Danfoss LOGOINSTALLATION INSTRUCTIONS:
MCD DEVICENET MODULE
Order Code: 175G9002

Important User Information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.
It is the installer’s responsibility to follow all instructions in this manual and to follow correct electrical practice.

Installation

Laserliner 082.015A DampFinder Compact Moisture Measuring Instrument - icon 2CAUTION
Remove mains and control voltage from the soft starter before attaching or removing accessories. Failure to do so may damage the equipment.
Install the Device Net Module using the following procedure:

  1. Remove control power and mains supply from the soft starter.
  2. Attach the module to the soft starter as illustrated.
  3. Set the Device Net Module Node Address (MAC ID) and Data Rate.
  4. Apply control power to the soft starter.
  5. Insert the network connector into the module and power up the Device Net network.

2.1. Physical Installation

  1. Fully pull out the top and bottom retaining clips on the module.
  2. Line up the module with the comms port slot.
  3. Push in the top and bottom retaining clips to secure the module to the starter.Danfoss 175G9002 VLT MCD DeviceNet Module - Physical

Remove the module using the following procedure:

  1. Take the module off-line.
  2. Remove the Device Net connector.
  3. Remove control power and mains supply from the soft starter.
  4. Fully pull out the top and bottom retaining clips on the module.
  5. Pull the module away from the soft starter.

Laserliner 082.015A DampFinder Compact Moisture Measuring Instrument - icon 2CAUTION
Network designs must decrease the maximum allowable cumulative dropline length by 400 mm for every module installed on the network. Failure to do so may result in network communication errors and decreased reliability.
Example: ODVA specifies a maximum cumulative dropline length of 156 m on a network operating at 125 kb/s. If six modules were installed on this network, the total cumulative dropline length would need to be decreased to 153.6 m.

Configuration

The Device Net Module is a Group 2 slave device, using a predefined master/slave connection set.
I/O data is produced and consumed using polled I/O messaging.
The soft starter must be added to the Device Net manager project using the EDS file and configuration/management software tool. This file is available from www.danfoss.com/drives. In order to operate successfully, the correct EDS file must be used. An on-screen graphics bitmap file (device.bmp) is also available.

Adjustment

The factory default settings for the rotary adjustment switches are:

Danfoss 175G9002 VLT MCD DeviceNet Module - switches

Changes to the rotary switch settings take effect when the Device Net network is next powered up.
Danfoss 175G9002 VLT MCD DeviceNet Module - icon5N.B.!:
The Data Rate and Node Address (MAC ID) must be set locally on the module.
These cannot be set using DeviceNet management software.
When the Data Rate and MSD Node Address (MAC ID) rotary switches are set on PGM position, the module uses the previously used valid on-line Data Rate and Node Address (MAC ID).

Connection

MCD 200: For the MCD Device Net Module to accept serial commands, a link must be fitted across terminals A1-N2 on the soft starter.
In order for the MCD 500 to accept commands from the serial network, the soft starter must be in Auto On mode and links must be fitted to terminals 17, 18 and 25, 18.
In Hand On mode, the starter will not accept commands from the serial network but the starter’s status can still be monitored.

Danfoss 175G9002 VLT MCD DeviceNet Module - Connection

1 MCD 200 1 MCD 500 (Auto On mode)
17, 18: Stop
25, 18: Reset
2 MCD Device Net Module 2 MCD Device Net Module
3 Standard connection onto Device Net network 3 Standard connection onto Device Net network

Danfoss 175G9002 VLT MCD DeviceNet Module - icon5N.B.!:
If MCD 500 parameter 3-2 Comms in Remote is set to Disable Comms in Remote, the starter will not accept start or stop commands from the serial network (the starter will still accept reset commands and allow status monitoring).

Module and Network LEDs

The Module LED indicates the condition of the power supply and module operation.
The Network LED indicates status of the communication link between the Device Net Module and the network Master.

Danfoss 175G9002 VLT MCD DeviceNet Module - LED indicates

LED State Description
 

(1)(Module)

Off Network power off
Green Normal operation
Red Unrecoverable fault
Red/Green flashing Self Test mode
 

(2)(Network)

Off Duplicate MAC ID test has not been completed
Green flashing Online but no connection with Master
Green Online and allocated to a Master
Red flashing One or more timed out I/O connections
Red Failed communication between module and Master
Red/Green flashing Communication faulted and received an Identity communication faulted request

Danfoss 175G9002 VLT MCD DeviceNet Module - icon5N.B.!:
When a communications failure occurs, the soft starter may trip if the Communication Timeout parameter for the network is set greater than zero. When communication is restored, the soft starter must be reset.

Device Net Polled I/O Structure

Once the EDS file has been loaded, the Device Net Module must be added to the scanner list with parameters shown in the following table:

Parameter Value
I/O connection type Polled
Poll receive size 14 bytes
Poll transmit size 2 bytes

Once the soft starter, module and Master have been set up, configured and powered up, the Master will transmit 2 bytes of data to the module and receive 14 bytes of data from the module.
Master > Slave polled I/O output data is as follows:

Byte Bit Function
0 0 0 = Stop command
1 = Start command
1 0 = Enable Start or Stop command
1 = Quick Stop (i.e. coast to stop) and disable Start command
2 0 = Enable Start or Stop command
1 = Reset command and disable Start command
3 to 7 Reserved
1 0 to 1 0 = Use soft starter remote input to select motor set 1 = Use primary motor set when starting 1
2 = Use secondary motor set when starting 1
3 = Reserved
2 to 7 Reserved

1Ensure that the programmable input is not set to Motor Set Select before using this function.
Slave > Master polled I/O input data is as follows:

Byte Bit Function Value
0 0 Trip 1 = Tripped
1 Warning 1 = Warning
2 Running 0 = Unknown, not ready, ready to start or tripped 1 = Starting, running, stopping or jogging
3 Reserved
4 Ready 0 = Start or stop command not acceptable 1 = Start or stop command acceptable
5 Control from Net 1 = Always except in Program mode
6 Local/Remote 0 = Local control
1 = Remote control
7 At reference 1 = Running (full voltage at the motor)
1 0 to 7 Status 0 = Unknown (menu open)
2 = Starter not ready (restart delay, thermal delay or run simulation)
3 = Ready to start (including warning state) 4 = Starting or running
5 = Soft stopping 7 = Trip
8 = Jog forward
9 = Jog reverse
2 0 to 7 Trip/Warning code See trip code table.
3 0 Initialised 1 = Phase sequence bit is valid (bit 1) after 1st start
1 Phase sequence 1 = Positive phase sequence detected
2 to 7 Reserved
4 1 0 to 7 Motor current (low byte) Current (A)
5 1 0 to 7 Motor current (high byte)
6 0 to 7 Current %FLC (low byte) Current as a percentage of soft starter FLC setting (%)
7 0 to 7 Current %FLC (high byte)
8 0 to 7 % Motor 1 temperature Motor 1 thermal model
9 0 to 7 % Motor 2 temperature Motor 2 thermal model
10 0 to 7 % Power factor Percentage power factor (100 = power factor of 1)
11 0 to 7 Power (low byte) Power low byte, scaled by power scale
12 0 to 3 Power (high nibble) Power high nibble, scaled by power scale
4 to 5 Power scale 0 = Multiply power by 10 to get W 1 = Multiply power by 100 to get W 2 = Power (kW)
3 = Multiply power by 10 to get kW
6 to 7 Reserved
13 0 to 3 Digital Input state 0 = Start (0 = open, 1 = closed)
1 = Stop
2 = Reset 3 = Input A
4 to 7 Reserved

1For models MCD5-0428C and smaller this value will be 10 times greater than the value displayed on the LCP.

7.1.1. Trip Codes

Code Trip Type MCD 201 MCD 202 MCD 500
0 No trip Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
11 Input A trip Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
20 Motor overload (thermal model) Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
21 Heatsink overtemperature Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
23 L1 phase loss Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
24 L2 phase loss Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
25 L3 phase loss Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
26 Current imbalance Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
28 Instantaneous overcurrent Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
29 Undercurrent Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
50 Power loss/Power circuit Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
54 Phase sequence Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
55 Frequency (Mains supply) Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
60 Unsupported option (function not available in inside delta) Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
61 FLC too high (FLC out of range) Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
62 Parameter out of Range Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
70 Miscellaneous Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
75 Motor thermistor Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
101 Excess start time Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
102 Motor connection Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
104 Internal fault x (where x is the fault code detailed in the table below). Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
113 Starter communication (between module and soft starter) Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
114 Network communication (between module and network) Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
115 L1-T1 shorted Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
116 L2-T2 shorted Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
117 L3-T3 shorted Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
119 Time-overcurrent (Bypass overload) Danfoss 175G9002 VLT MCD DeviceNet Module - icon1 Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
121 Battery/clock Danfoss 175G9002 VLT MCD DeviceNet Module - icon1
122 Thermistor circuit Danfoss 175G9002 VLT MCD DeviceNet Module - icon1

* For MCD 500, time-overcurrent protection is only available on internally bypassed models.
The table below details the internal fault code associated with trip code 104.

Internal fault Message displayed on the LCP
70 ~ 72 Current Read Err Lx
73 Power On in Simulation mode
74 ~ 76 Motor connection Tx
77 ~ 79 Firing fail SCRx
80 ~ 82 VZC Fail Px
83 Low Control Volts
84 ~ 98 Internal fault X
Contact your local supplier with the fault code (X).

Parameter Object

The Device Net Module supports parameter objects through explicit messaging. Soft starter parameters can be uploaded (written) and downloaded (read) using Device Net management software. When the Device Net Module is powered up, it automatically obtains parameter information from the soft starter.

Detail Value (Hex) Comment
Class 0F Parameter object address
Instance 1 ~ xxx xxx = maximum soft starter parameter number
Attribute ID 01 Always 0x01
Get Service 0E Read single soft starter parameter value
Set Service 10 Write single soft starter parameter value

Danfoss 175G9002 VLT MCD DeviceNet Module - icon5N.B.!:
Only available on MCD 500 soft starters. For parameter details, see the soft starter User Manual.

Specifications

Enclosure
Dimensions ………………… 40 mm (W) x 166 mm (H) x 90 mm (D)
Weight ……………………………………. 250 g
Protection …………………….. IP20
Mounting
Spring-action plastic mounting clips (x 2)
Connections
Soft starter …………………………. 6-way pin assembly
Network ………………………………. 5-way male and unpluggable female connector (supplied)
Maximum cable size ………………………………………. 2.5 mm2
Contacts …………………………………….. Gold flash
Settings
Node address (MAC ID)
Setting …………………………………… Rotary switches
Range ……………….. 0 to 63 (63, factory default)
Data rate
Setting ………………………… Rotary switch
Options ……………………………………… 125 kB, 250 kB, 500 kB (125 kB, factory default)
Power
Consumption
steady state ……………….. 19 mA at 25 VDC ……………… 31 mA at 11 VDC in-rush (at 24 VDC) ……………… 1.8 A maximum for 2 ms
Galvanically isolated
Certification
CE …………………………. IEC 60947-4-2

Danfoss 175G9002 VLT MCD DeviceNet Module - bar codeMG17HA02 – VLT® is a registered