BOSCH B228 SDI2 8-Input, 2-Output Expansion Module
Specifications
- 8 points/zones supervised expansion device
- 2 additional switched outputs
- Connects to control panels through the SDI2 bus
- Communicates back all point status changes to the control panel
- Inputs and outputs accessed through on-board screw terminal connections
Safety
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
Overview
- The B228 8-Input, 2-Output Expansion Module is an 8 points/zones supervised expansion device with 2 additional switched outputs that connects to control panels through the SDI2 bus.
- This module communicates back to the control panel all point status changes, and the outputs are switched on and off through a command from the control panel. The inputs and outputs are accessed through on-board screw terminal connections.
Fig. 1: Board overview
1 | Heartbeat LED (blue) |
2 | Tamper switch connector |
3 | SDI2 interconnect wiring connectors (to control panel or additional modules) |
4 | SDI2 terminal strip (to control panel or additional modules) |
5 | Terminal strip (outputs) |
6 | Terminal strip (point inputs) |
7 | Address switches |
Address settings
- Two address switches determine the address for the B228 module. The control panel uses the address for communications. The address also determines the output numbers.
- Use a slotted screwdriver to set the two address switches.
Notice!
- The module reads the address switch setting only during power up.
- If you change the switches after you apply power to the module, you must cycle the power to the module to enable the new setting.
- Configure the address switches based on the control panel setup.
- If multiple B228 modules are present in the same system, each B228 module must have a distinct address. The address switches of the module indicate the tens and ones value of the module’s address.
- When using single-digit address numbers from 1 to 9, set the tens switch to 0 and the ones digit to the corresponding number.
Address settings per control panel
Valid B228 addresses are dependent on the number of points allowed by a particular control panel.
Control panel | Onboard point numbers | Valid B228 addresses | Corresponding point numbers |
ICP-SOL3-P ICP-SOL3- APR
ICP-SOL3-PE |
01 – 08 | 01 | 09 – 16 |
ICP-SOL4-P ICP-SOL4-PE | 01 – 08 | 01
02 03 |
09 – 16
17 – 24 25 – 32 |
01 – 08 (3K3)
09 – 16 (6K8) |
02
03 |
17 – 24
25 – 32 |
|
01 – 08 (3K3)
09 – 16 (6K8) |
02 | 17 – 24 (3K3)
25 – 32 (6K8) |
Installation
After you set the address switches for the proper address, install the module in the enclosure, and then wire it to the control panel.
Mount the module in the enclosure
Mount the module into the enclosure’s 3-hole mounting pattern using the supplied mounting screws and mounting bracket.
Mounting the module in the enclosure
1 | Module with mounting bracket installed |
2 | Enclosure |
3 | Mounting screws (3) |
Mount and wire the tamper switch
You can connect an optional enclosure door tamper switch for one module in an enclosure. st
- Installing the optional tamper switch: Mount the ICP-EZTS Tamper Switch (P/N: F01U009269) into the enclosure’s tamper switch mounting location. For complete instructions, refer to EZTS Cover and Wall Tamper Switch Installation Guide (P/N: F01U003734)
- Plug the tamper switch wire onto the module’s tamper switch connector.
Wire to the control panel
Wire the module to a control panel using either of below methods, but do not use both.
- SDI2 interconnect wiring connectors, wire included
- SDI2 terminal strip, labeled with PWR, A, B, and COM
Interconnect wiring parallels the PWR, A, B, and COM terminals on the terminal strip.
Notice!
When connecting multiple modules, combine terminal strip and interconnect wiring connectors in series.
Using SDI2 interconnect wiring connectors
1 | Control panel |
2 | B228 module |
3 | Interconnect cable (P/N: F01U079745) (included) |
Using terminal strip
1 | Control panel |
2 | B228 module |
Output loop wiring
- There are 3 terminals for the outputs.
- The two outputs OC1 and OC2 shares one common terminal labeled +12V. These two outputs are independently switched outputs, and their output types and functions are supported by the control panel.
- When using detectors, the switched outputs provides SDI2 voltage over than 100 mA of power.
Sensor loop wiring
The resistance of the wires on each sensor loop, when connected to the detection devices, should be below 100Ω.
The B228 module detects open, short, normal, and ground fault circuit conditions on its sensor loops and transmits these conditions to the control panel. Each sensor loop is assigned a unique point/zone number and transmits individually to the control panel. Ensure that the wiring is routed away from telephone and AC wiring within the premises.
Fig. 4: Sensor loops
1 | Zone without resistor |
2 | Single zone input |
3 | Double zones with tamper |
4 | Double zones inputs |
LED descriptions
The module includes one blue heartbeat LED to indicate that the module has power and to indicate the module’s current state.
Flash pattern | Function |
Flashes once every 1 sec | Normal state: Indicates normal operation state. |
3 quick flashes
every 1 sec |
Communication error state: Indicates (the module is in a “no communication state”) resulting in an SDI2 communication error. |
ON Steady | LED trouble state:
|
OFF Steady |
Firmware version
To show the firmware version using an LED flash pattern:
- If the optional tamper switch is installed:
- With the enclosure door open, activate the tamper switch (push and release the switch).
- If the optional tamper switch is NOT installed:
- Momentarily short the tamper pins.
When the tamper switch is activated, the heartbeat LED stays OFF for 3 seconds before indicating the firmware version. The LED pulses the major, minor, and micro digits of the firmware version, with a 1 second pause after each digit.
Example:
Version 1.4.3 shows as LED flashes: [3 second pause] *___****___*** [3 second pause, then normal operation].
Technical data
Electrical
Current consumption (mA) | 30 mA |
Nominal voltage (VDC) | 12 VDC |
Output voltage (VDC) | 12 VDC |
Mechanical
Dimensions (H x W x D) (mm) | 73.5 mm x 127 mm x 15.25 mm |
Environmental
Operating temperature (°C) | 0 °C | – 50 | °C |
Operating relative humidity, non-condensing (%) | 5% – | 93% |
Connectivity
Loop inputs | Input contacts may be Normally Open (NO) or Normally Closed (NC). NOTICE! Normally Closed (NC) is not permitted in Fire installations. |
Loop End-of-Line (EOL) resistance |
|
Split EOL3k3 / 6k8 with tamper | |
Split EOL3k3 / 6k8 |
Loop wiring resistance | 100 Ω maximum |
Terminal wire size | 12 AWG to 22 AWG (2 mm to 0.65 mm) |
SDI2 wiring | Maximum distance – Wire size (Un- shielded wire only):
|
- Bosch Security Systems B.V.
- Torenallee 49
- 5617 BA Eindhoven
- Netherlands
- www.boschsecurity.com
- © Bosch Security Systems B.V., 2024
Building solutions for a better life
- 2024-06
- V01
- F.01U.424.842
- 202409300554
FAQ
- Q: What should I do if I need to change the address settings after powering up?
- A: If you change the switches after powering up, cycle the power to the module to enable the new setting.
- Q: How many B228 modules can be present in a single system?
- A: If multiple B228 modules are used, each module must have a distinct address setting.
Documents / Resources
![]() |
BOSCH B228 SDI2 8-Input, 2-Output Expansion Module [pdf] Installation Guide B228-V01, B228 SDI2 8 Input 2 Output Expansion Module, B228, SDI2 8 Input 2 Output Expansion Module, 8 Input 2 Output Expansion Module, Expansion Module, Module |