Products - Roking d.o.o.Haiwell PLC User Manual
A Series Card-type PLC

Analog Module User Manual & Application Cases

Haiwell Card Type PLC Analog Module -

Analog Module User Manual

Product Model List and Dimension

Model Power (24V) Dimension
A04AI DC24V~0.1A MAX 25*95*65 mm
A04AO DC24V~0.1A MAX
A04XA DC24V~0.1A MAX
A08AI DC24V~0.1A MAX
A08A0 DC24V~0.15A MAX

Haiwell Card Type PLC Analog Module - 2

  1. Indicator
  2. PWR power indicator, LINK module communication indicator
  3. Terminal definition
  4. Removable terminal
  5. Guide rail buckle
  6. Module lock buckle
  7. Module positioning hole
  8. Module extension port
  9. 35mm DIN guide rail track

Indicator Description

  1. PWR: power indicator. green, constant light -Power normal; Not light – Power abnormal.
  2. LINK: multi-status indicator. three colors (Red. Yellow. Green), as follow:
Reference processing mode Module bus state LINK indicator state
Normal No communication of module No light
MPU has identified the module but no communication Constant light in green
Serial or parallel port in communication Green jitter: indicator on 30ms and off 30ms
A parallel power supply is not enough, must connect to the external power supply Without serial or parallel port in communication Yellow flicker: indicator on 0.5s and off 0.5s
With the serial or parallel port in communication Yellow is darkened and jitter alternately: indicator off 0.5s and jitter 0.5s
Firmware upgrade failed, re-upgrade the module firmware Without serial or parallel port in communication Red flicker: indicator on 0.5s and off 0.5s
With the serial or parallel port in communication Red is darkened and jitter alternately: indicator off 0.5s and jitter 0.5s
Hardware failure and maintenance Without serial or parallel port in communication Constant light in red

Power Supply Specification

Item DC Power Supply
Power supply voltage 24VDC -15%—+20%
Power supply frequency ______
Instantaneous surge MAX 20A 1.5ms @24VDC
Power loss time 10ms or less
Fuse 0.3A, 250V
24V Output voltage (for input and expansion) None
Isolation Type No Electrical isolation
Power Protection DC input power polarity reverse, over-voltage protection

Environmental Specifications for Product

Item Environment Specification
Temperature/Humidity Operating temperature:0~+55℃ Storage temperature:-25~+70℃ Humidity: 5~95%RH, No condensation
Vibration Resistance 10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10 times each for X-axis, Y-axis and Z-axis
Impact Resistance 15G, duration=11ms, 6 times each for X-axis, Y-axis, and Z-axis
Interference Immunity DC EFT:±2500V Surge:±1000V
Over-Voltage Resistance 1500VAC/1min between AC terminal and PE terminal, 500VAC/1min between DC terminal and PE terminal
Insulation Impedance Between AC terminal and PE terminal @500VDC,>=5MΩ, all input/output points to PE terminal @500VDC
Operating environment Avoid dust, moisture, corrosion, electric shock, and external shocks

Analog Input (AI) Specification

Item Voltage input Current input
Input range OV-+10V OV-+5V 1V-+5V 0-20mA 4-20mA
Resolution 2.5mV 1.25mV 1.25mV 5pA
Input impedance 6M0 2500
Maximum input range ±13V ± 30mA
Input indication LED light ON means normal OFF means external disconnect
Response time 5ms14 Channel
Digital input range 12 bits, Code range:0-32000(H series module 16 bits ND convert)
Precision 0.2% F.S
Power supply MPU uses an internal power supply, the extended module uses an external power supply of 24VDC ±10% 5VA
Isolation mode Optoelectronic isolation, Non-isolation between Channels, between analog and digital is optoelectronic isolation
Power consumption 24VDC ±20%,100mA(maximum)

Analog Output (AQ) Specification

Item

Voltage output

Current output

Output range OV- +10V OV-+5V 1V-+5V 0-20mA 4-20mA
Resolution 2.5mV 1.25mV 1.25mV 5uA 5uA
Output load impedance 1K0@10V 5000@10V ≤500Ω
Output indication LED ON means normal
Drive capability 10mA
Response time 3ms
Digital output range 12 bits, Code range:0-32000(H series module 16 bits D/A convert)
Precision 0.2% F.S
Power supply MPU uses an internal power supply, and expansion modules use an external power supply of 24VDC ±10% 5VA
Isolation mode Optoelectronic isolation, Non-isolation between Channels, between analog and digital is optoelectronic isolation
Power consumption 24VDC ±20%,100mA(maximum)

Analog Input (AI) Wiring Diagram

Haiwell Card Type PLC Analog Module - 3

Analog Output (AQ) Wiring Diagram

Haiwell Card Type PLC Analog Module - 4

Terminal Diagram

Haiwell Card Type PLC Analog Module - 5

Module Parameter Table

(CR code is corresponding to the Modbus register address)
4-channel analog module parameter table
Note: CR code is corresponding to the Modbus register address, the ray parts are read-only, and the white parts are readable and writable.

CR code Function Description
A04AI A04AO A04XA
00H Low byte for module code, and high byte for the module version number.
01H Communication address
02H Communication protocol: The low 4-bit of the low byte: 0 – N,8,2 For RTU, 1 – E,8,1 For RTU, 2 – O,8,1 For RTU, 3 – N,7,2 For
ASCII, 4 – E,7,1 For ASCII, 5 – O,7,1 For ASCII, 6 – N,8, 1 For RTU
The high 4-bit of the low byte: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 – 115200

 

 

CR code

Function Description

A04AI A04AO A04XA
03H~06H Module name
07H~08H Default IP address: 192.168.1.111
09~0AH Reserve
0BH High byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example subnet mask 255.255.255.0, b3~b0=1110), low byte reserved
0CH-0EH Reserve
0FH Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power supply
10H channel 1 input value channel 1 output value input channel 1 input value
11H channel 2 input value channel 2 output value input channel 2 input value
12H channel 3 input value channel 3 output value input channel 1 signal type, note 2
13H channel 4 input value channel 4 output value input channel 2 signal type, note 2
14H channel 1 signal type, note 2 channel 1 signal type, note 2 Use the engineering value mark, note 6
15H channel 2 signal type, note 2 channel 2 signal type, note 2 input channel 1 engineering lower limiting value
16H channel 3 signal type, note 2 channel 3 signal type, note 2 input channel 2 engineering lower limiting value
17H channel 4 signal type, note 2 channel 4 signal type, note 2 input channel 1 engineering upper limiting value
18H Use the engineering value mark, note 6 Use the engineering value mark, note 6 input channel 2 engineering upper limiting value
19H channel 1 engineering lower limiting value channel 1 engineering lower limiting value input channel 1 sampling frequency, note 1
1AH channel 2 engineering lower limiting value channel 2 engineering lower limiting value input channel 2 sampling frequency, note 1
1BH channel 3 engineering lower limiting value channel 3 engineering lower limiting value input channel 1 zero point correction value
1CH channel 4 engineering lower limiting value channel 4 engineering lower limiting value input channel 2 zero point correction value
1DH channel 1 engineering upper limiting value channel 1 engineering upper limiting value Channel 1~2 input disconnection alarm, note 5
1EH channel 2 engineering upper limiting value channel 2 engineering upper limiting value output channel 1 output value
1FH channel 3 engineering upper limiting value channel 3 engineering upper limiting value output channel 2 output value
20H channel 4 engineering upper limiting value channel 4 engineering upper limiting value output channel 1 signal type, note 2
21H channel 1 sampling frequency, note 1 power-off output mark, note 8 output channel 2 signal type, note 2
22H channel 2 sampling frequency, note 1 channel 1 power-off output value Use the engineering value mark, note 6
23H channel 3 sampling frequency, note 1 channel 2 power-off output value output channel 1 engineering lower limiting value
24H Channel 4 sampling frequency, note 1 channel 3 power-off output value output channel 2 engineering lower limiting value
25H channel 1 zero point correction value channel 4 power-off output value output channel 1 engineering upper limiting value
26H channel 2 zero point correction value Channel indicator status, note 7 output channel 2 engineering upper limiting value
27H channel 3 zero point correction value Reserve power-off output mark, note 8
28H channel 4 zero point correction value output channel 1 power-off output value
29H Channel 1~4 input disconnection alarm, note 5 output channel 2 power-off output value
2AH Reserve output channel indicator, note 7
2BH~2FH Reserve

channel analog module parameter table

Note: CR code is corresponding to the Modbus register address, the gray parts are read-only, and the white parts are readable and writable.

CR code

Function description

A08AI A08AO A08XA
00H Low byte for module code, and high byte for the module version number.
01H Communication address
 

02H

Communication protocol: The low 4-bit of the low byte: 0 – N,8,2 For RTU, 1 – E,8,1 For RTU, 2 – O,8,1 For RTU, 3 – N,7,2 For ASCII, 4 – E,7,1 For ASCII, 5 – O,7,1 For ASCII, 6 – N,8, 1 For RTU
The high 4-bit of the low byte: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 – 115200
03H~06H Module name
07H~08H Default IP address: 192.168.1.111
09~0AH Reserve
0BH High byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example subnet mask 255.255.255.0, b3~b0=1110), low byte reserved
0CH~0EH Reserve
0FH Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power supply
10H channel 1 input value channel 1 output value input channel 1 input value
11H channel 2 input value channel 2 output value input channel 2 input value
12H channel 3 input value channel 3 output value input channel 3 input value
13H channel 4 input value channel 4 output value input channel 4 input value
14H channel 5 input value channel 5 output value input channel 1 signal type, note 2
15H channel 6 input value channel 6 output value input channel 2 signal type, note 2
16H channel 7 input value channel 7 output value input channel 3 signal type, note 2
17H channel 8 input value channel 8 output value input channel 4 signal type, note 2
18H channel 1 signal type, note 2 channel 1 signal type, note 2 Use the engineering value mark, note 6
19H channel 2 signal type, note 2 channel 2 signal type, note 2 input channel 1 engineering lower limiting value
1AH channel 3 signal type, note 2 channel 3 signal type, note 2 input channel 2 engineering lower limiting value
1BH channel 4 signal type, note 2 channel 4 signal type, note 2 input channel 3 engineering lower limiting value
1CH channel 5 signal type, note 2 channel 5 signal type, note 2 input channel 4 engineering lower limiting value
1DH channel 6 signal type, note 2 channel 6 signal type, note 2 input channel 1 engineering upper limiting value
1EH channel 7 signal type, note 2 channel 7 signal type, note 2 input channel 2 engineering upper limiting value
1FH channel 8 signal type, note 2 channel 8 signal type, note 2 input channel 3 engineering upper limiting value
20H Use the engineering value mark, note 6 Use the engineering value mark, note 6 input channel 4 engineering upper limiting value
21H channel 1 engineering lower limiting value channel 1 engineering lower limiting value input channel 1 sampling frequency, note 1
22H channel 2 engineering lower limiting value channel 2 engineering lower limiting value input channel 2 sampling frequency, note 1
23H channel 3 engineering lower limiting value channel 3 engineering lower limiting value input channel 3 sampling frequency, note 1
24H channel 4 engineering lower limiting value channel 4 engineering lower limiting value input channel 4 sampling frequency, note 1
25H channel 5 engineering lower limiting value channel 5 engineering lower limiting value input channel 1 zero point correction value
26H channel 6 engineering lower limiting value channel 6 engineering lower limiting value input channel 2 zero point correction value
27H channel 7 engineering lower limiting value channel 7 engineering lower limiting value input channel 3 zero point correction value
28H channel 8 engineering lower limiting value channel 8 engineering lower limiting value input channel 4 zero point correction value
29H channel 1 engineering upper limiting value channel 1 engineering upper limiting value Channel 1~4 input disconnection alarm, note 5
2AH channel 2 engineering upper limiting value channel 2 engineering upper limiting value output channel 1 output value
2BH channel 3 engineering upper limiting value channel 3 engineering upper limiting value output channel 2 output value
2CH channel 4 engineering upper limiting value channel 4 engineering upper limiting value output channel 3 output value
2DH channel 5 engineering upper limiting value channel 5 engineering upper limiting value output channel 4 output value
2EH channel 6 engineering upper limiting value channel 6 engineering upper limiting value output channel 1 signal type, note 2
2FH channel 7 engineering upper limiting value channel 7 engineering upper limiting value output channel 2 signal type, note 2
30H channel 8 engineering upper limiting value channel 8 engineering upper limiting value output channel 3 signal type, note 2
31H channel 1 sampling frequency, note 1 power-off output mark output channel 4 signal type, note 2
32H channel 2 sampling frequency, note 1 channel 1 power-off output value Use the engineering value mark, note 6
33H channel 3 sampling frequency, note 1 channel 2 power-off output value output channel 1 engineering lower limiting value
34H channel 4 sampling frequency, note 1 channel 3 power-off output value output channel 2 engineering lower limiting value
35H channel 5 sampling frequency, note 1 channel 4 power-off output value output channel 3 engineering lower limiting value
36H channel 6 sampling frequency, note 1 channel 5 power-off output value output channel 4 engineering lower limiting value
37H channel 7 sampling frequency, note 1 channel 6 power-off output value output channel 1 engineering upper limiting value
38H channel 8 sampling frequency, note 1 channel 7 power-off output value output channel 2 engineering upper limiting value
39H channel 1 zero point correction value channel 8 power-off output value output channel 3 engineering upper limiting value
3AH channel 2 zero point correction value Channel indicator status output channel 4 engineering upper limiting value
3BH channel 3 zero point correction value Reserve power-off output mark
3CH channel 4 zero point correction value output channel 1 power-off output value
3DH channel 5 zero point correction value output channel 2 power-off output value
3EH channel 6 zero point correction value output channel 3 power-off output value
3FH channel 7 zero point correction value output channel 4 power-off output value
40H channel 8 zero point correction value output channel indicator
41H Channel 1~8 input disconnection alarm, note 5 Reserve
42H~4FH Reserve

Note:

  • Sampling frequency:0 – 2 times, 1 – 4 times, 2 – 8 times, 3 – 16 times, 4 – 32 times, 5 – 64 times, 6 – 128 times, 7 – 256 times
  • Signal type: 0 – [4,20]mA, 1 – [0,20]mA, 2 – [1,5]V, 3 – [0,5]V, 4 – [0,10]V
  • Disconnection alarm: Each bit indicates 1 channel, 0-normal, 1-disconnection
  • Use the engineering value mark: Each bit indicates 1 channel, 0-No, 1-Yes
  • Channel indicator status: Each bit indicates 1 channel, 0-off, 1-on
  • Power-off output mark: Each bit indicates 1 channel, 0-No, 1-Yes

Mounting and installation

The PLC should be secured to an enclosed cabinet while mounting. For heat dissipation, make sure to provide a minimum
clearance of 50mm between the unit and all sides of the cabinet. (See the figure.)
Rail Mounting: Use standard 35 mm rail.
Connecting Extended Module
Join the lower right parallel interface of the Last module (Host or Extension Module ) to the lower right of the parallel interface of next
module, then tight with two buckles on top and bottom.
The interface of the right side module is left for the extension interface for the next extension module.

Haiwell Card Type PLC Analog Module - 6

Analog Module Application Case

Expand module through the host PLC parallel port

Module power supply

Fan off ICONAn  Analog module can be the expansion module for an A series PLC; When the module is directly connected to the host PLC, no need to take an external power supply, the module is powered by the host PLC.

The analog needn’t be written any conversion program, read the analog register value directly.

For example, the host PLC AT16S0R, respectively, is expanded with three modules of A16DI, A16XDR, A04AI, and A04AO from left to right, assuming the scene:

  • Analog module A04AI input channel 1, signal type is 4-20mA, used to measure the pressure, the pressure range of 0.0~3.0Mpa;
  • Analog module A04AO input channel 1, signal type is 0-10V, used to control the inverter frequency of 0.0~50.0Hz;

First, enter the PLC programming software menu bar – view – hardware configuration, in accordance with the external order of actual modules to add the module models, after added, the analog address will be automatically arranged, as shown below:

Haiwell Card Type PLC Analog Module - 7

Haiwell analog module needn’t be written any conversion program, as for above pressure measurement, we only need to check the use of engineering value, set the lower limit value of 0 corresponding 0.0Mpa, set the upper limit value of 3000 indicating 3.000Mpa, the upper limit value 3000 hidden three decimal places can achieve magnification times and improve accuracy. Then we read the value of the analog input register AI0, if AI0 = 1234, then the actual value is 1.234Mpa.

Haiwell Card Type PLC Analog Module - 8

Similarly, for the analog output, check the use of engineering value, set the lower limit value of 0 indicating 0.0Hz, and set the upper limit value of 500 indicating 50.0Hz, if you want the inverter frequency output to be 25.6Hz, as long as the force the AQ0 value as 256 or through other logic instructions to output the AQ0 value of 256. As shown below:

Haiwell Card Type PLC Analog Module - 9

Programming skills

If you want to write the alarm program that pressure exceeds the setting value, for example, when the pressure is more than 1.25Mpa, it will alarm, the program of PLC can be written as follows:

Haiwell Card Type PLC Analog Module - 10

Display analog value on SCADA, HMI

If the SCADA, touch screen, text, and other PC software want to display the current pressure, and only need to set three decimal digits on the numerical display primitive, then the real value will be automatically reduced 1000 times in the configuration, that is the actual temperature value, for example, you can set 3 on decimal digits of Haiwell Cloud SCADA settings.Haiwell Card Type PLC Analog Module - 11

So that when the PLC read AI0 value, AI0=1234, that is the actual value of 1.234Mpa, there is no need to have data processing in PLC and configuration, only set the 3 decimal places on the numerical display primitive, then it will be automatically reduced by 1000 times, displaying the value of 1.234, that is the actual value of 1.234Mpa.

When the engineering value is not used, the default code value is 0 ~ 32000

When using the engineering value, the linear transformation is specified by the lower limit and the upper limit value, and the program is automatically transformed. When the engineering value is not used, all types are unified to correspond with 0 ~ 32000 code values.In the same case of pressure measurement, this time can according to the linear transformation formula: Out = (In – InDw) * (OutUp- OutDw) / (InUp- InDw) + OutDw to write the conversion program, or use the SC linear transformation instructions to calculate directly.

Haiwell analog is used easily, it is recommended to check the use of engineering value so that the analog will be very convenient without writing any program.

Module CR code application example: Read the module channel disconnection alarm

In this example, in order to read the external sensor disconnection information of the A08XA module, the disconnection alarm data of the A08XA module input channel 1-4 is stored in CR29, that is, 29H (hexadecimal), decimal 41. (More CR contents can be found in the software online help – hardware manual – expansion module parameters within the corresponding model). This program is as follows:

  • Slot: Position number, A08XA is the third module, so fill in 3;
  • CR: Module disconnection alarm CR41, that is, 29H (hexadecimal) = 41 (decimal), can be directly input 41 or 0x29 into the instruction CR terminal;
  • N: Number for readings, 1 register for 16 bits, low 4 bits corresponding channel 1-4, disconnection for 1 (ON), normal for 0 (OFF).

Haiwell Card Type PLC Analog Module - 12

Thanks for choosing Haiwell Products, If you have any questions about our products or services, please let us know!
Harwell website: www.haiwell.com Copyright © 2005 Xiamen Haiwell Technology Co., Ltd.