Danfoss EVR 2 – 22 Solenoid Valves Normally Open Instructions
Instruction
Refrigerants CFC, HCFC, HFC
- EVR (NC flare)
- EVR (NC solder)
- EVR (NC flange)
- EVR (NO solder)
Dimension
EVR | Nm | kpm | ft-lbs | Torx size |
2, 3 | 1.4 | 0.15 | 1 | T 15 |
4, 6, 8 | 2.5 | 0.25 | 1.8 | T15 |
EVR | Nm | kpm | ft-lbs | Torx size |
10, 15, 18 | 2.8 | 0.3 | 2 | T 25 |
20, 22 | 12 | 1.2 | 9 | T 40 |
Min. medium temperature: -40°C (-40°F)
Max. medium temperature: 105°C (221°F)
Max. working pressure: EVR 2-8 PB = 45.2bar
Max, working pressure: EVR 10 PB = 35bar
Max, working pressure: EVR 15-22 PB = 32bar
Max. opening diff. pressure (MOPD):
Warning
Never switch on power to the coil when the coil is dismounted from the valve. Otherwise the coil may be damaged and there is risk of injuries and burns.
EVR 4 – 8
EVR 4 – 8 Dismounting gasket :
Pres and twist
EVR 2- 3 (NC)
EVR 4 – 22 (NC)
EVR 4 – 10 (NC)
EVR 15 – 22 (NC)
Installation Instruction
Documents / Resources
![]() |
Danfoss EVR 2 - 22 Solenoid Valves Normally Open [pdf] Instructions 032R9545, EVR 2, 3 4, EVR 4 - 8, EVR 2 - 22 Solenoid Valves Normally Open, EVR 2 - 22, Solenoid Valves Normally Open, Valves Normally Open, Normally Open |