in force in your country regarding the return and proper disposal of electrical devices. The product is potentially not harmful to human health and the environment, but if it is illegally disposed of in the environment, it will have a negative impact on the ecosystem. Illegal disposal of the device in the environment is punishable by law.
It is the personal responsibility of the user of the meter, if necessary, to delete his private data before disposal.
MOUNTING THE FLOW METER
Operating conditions, materials and dimensions
The operating parameters of the heating or cooling circuit must not exceed, Maximal pressure (PMA), Operating temperature indicated on type plate.
- Max permanent operating temperature: version for heat 130°C/150°C (permanent/accidental); version for cooling 50°C
- PMA at extreme temperatures
- PN16 120°C < Maximal pressure: 15.2 bar < 130°C
- PN25 120°C < Maximal pressure: 23.8 bar < 130°C
Minimum pressure to ovoid internal cavitation
- DN65-100
- For fluid temperature < 90°C: minimum pressure = 1 bar
- For fluid temperature ≥ 90°C: minimum pressure = (minimum pressure to keep water at liquid state) + 1 bar
- DN125-150
- For fluid temperature < 90°C: minimum pressure = 2bar
- For fluid temperature ≥ 90°C: minimum pressure = (minimum pressure to keep water at liquid state) + 1,5 bar
Raw materials in contact with water
- O-Ring: EPDM (channel) & FKM
- Bodies: Bronze (PN16 and 25), stainless steel (PN40).
- Transducer support: brass plated (PN16 and 25), Stainless steel (PN40)
- Measurment Channel, Stabilizer: Thermoplastic
- Membrane: stainless steel
Pressure loss: at qp/50°C (bar)
- DN65 < 0.10 bar
- DN80 < 0.17 bar
- DN100 < 0.13 bar
- DN 125 < 0.22 bar
- DN150 < 0.15 bar
For further technical data, refer to table
- Flanges PN16 and PN25 according EN 1092-2 / Mobile Flanges Elevated interface type B
- Flanges PN40 according EN 1092-1 / Type 21 PN40 Male hubbed socket Type E
Mounting instructions
- Never carry out welding or drilling work near the meter.
- All handlings operations must be made with the lifting ear of the product. If there are no lifting ear, handling operations can be made by hand.
- Leave the meter in its original package until all connection, insulating, painting and cleaning tasks have been performed.
- Always install the meter according to the mounting position indicated on the nameplate of the calculator (supply or return or cold or warm line). It is recommended that stop valves are fitted before and after the flow sensor to simplify dismantling.
The flow sensor should be installed in a convenient position for service and operating personnel. - The flow sensor can be installed in both horizontal and vertical pipe sections, any position is allowed.
- Aluminum rib of electronic compartment should be visible in case of thermal insulation. (See Fig N°1)
- For medium temperatures above 130°C a flow meter with thermal insulation must be installed in that way, that the electronic is beside the pipe and not above. (See Fig N°2)
- Ensure that the flow sensor is always filled with liquid after installation. (See Fig N°3)
- By approval calming sections before and after the flow sensor are not required. Nevertheless we recommend to design calming sections 5xDN if the space for installation is available.
- The heat meter must be protected against shocks and vibrations which might occur at the place of installation.
- When charging the pipes with water, isolation valves must be opened slowly.
- Flange connections of the meter must match with the nominal diameter DN and nominal pressure PN (according to EN 1092) of the corresponding counterparts of the pipes. The metering unit must not be subject to excessive tensions caused by pipes or molded parts. The pipes of the heating system must be secularly fastened before and after the flow meter. In case of flanged connections, all bolts must be used and tightened. All bolts, nuts and gaskets used must comply with the nominal with DN, the pressure level PN, the maximum admissible temperature and pressure.
- Installation of AXONIC. Versions PN16 and PN25 with dedicated seat of moving flanges. (See Fig N°4)
- CF 51 and CF 55 calculators can be attached to the flowmeter using the adapter supplied with the flowmeter. (See Fig N°5)
- For repair or reconditioning flow meter have to be sent back to the manufacturer or to a repair shop authorised by the manufacturer.
- The device must be replaced in case of fire, explosion at its close proximity.
- Keep the cable length as short as possible.
Gaskets
Thickness following NF EN 1514-1 and in accordance with the supplier
ELECTRICAL CONNECTION AND POWER SUPPLY
AXONIC must be power-supplied by the integrator (CF 51, CF 55 or CF 800) or an exterior power supply. (eg: Itron Pulse-Box or other integrator with galvanic insulation).
Connecting the flow meter to integrator unit
- Beside the main pulse output A the product could offer (as option) a 2nd pulse output B providing pulses and backflow to another independent device (e.g regulator). This option would be configured at factory.
- This pulse output B is following the same hardware specification as output A. Pulse-weight and pulse length of output A and B are independent.
- Before connecting, make sure the pulse weights of flow meter and integrator are equal (typeplate of both devices)!
- Connect to integrator according to the following connecting diagram (figures show connecting diagram for CF 51, CF 55, Pulse-Box and CF 800).
- Before connecting an Axonic to other Systems to other systems make sure that a galvanic insulation is guaranteed. (e.g. by using the Itron Pulse-Box)
Always make sure that the housing and gasket line up properly.
Specification of connection to integrator
Cable A: 4 wires connecting cable, used for connection to integrator
Allocation of wire colors
- WHITE: µCom/diagnostic
- BLUE: pulse A or diagnostic
- BLACK: earth connection (-)
- RED: power supply AXONIC (+)
Cable B: 3 wires connecting cable, used for connection to any devices
Allocation of wire colors
- RED: Pulse B
- BLACK: earth connection (-)
- WHITE: DIR. (Direction of the flow: 1 = normal flow, 0 = backword flow)
Characteristic of pulse outputs (A+B)
- conform to class OB, OC and OD of EN1434-2
- Type: Open Drain
- Polarity: non reversible (observe connection diagram)
- Duration of pulse: see table below
- Max voltage: 30V DC
- Max current: 27 mA
- Drop of voltage when switched on: ≤ 0.3V at 0.1 mA /≤ 2V at 27 mA
- Max output frequency: 128 Hz
- Resistance when switched off: ≥ 6MΩ
- Pulse length according table
- Max. cable length: 10 m
DN65 – qp 25 DN80 – qp 40 DN100 – qp 60 DN125 – qp 100 DN150 – qp 150
Pulse Weight Pulse Length (ms)
8 | p/L | 5 | n.a. | n.a. | n.a. | n.a. |
4 | p/L | n.a. | 5 | n.a. | n.a. | n.a. |
2 | p/L | n.a. | n.a. | 5 | n.a. | n.a. |
1 | L/p | 20 | 20 | 10 | 5 | 5 |
2,5 | L/p | 50 | 50 | 20 | 10 | 10 |
10 | L/p | 100** (200, 500) | 100** (200) | 100 | 50 | 50 |
25 | L/p | 100** (200, 500) | 100** (200, 500) | 100** (200) | 100** (200) | 100 |
100-2500 | L/p | 100** (200, 500) | 100** (200, 500) | 100** (200, 500) | 100** (200, 500) | 100** (200, 500) |
Power supply
- Nominal voltage: 3,2 … 6V DC
- Average current consumption: < 50 µA. (depends on product configuration)
- Peak current consumption Imax: < 3 mA
Optional connecting AXONIC with Pulse-Box to integrator unit (optional power supply)
The Pulse-Box offers the following functions
- Power supply of AXONIC independently of the integrator.
- Galvanic insulation of AXONIC from the integrator.
- Pulse length increase of AXONIC’s pulses.
- 2 wire pulse output
Before connecting, make sure that the pulse of AXONIC and integrator match!
Connection of AXONIC with Pulse-Box to an integrator according to mounting instructions: respect polarities!
Characteristics of pulse exit
- Version: Open collector
- Polarity: non reversible (respect connecting diagram)
- Duration of impulse: 135 ±35 ms
- Maximum input voltage: 30 V DC
- Max. input current: 27 mA
- Voltage drop when switched on: ≤ 0.3 V at 0.1 mA, ≤ 2.0 V at 27 mA
- Resistance when switched off: ≥ 6 MΩ
- Maximum pulse frequency: 1Hz
- Maximum cable length: 10 m
FUNCTION CONTROL OF AXONIC
The AXONIC flow sensor is equipped with a LED in order to perform a simple functional check. The signal sequence depends on operation conditions and will be repeated any 10 as follow
Information | Number of flashes | Signal/Period (Repetition) |
Flow detected | 1 | 20ms (LED ON) / 10s |
Air in pipe / US Asic alarm | 2 | 20/500ms (LED ON/OFF) / 10s |
Low signal amplitude alarm | 3 | 20/500ms (LED ON/OFF) / 10s |
Max flow alarm | 4 | 20/500ms (LED ON/OFF) / 10s |
Back flow alarm | 5 | 20/500ms (LED ON/OFF) / 10s |
Product in test mode | Permanent flashing | 20/500ms (LED ON/OFF) / permanent |
Product configuration un-locked | Flash sequence as above 1…5, but inverted | 500/20ms (LED ON/OFF) / 10s |
Product configuration corrupt | Permanent ON | Permanent (LED ON) |
- Function control at the calculator
A functional control and plausibility check shall be done by observing the indications of flow rate and volume index, see calculators manual and operating instructions. - Putting into operation
After successful functional test AXONIC is now ready for use and final technical inspection.
Join us in creating a more resourceful world. To learn more visit itron.com
While Itron strives to make the content of its marketing materials as timely and accurate as possible, Itron makes no claims, promises, or guarantees about the accuracy, completeness, or adequacy of, and expressly disclaims liability for errors and omissions in, such materials. No warranty of any kind, implied, expressed, or statutory, including but not limited to the warranties of non-infringement of third party rights, title, merchantability, and fitness for a particular purpose, is given with respect to the content of these marketing materials. © Copyright 2022 Itron. All rights reserved. HE-0058.4-ig-ML-11.22 17768-AD