iSMACONTROLLI SfAR-1M-2DI1AO Expansion Module 2 Digital Inputs 1 Analog Output 

iSMACONTROLLI SfAR-1M-2DI1AO Expansion Module 2 Digital Inputs 1 Analog Output

Introduction

Thank you for choosing our product.

This manual will help you with proper handling and operating of the device.
The information included in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not discharge you from the liability of your own judgement and verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations concluded therein.

WARNING! 

Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.

Revision History
Rev. Date Description
3.1 25 May 2022 Rebranded

Safety Rules

  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty
    operation.
  • Use the product only within the operating ranges recommended in the specification
    (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.
  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
  • Avoid installing the product in close proximity to high-power electrical devices and
    cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high
    power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external
    communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Module Features

Purpose and Description of the Module

The SfAR-1M-2DI1AO module has 1 current analog output (0-20 mA or 4-20 mA) and 1 voltage analog output (0-10 V). Both outputs can be used at the same time. The module is equipped in two digital inputs. In addition, terminals IN1 and IN2 can be used to connect one encoder. Setting the output current or voltage value is done via RS485 (Modbus protocol), so the module can be easily integrated with popular PLCs, HMI, or PC equipped with an appropriate adapter.

This module is connected to the RS485 bus with a twisted-pair wire. Communication is via Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200.

The module is designed for mounting on a DIN rail in accordance with DIN EN 5002.
The module is equipped with a set of LEDs to indicate the status of inputs and outputs, which is useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program. It also allows for changing the parameters using the Modbus protocol.

Technical Specification
Power Supply Voltage 10-38 V DC; 10-28 V AC
Power consumption (with active Modbus transmission and high state on all inputs) 1 W at 24 V DC
2 VA at 24 V AC
Isolation Isolation between power supply and I/O 1000 V DC
Analog Outputs No. of outputs 1
Voltage output 0 V – 10 V (resolution 1.5 mV)
Max. load current 0-10 V 5 mA
Accuracy ± 2%
Current output 0 mA – 20 mA (resolution 5 μA)
4 mA – 20 mA (value in ‰ – 1000 steps) (resolution 16 μA)
Max. resistance 500 ohm
Accuracy ±1%
Output resolution 12 bits
DAC time processing 16 ms/channel
Digital Inputs No. of inputs 2
Voltage range 0-36 V
Low state “0” 0-3 V
High state “1” 6-36 V
Input impedance 4 kΩ
Isolation 1500 Vrms
Input Type PNP or NPN
Counters No. of counters 2
Resolution 32-bit
Frequency 1 kHz (max.)
Impulse width 500 μs (min.)
Temperature Work -20 °C to +65°C
Storage -40 °C to +85°C
Connectors Power supply 3 pin
Communication 3 pin
Inputs 2 x 3 pin
Configuration mini USB
Size Height 90 mm
Length 56.4 mm
Width 17.5 mm
Interface RS485 Up to 128 devices
Dimensions

The appearance and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication and IOs are at the bottom and top of the module. USB connector configuration and indicators located on the front of the module.

  • Figure 1. Dimensions
    Dimensions

Communication

Grounding and Shielding

In most cases, I/O modules will be installed in an enclosure along with the other devices, which generate electromagnetic radiation. Relays, contactors, transformers, motor invertors, etc., are examples of such devices. Radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module. Whether or not the SfAR modules are immune to such effects, the interferences must be suppressed at
their source if possible to ensure the proper functioning of the entire system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. It is recommended to at least follow the rules below:

  • line power cables must be routed with spatial separation from signal and data transmission cables;
  • analog and digital signal cables should also be separated;
  • it is recommended to use shielded cables for analog signals, cable shields should not be interrupted by intermediate terminals;
  • the shielding should be earthed directly after the cable enters the cabinet.

It is recommended to install interference suppressors when switching inductive loads (e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must be connected as close to the coil as possible.

Network Termination

Transmission line effects often present problems for data communication networks. These problems include reflections and signal attenuation. To eliminate the presence of reflections of signal from the end of the cable, the cable must be terminated at both ends
with a resistor across the line adequate to its characteristic impedance. Both ends must be terminated since the propagation is bidirectional. In case of an RS485 twisted pair cable, this termination is typically 120 Ω.

Types of Modbus Functions

There are 4 types of Modbus functions supported by the SfAR modules.

Table 3. Types of Modbus functions supported by the module 

Type Beginning Address Variable Access Modbus Command
1 00001 Digital Outputs Bit Read/write 1, 5, 15
2 10001 Digital Inputs Bit Read 2
3 30001 Input Registers Registered Read 3
4 40001 Output Registers Registered Read/write 4, 6, 16
Communication Settings

The data stored in the module’s memory is given in the 16-bit registers. The access to registers is via Modbus RTU or Modbus ASCII.

Default Settings

Table 4. Default settings 

Parameter Name Value
Address 1
Baud rate 19200
Parity No
Data bits 8
Stop bits 1
Reply delay [ms] 0
Modbus type RTU

Configuration Registers

Table 5. Configuration registers

Modbus Address Decimal Address Hex Address Name Values
40003 2 0x02 Baud Rate 0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005 4 0x04 Parity 0 – none
1 – odd
2 – even
3 – always 0
4 – always 1
40004 3 0x03 Stop Bits 1 – one stop bit 2 – two stop bits
40004 3 0x03 Data Bits 7 – 7 data bits

8 – 8 data bits

40006 5 0x05 Response Delay Time in ms
40007 6 0x06 Modbus Mode 0 – RTU

1 – ASCII

Watchdog

This 16-bits register specifies the time in milliseconds to watchdog reset. If the module does not receive any valid message within that time, all digital and analog outputs will be set to the default state.
This feature is useful if there is an interruption in data transmission and for security reasons. Output states must be set to the appropriate state in order to reassure the safety of persons or property.
The default value is 0 milliseconds, which means the watchdog function is disabled.

Indicators

Figure 2. Indicators 

Indicators

Table 6. Description of indicators

Indicator Description
ON The LED indicates that the module is correctly powered
TX The LED lights up when the unit received the correct packet and sends the answer
DI1, DI2 The LED indicates that on the input is high state
DO1, DO2 The LED indicates that the output is on

Connections

Block Diagram

Figure 3. Block diagram 

Block Diagram

Power Supply Connection

DC Power Connection

  • Figure 4. DC power connection
    DC Power Connection

AC Power Connection 

  • Figure 5. AC power connection
    AC Power Connection 
Communication Bus Connection
  • Figure 6. Communication bus connection
    Communication Bus Connection
Connection of Outputs

Connection of Voltage Output 

  • Figure 7. Connection of voltage output
    Connection of Voltage Output 

Connection of Current Output 

  • Figure 8. Connection of current output
    Connection of Current Output 

Connection of Digital Inputs

  • Figure 9. Connection of digital inputs
    Connection of Digital Inputs

Modules Registers

Registered Access

Table 7. Registered access 

Modbus Address Decimal Address Hex Address Register Name Access Description
30001 0 0x00 Version/Type Read Version and type of the device
30002 1 0x01 Address Read Module address
40003 2 0x02 Baud Rate Read/write RS485 baud rate
40004 3 0x03 Stop Bits & Data Bits Read/write No. of stop bits & data bits
40005 4 0x04 Parity Read/write Parity bit
40006 5 0x05 Response Delay Read/write Response delay in ms
40007 6 0x06 Modbus Mode Read/write Modbus mode (ASCII or RTU)
40009 8 0x08 Watchdog Read/write Watchdog
40013 12 0x0C Default Output State Read/write Default output state (after power on or watchdog reset)
40033 32 0x20 Received Packets LSR (Least Significant Register) Read/write No. of received packets
40034 33 0x21 Received Packets MSR (Most Significant Register) Read/write
40035 34 0x22 Incorrect Packets LSR Read/write No. of received packets with error
40036 35 0x23 Incorrect Packets MSR Read/write
40037 36 0x24 Sent Packets LSR Read/write No. of sent packets
40038 37 0x25 Sent Packets MSR Read/write
30051 50 0x32 Inputs Read Inputs state
40052 51 0x33 Outputs Read/write Output state
40053 52 0x34 Counter 1 LSR Read/write 32-bit counter 1
40054 53 0x35 Counter 1 MSR Read/write
40055 54 0x36 Counter 2 LSR Read/write 32-bit counter 2
Modbus Address Decimal Address Hex Address Register Name Access Description
40056 55 0x37 Counter 2 MSR Read/write  
40061 60 0x3C CCounter 1 LSR Read/write 32-bit value of captured counter 1
40062 61 0x3D CCounter 1 MSR Read/write
40063 62 0x3E CCounter 2 LSR Read/write 32-bit value of captured counter 2
40064 63 0x3F CCounter 2 MSR Read/write
40069 68 0x44 Counter Config 1 Read/write Counter configuration
+1 – time measurement (if 0 counting impulses)
+2 – autocatch counter
every 1 sec +4 – catch value when input low +8 – reset counter after catch +16 – reset counter if input low
+32 – encoder
40070 69 0x45 Counter Config 2 Read/write
40073 72 0x48 Catch Read/write Catch counter
40074 73 0x49 Status Read/write Captured counter
Bit Access

Table 8. Bit access

Modbus Address Decimal Address Hex Address Register Name Access Description
193 192 0x0C0 Default state of output 1 Read/write Default state of output 1
194 193 0x0C1 Default state of output 2 Read/write Default state of output 2
10801 800 0x320 Input 1 Read Input 1 state
10802 801 0x321 Input 2 Read Input 2 state
817 816 0x330 Output 1 Read/write Output 1 state
818 817 0x331 Output 2 Read/write Output 2 state
1153 1152 0x480 Capture 1 Read/write Capture counter 1
1154 1153 0x481 Capture 2 Read/write Capture counter 2
1169 1168 0x490 Captured 1 Read/write Captured value of counter 1
1170 1169 0x491 Captured 2 Read/write Captured value of counter 2

Configuration Software

The SfAR Configurator is the type of software, which is designed to set the communication module registers over Modbus network as well as to read and write the current value of other registers of the module. It is a convenient way to test the system as well as to observe real-time changes in the registers.
Communication with the module is via the USB cable. The module does not require any drivers.

Figure 10. PC connection 

PC connection 

The SfAR Configurator is a universal software, where it is possible to configure all available modules.

Figure 11. The SfAR Configurator

The SfAR Configurator

Customer Support

www.ismacontrolli.com
DMP266en | 3rd
Issue rev. 1 | 05/2022