Home » BITMAIN » BITMAIN ANTRACK Hydro Cooling Mining User Guide 

BITMAIN ANTRACK Hydro Cooling Mining
Specifications
Product Glance |
Value |
Model |
ANTRACK |
Version |
V1 |
Capacity |
4 units ANTMINER (Hydro) |
Maximum load, kW |
24 |
Detailed Characteristics |
Value |
Hardware configuration |
Size (Length*Width*Height), mm (without package) |
1000*600*2100 |
Size (Length*Width*Height), mm (with package) |
2260*1130*780 |
Net weight, kg (without package) |
207 |
Gross weight, kg (with package) |
300 |
Network connection mode |
RJ45 Ethernet 10/100M |
Power supply |
Power supply AC input voltage, Volt(1-1) |
380~415V AC |
Power supply AC input frequency range, Hz |
50~60 |
Maximum power supply AC input current, Amp(1-2) |
80 |
Fan |
Rated power, W |
120 |
Noise, dBA@1m |
68 |
Size (Length*Height*Thickness), mm |
280*280*80 |
Pump |
Rated power, W |
450 |
Noise, dBA@1m |
55 |
Size (Length*Width* Height), mm |
360*210*268 |
Plate heat exchanger |
Maximum heat exchange power, kW |
30 |
Size (Length*Width* Height), mm |
305*106*64 |
Diameter of water pipe connector, mm |
DN25 |
Environment requirements |
Ambient temperature, °C |
15~45 |
Water flow, L/min |
32.0~40.0 |
Water pressure, bar |
≤3.5 |
Working fluid(1-3) |
Antifreeze (10%) |
Liquid PH |
7.8~8.5 |
Storage temperature, °C |
-20~70 |
Operation humidity(non-condensing), RH |
10~90% |
Product Usage Instructions
- Caution: Ensure correct input voltage to prevent server damage.
- Fluid Maintenance: If water conductivity reaches 100 s/cm, replace the fluid. Initial conductivity should be less than 20 s/cm.
- Caution: Wrong input voltage may cause server damaged.
- Three-phase AC input.
- If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.
Frequently Asked Questions
- Q: What should I do if the server is not powering on?
- A: Check the input voltage and ensure it is within the specified range to avoid damage.
- Q: How often should the fluid be replaced?
- A: Replace the fluid if the water conductivity reaches 100 s/cm. Initially, ensure the conductivity is less than 20 s/cm.