Beijer ELECTRONICS GL-9031 Network Adapter Module

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-product

Specifications

  • Product Name: GL-9031 Network Adapter Module
  • Network Type: CC-Link
  • Version: Light
  • Maximum Slices: 12

Product Information

  • The GL-9031 Network Adapter Module is a CC-Link network adapter designed for use in the G-series system by Beijer Electronics. It offers a light version with a maximum capacity of 12 slices, providing seamless integration within the system.

Usage Instructions

Installation

  1. Ensure that the power source is disconnected before installation.
  2. Align the module with the designated slot in the G-series system.
  3. Gently push the module into place until securely connected.

Setup

  1. Power on the G-series system and access the configuration settings.
  2. Locate the network adapter settings and configure them according to your network requirements.
  3. Save the settings and restart the system to apply the changes.

Usage

  1. Once installed and set up, the network adapter module will facilitate communication within the CC-Link network.
  2. Monitor the LED indicators to ensure proper network connectivity.

About This Manual

This manual contains information on the software and hardware features of the Beijer Electronics GL-9031 Network Adapter Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product.

Symbols Used in This Manual

This publication includes Warning, Caution, Note and Important icons where appropriate, to point out safety-related, or other important information. The corresponding symbols should be interpreted as follows:

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-1WARNING

The Warning icon indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury, and major damage to the product.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-2CAUTION

The Caution icon indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury, and moderate damage to the product.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-3NOTE

The Note icon alerts the reader to relevant facts and conditions.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-4IMPORTANT

The Important icon highlights important information.

Safety

Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions!

In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product.

The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.

Product Certifications

The product has the following product certifications.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-5.

General Safety Requirements

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-1WARNING

  • Do not assemble the products and wires with power connected to the system. Doing so cause an “arc flash”, which can result in unexpected dangerous events (burns, fire, flying objects, blast pressure, sound blast, heat).
  • Do not touch terminal blocks or IO modules when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
  • Never let external metallic objects touch the product when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
  • Do not place the product near inflammable material. Doing so may cause a fire.
  • All wiring work should be performed by an electrical engineer.
  • When handling the modules, ensure that all persons, the workplace and the packing are well grounded. Avoid touching conductive components, the modules contain electronic components that may be destroyed by electrostatic discharge.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-2CAUTION

  • Never use the product in environments with temperature over 60℃. Avoid placing the product in direct sunlight.
  • Never use the product in environments with over 90% humidity.
  • Always use the product in environments with pollution degree 1 or 2.
  • Use standard cables for wiring.

About the G-series System

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-6

System overview

  • Network Adapter Module: The network adapter module forms the link between the field bus and the field devices with the expansion modules. The connection to different field bus systems can be established by each of the corresponding network adapter module, e.g., for MODBUS TCP, Ethernet IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc.
  • Expansion Module: Expansion module types: Digital IO, Analog IO, and Special modules.
  • Messaging: The system uses two types of messaging: Service messaging and IO messaging.

IO Process Data Mapping

An expansion module has three types of data: IO data, configuration parameter, and memory register. The data exchange between the network adapter and the expansion modules is made via IO process image data by internal protocol.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-7

Data flow between network adapter (63 slots) and expansion modules

The input and output image data depend on the slot position and the data type of the expansion slot. The ordering of input and output process image data is based on the expansion slot position. Calculations for this arrangement are included in the manuals for network adapter and programmable IO modules.

Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data.

Specifications

Environmental Specifications

Operating temperature -20°C – 60°C
UL temperature -20°C – 60°C
Storage temperature -40°C – 85°C
Relative humidity 5% – 90% non-condensing
Mounting DIN rail
Shock operating IEC 60068-2-27 (15G)
Vibration resistance IEC 60068-2-6 (4 g)
Industrial emissions EN 61000-6-4: 2019
Industrial immunity EN 61000-6-2: 2019
Installation position Vertical and horizontal
Product certifications CE, FCC, UL, cUL

General Specifications

UL system power Supply voltage: 24 VDC nominal, class 2
System power Supply voltage: 24 VDC nominal Supply voltage range: 15 – 28.8 VDC

Reverse polarity protection

Power dissipation 35 mA typical @ 24 VDC
Current for IO module 1.0 A @ 5 VDC
Isolation System power to internal logic: Non-isolation

System power IO driver: Isolation

UL field power Supply voltage: 24 VDC nominal, class 2
Field power Supply voltage: 24 VDC typical (max. 28.8 VDC)

NOTE! The field power range depends on the IO module series. Refer to the IO module specification for specific details.

Max. current field power contact Max. DC 8 A
Wiring IO cable max. 2.0 mm2 (AWG 14)
Weight 71 g
Dimensions 22 mm x 109 mm x 70 mm

Communication Interface Specification

Adapter type Slave node (CC-Link Version 1)
Max. expansion slot 12 slots
IO data size System area: 16 points

RX/RY: 112 points (4staion occupied) RWr/RWw: 16 points (4station occupied)

Maximum number of stations per master station 42
The number of device station 1 – 64
Baud rate 156 / 625 / 2500 / 5000 / 10000 Kbps
Interface connector 5 Pin open connector
LED indicators 4 status LEDs:

Module status (MOD) – Green/Red Current running status (NET) – Green Error status (ERR) – Green

Expansion module status (IOS) – Green/Red

Module location Starter module left side of G-series system
Station class Remote device station

Wiring Diagram

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-8

Pin no. Signal description
1 System power, 24 V
2 System power, ground
3 Frame ground
4 Field power, ground
5 Field power, 24 V

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-1WARNING

  • Never connect system power to field power! Use separate power supplies.

LED Indicator

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-9

LED LED function / description LED color
MOD Module status Green/Red
RUN Communication status Green
ERR Error status Green
IOS Expansion module status Green/Red

MOD (Module Status)

Status LED Indicates
Not powered OFF Power is not supplied to the unit.
Normal, operational Green The unit is operating in normal condition.
Device in standby Red EEPROM parameter is not initialized yet.

Serial number is zero value (0x00000000).

RUN (Network Status)

Status LED Indicates
Init / No communication Red No communication / Communication disconnection.
Communication Green Normal communication.
Communication error OFF Communication error / Token passing

ERR (Error Status)

Status LED Indicates
No error OFF No error.
Invalid configuration Red Exceeded number range of device station.

IOS (Expansion Module Status)

Status LED Indicates
Not powered, no expansion module OFF Device has no expansion module or is not powered.
No expansion module Flashing red Adapter has no expansion module.
Status LED Indicates
Internal bus connection, run exchanging IO data Green Exchanging IO data.
Expansion configuration failed Red Failed to initialize expansion module.

•   Detect invalid expansion module ID.

•   Overflowed input/output size.

•   Too many expansion modules.

•   Initialization failure.

•   Communication error.

•   Changed expansion module configuration.

•   Mismatch vendor code between adapter and expansion module.

5-Pin Open Connector

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-10

Connector no. Signal name Description
1 DATA+ Transceiver data high
2 DATA- Transceiver data low
3 GND Signal common
4 Shield Shield
5 FG Frame Ground. Internally shorted with shield.

Dip Switches

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-11

Pole# Description
1 Node address setting Node address set-up is dip switch.

Max. node Address is 64. See Node address setting examples below.

2
3
4
5
6
7
8 Baud rate #1 156 Kbps: 8 OFF, 9 OFF, 10 OFF
9 Baud rate #2 625 Kbps: 8 ON, 9 OFF, 10 OFF
10 Baud rate #3 2.5 Mbps: 8 OFF, 9 ON, 10 OFF
    5 Mbps: 8 ON, 9 ON, 10 OFF
    10 Mbps: 8 OFF, 9 OFF, 10 ON
    Default baud rate: 156 Kbps

Node address pole setting examples

  #1(

1)

#2(

2)

#3(

4)

#4(

8)

#5(

10)

#6(

20)

#7(

40)

#8 #9 #1

0

ID = 0 OFF OFF OFF OFF OFF OFF OFF
ID = 1 ON OFF OFF OFF OFF OFF OFF
ID = 10 OFF OFF OFF OFF ON OFF OFF
ID = 42 OFF ON OFF OFF OFF OFF ON
ID = 64 OFF OFF ON OFF OFF ON ON

4 Pole Switch

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-12

Pole# Description
1 Fixed station OFF: Auto addressable.

ON: 4station occupied.

Pole# Description
2 Mode Mode switch is ON, the IO size will be increased 2 bytes more respectively.
3 STOP action OFF: Master value dependent.

ON: Output clear.

4 Reserved

2 Pole Switch

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-13

Pole# Description
1 Terminator resistor 1 ON, 2 ON: Terminator resistor set.

Other: Terminator resistor not set.

2

Hardware Setup

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-2CAUTION

  • Always read this chapter before installing the module!
  • Hot surface! The surface of the housing can become hot during operation. If the device is used in high ambient temperatures, always let the device cool down before touching it.
  • Working on energized devices can damage the equipment! Always turn off the power supply before working on the device.

Space Requirements

The following drawings show the space requirements when installing the G-series modules. The spacing creates space for ventilation, and prevents conducted electromagnetic interference from influencing the operation. Installation position is valid vertical and horizontal. The drawings are illustrative and may be out of proportion.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-2CAUTION

NOT following the space requirements may result in damaging the product.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-14

Mount Module to DIN Rail

The following chapters describe how to mount the module to the DIN rail.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-2CAUTION

The module must be fixed to the DIN rail with the locking levers.

Mount GL-9XXX or GT-XXXX Module

The following instructions apply to these module types:

  • GL-9XXX
  • GT-1XXX
  • GT-2XXX
  • GT-3XXX
  • GT-4XXX
  • GT-5XXX
  • GT-7XXX

GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-15

Mount GN-9XXX Module

To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions:

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-16

Field Power and Data Pins

Communication between the G-series network adapter and the expansion module, as well as system /field power supply of the bus modules is carried out via the internal bus. It is comprised of 2 Field Power Pins and 6 Data Pins.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-1WARNING

Do not touch the data and field power pins! Touching can result in soiling and damage by ESD noise.

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-17

Pin no. Name Description
P1 System VCC System supply voltage (5 VDC)
P2 System GND System ground
P3 Token output Token output port of processor module
P4 Serial output Transmitter output port of processor module
P5 Serial input Receiver input port of processor module
P6 Reserved Reserved for bypass token
P7 Field GND Field ground
P8 Field VCC Field supply voltage (24 VDC)

Process Image

Remote Input Area

No. of occupied station Size Signal name
1 station: 16 points 2 bytes Discrete input
2 stations: 48 points 6 bytes
3 stations: 80 points 10 bytes
4 stations: 112 points 14 bytes
System area 2 bytes System

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-3NOTE

When Mode switch is ON, the IO size will be increased 2 bytes more respectively.

Remote Output Area

No. of occupied station Size Signal name
1 station: 16 points 2 bytes Discrete input
2 stations: 48 points 6 bytes
3 stations: 80 points 10 bytes
4 stations: 112 points 14 bytes
System area 2 bytes System

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-3NOTE

When Mode switch is ON, the IO size will be increased 2 bytes more respectively.

RWr / RWw Area

Analog in / Special module

Address Configuration Size
RWr0 – RWr3 1 station 4 words
RWr4 – RWr7 2 stations 8 words
RWr8 – RWr11 3 stations 12 words
RWr12 – RWr27 4 stations 16 words

Analog out / Special module

Address Configuration Size
RWw0 – RWw3 1 station 4 words
Address Configuration Size
RWw4 – RWw7 2 stations 8 words
RWw8 – RWw11 3 stations 12 words
RWw12 – RWw27 4 stations 16 words

System Area

Input Description Output Description
RX0 Reaction on network error RY0 Reaction on network error
RX1 Reaction on network error RY1 Reaction on network error
RX2 Reserved RY2 Reserved
RX3 Reserved RY3 Reserved
RX4 Reserved RY4 Reserved
RX5 Reserved RY5 Reserved
RX6 Msg service ready RY6 Msg service start request
RX7 Msg response completed RY7 Msg request
RX8 Reserved RY8 Reserved
RX9 Reserved RY9 Reserved
RXA Error status flag RYA Reserved
RXB Remote station ready RYB Reserved
RXC Reserved RYC Reserved
RXD Reserved RYD Reserved
RXE Reserved RYE Reserved
RXF Reserved RYF Reserved

Reaction on Network Error

RY1 RY0 Description
0 0 Hold last value
0 1 Clear output to zero
1 0 Stop bus
1 1 Not used (internally switched to 10)

Service Message

Beijer-ELECTRONICS-GL-9031-Network-Adapter-Module-fig-18

Service Message Request

Address High byte Low byte Station
RWw[0] Slot number Service code:

•   Read Parameter: 2

•   Write Parameter: 3

1
RWw[1] Offset
RWw[2] User data length
RWw[3] User data 1 User data 0
RWw[4] User data 3 User data 2 2
RWw[5] User data 5 User data 4
RWw[6] User data 7 User data 6
RWw[7] User data 9 User data 8
RWw[8] User data 11 User data 10 3
RWw[9] User data 13 User data 12
RWw[10] User data 15 User data 14
RWw[11] User data 17 User data 16
RWw[12] User data 19 User data 18 4
RWw[13] User data 21 User data 20
RWw[14] User data 23 User data 22
RWw[15] User data 25 User data 24

Service Message Response

Address High byte Low byte Station
RWw[0] Slot number Service code:

•   Read Parameter: 2

•   Write Parameter: 3

1
RWw[1] Offset
RWw[2] User data length
RWw[3] User data 1 User data 0
RWw[4] User data 3 User data 2 2
RWw[5] User data 5 User data 4
RWw[6] User data 7 User data 6
RWw[7] User data 9 User data 8
RWw[8] User data 11 User data 10 3
RWw[9] User data 13 User data 12
RWw[10] User data 15 User data 14
RWw[11] User data 17 User data 16
RWw[12] User data 19 User data 18 4
RWw[13] User data 21 User data 20
RWw[14] User data 23 User data 22
RWw[15] User data 25 User data 24

The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document. All examples in this document are only intended to improve understanding of the functionality and handling of the equipment. Beijer Electronics AB cannot assume any liability if these examples are used in real applications.

In view of the wide range of applications for this software, users must acquire sufficient knowledge themselves in order to ensure that it is correctly used in their specific application. Persons responsible for the application and the equipment must themselves ensure that each application is in compliance with all relevant requirements, standards, and legislation in respect to configuration and safety. Beijer Electronics AB will accept no liability for any damage incurred during the installation or use of equipment mentioned in this document. Beijer Electronics AB prohibits all modification, changes, or conversion of the equipment.

More Info

Head Office

Beijer Electronics AB

Box 426

201 24 Malmö, Sweden

FAQ

  • Q: What should I do if the LED indicators show no network connectivity?
    • A: Check the network adapter settings and cables for any issues. Restart the system and verify the configuration.