EMS FCX Series FireCell Combined Sounder Detector Visual Indicator

 Detector Visual Indicator

INSTALLATION GUIDE

Combined Sounder/Detector/Visual Indicator

Example shown:

 Detector Visual Indicator

Part no Description
FCX-174-001 Multisensor Smoke Detector Only
FCX-175-001 Heat A1R Detector Only
FCX-176-001 Heat CS Detector Only
FCX-177-001 Optical Smoke Detector Only
FCX-191-000 Sounder/Detector Base Only
FCX-191-200 Sounder/Detector/Red Visual Indicator Base Only

See the Specification section for compliance information.

1. Pre installation

Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.

  • Ensure that the device is installed as per the site survey.
  • The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
  • Do NOT press the log on button on a pre-programmed device, as this will cause communication with the control panel to be lost. Should this happen, delete the device from the system and add it back on.
  • This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.
  • For pre-2024 versions of this device with a 4-way power/sounder configuration switch, refer to the legacy version of this manual.

2. Components

 Detector Visual Indicator

1. Dust cover,
2. Detector,
3. Wireless module,
4. Mounting plate

3. Fix mounting plate

Remove the mounting plate by turning the device ANTICLOCKWISE, to release it from the mounting plate.

  • Use both fixing positions to ensure a firm fixing.
  • Use suitable fasteners and fixings

 Detector Visual Indicator

4. Power device

 Detector Visual Indicator

  • When fitting / replacing batteries; observe correct polarity, using only specified batteries.
  • Set the P (POWER) switch to the ON position to power the device. See the ‘Switches’ section for other available switch settings.
  • Once powered, reassemble the device.

5. Device locking

 Detector Visual Indicator

  • To lock the detector into the wireless module, remove the cut out (shaded) section as shown.
  • To unlock the detector, insert a 1.5 mm allen key and lever the allen key towards the outside of the device and turn the detector anticlockwise to release.
  • The wireless module can also be locked into the mounting plate by removing the shaded section shown and fitting a 5/16 Phillips pan head screw.

6. Important

  • Remove dust cover before use.
  • The device should be tested upon installation and in accordance with local requirements.
  • Testing should only be carried out by a fully trained competent person.
  • The manufacturer recommends regular functional testing of at least once per annum or in accordance with local codes of practice.
  • Cleaning and repairs must be undertaken by the manufacturers authorised representative.
  • Do not open the case to clean inside the detector.
  • When activated, the device will sound for a maximum of 30 minutes before switching off to conserve battery life.

7. Configuration

This device is intended to form part of a wireless fire alarm system. The device’s loop address is configured within the user interface’s menu structure.

 Detector Visual Indicator

Refer to the programming manual for full programming details.

FireCell = MK98
Fusion = TSD062
WZM = TSD143

Free to download from www.emsgroup.co.uk

8. Switches

Device power/volume/flash only (set on wireless module)

 Detector Visual Indicator

The PVF switches control the device’s power supply, adjust the sounder volume and, if necessary, initiate flash only mode (sounder off).

 Detector Visual Indicator

= Default setting.

* Flash only mode is applicable to the FCX-191-200 model only. If selected, this is not within the scope of EN54-3.

Sounder tone (set on wireless module)

Switches 1 to 5 select the sounder tone.
= Default setting.

 Detector Visual Indicator

Note: Tones 1, 2, 3, 5, 6, 7, 10, 13, 21 are EN54-3 approved tones. Secondary tones and low volume settings are not approved.

 Detector Visual Indicator

Specification

 Detector Visual Indicator

Regulatory information

 Detector Visual Indicator

 

Specifications:

  • Operating temperature: 0°C to 50°C
  • Storage temperature: -20°C to 60°C
  • Humidity: 0 to 95% non-condensing
  • Power Supply: 3 x AA alkaline batteries (Panasonic LR6AD
    Powerline / Varta 4006 Industrial)

QUICK Usage Instructions:

1. Pre-Installation:

Ensure that the installation complies with local installation codes and is carried out by a trained individual.

2. Components:

The package includes a dust cover, detector, wireless module, and mounting plate.

3. Fix Mounting Plate:

To fix the mounting plate, turn the device ANTICLOCKWISE to release it from the mounting plate.

4. Power Device:

Insert 3 x AA alkaline batteries into the designated compartment to power the device.

5. Device Locking:

Ensure the device is securely locked in place after installation.

6. Important!

This device is part of a wireless fire alarm system and should be configured within the user interface’s menu structure.

7. Configuration:

The loop address of the device can be configured using the user interface menu.

8. Switches:

The switches control power/volume/flash settings. Refer to the user manual for detailed switch settings based on the model.


Frequently Asked Questions (FAQ):

Q: Can I use rechargeable batteries with this device?

A: It is recommended to use AA alkaline batteries for optimal performance. Rechargeable batteries may not provide the same level of reliability.

Q: How do I change the sounder tone?

A: The sounder tone can be changed using the switches on the wireless module. Refer to the provided tone chart in the user manual for approved tones and their descriptions.

Documents / Resources

EMS FCX Series FireCell Combined Sounder Detector Visual Indicator [pdf] Installation Guide
FCX-174-001, FCX-175-001, FCX-176-001, FCX-177-001, FCX-191-000, FCX-191-200, FCX Series FireCell Combined Sounder Detector Visual Indicator, FireCell Combined Sounder Detector Visual Indicator, Sounder Detector Visual Indicator, Detector Visual Indicator, Visual Indicator

References

Leave a comment

Your email address will not be published. Required fields are marked *