SmartGen SGQ_ATS Automatic Transfer Switch

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-PRO

SUMMARY

SGQ Automatic Transfer Switch (ATS) is used under conditions of AC660V 50/60Hz or DC250V It is two-stage PC class type with an electromagnetism drive structure, which can make fast load transfer (transfer time ≤80ms) of two power circuits. It can be widely used for national one-class load, for example: high buildings, post, telecommunications, coal mines, ships, industrial assembly lines, health care, military facilities etc. The two power circuits can be grid, auto start genset, storage battery etc.

STRUCTURE AND CHARACTERISTICS

SGQ Automatic Transfer Switch (ATS) adopts an electromagnetic coil drive, electrical and mechanical interlocking structure, main loop structure of two static contacts and one dynamic contact. Dynamic contact applies V type, which ensures two power circuits shall not be short circuit. N-type and T type apply double coils; M-type applies single coil. Coils are only energized at the time of transfer and this extends the usage life of switch to a great degree. Coil control power can be supplied by master/slave AC or DC power and it is not needed to add another control power. Switch itself has mechanical or electrical close indication, and at the same time it provides volts-free auxiliary contact.

APPEARANCE AND CLASSIFICATION

ILLUSTRATION
SGQ ATS can be classified into 3 types by appearance: N type, T type, M type. Each type has 3P and 4P, and N type still has 2P.

The rated current series are: 63A, 125A, 160A, 200A, 250A, 400A, 630A, 800A, 1000A and 1250A. Switch appearances are as below.
Table 2 Switch Appearance

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-1

N TYPE CASE DIMENSIONS AND TECHNICAL DATA 

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-2

Table 3 N Type Case Dimensions 

 ModelOverall size (mm)Installation size (mm)Copper bar and

location hole (mm)

ADCBEMUT
2P3P4P2P3P4P
SGQ63N17220022818615513916719516551227
SGQ125N19222826518615515919523216572037

Table 4 N Type Technical Data 

TypeSGQ63NSGQ125N
Rated current63A125A
Rated limited short-circuit current35kA
Coil operating voltageAC220V (176~265)V
Coil operating current3.5A
Auxiliary contact1A 250VAC, N/O, Free Voltage, Each side has 2.
Operation timeMechanical10000 times
Electrical4000 times
Number of poles2P3P4P2P3P4P
Net weight (kg)3.544.544.55. 5
Operation cycle15 seconds /time

T TYPE CASE DIMENSIONS AND TECHNICAL DATA 

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-3

Table 5 T Type Case Dimensions

 ModelOverall size(mm)Installation size (mm)Copper bar and location hole (mm)
ADCBEMNMUNUT
3P4P3P4P
SGQ160T32637529214630735620099202049
SGQ200T32637529214630735620099202049
SGQ250T32637529214630735620099202049
SGQ400T356405292146337386200119302059
SGQ630T3684273101463494082001414403063

Table 6 T Type Technical Data 

TypeSGQ160TSGQ200TSGQ250TSGQ400TSGQ630T
Rated current160A200A250A400A630A
Rated limited short-circuit current35kA
Coil operating voltageAC220V (176~265)V
Coil operating current7A
Auxiliary contact1A 250VAC, N/O, Free Voltage, Each side has 2.
 Operation timeMechanical8000 times
Electrical3000 times
Number of poles3P4P3P4P3P4P3P4P3P4P
Net weight (kg)18201820182019212022
Operation cycle10 seconds/time

M TYPE CASE DIMENSIONS AND TECHNICAL DATA

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-4

Table 7 M Type Case Dimensions

 ModelsOverall size(mm)Installation size(mm)Copper bar and location hole (mm)
A 

D

 

C

B 

E

 

M

 

U

 

T

3P4P3P4P
SGQ630M530600280345490560210123090
SGQ800M530600280345490560210124090
SGQ1000M530600280345490560210124590
SGQ1250M530600280345490560210125590

Table 8 M Type Technical Data 

TypeSGQ630MSGQ800MSGQ1000MSGQ1250M
Rated current630A800A1000A1250A
Rated limited short-circuit current50 kA
Coil operating voltageAC220V (176~265)V
Coil operating current16A
Secondary contact1A 250VAC, N/O, Free Voltage, Each side has 1.
 Operation timeMechanical6000 times
Electrical3000 times
Number of poles3P4P3P4P3P4P3P4P
Net weight (kg)3743.5394641484857
Operation cycle15s/time20s/time25s/time25s/time

WORKING REQUIREMENTS

Table 9 Working Requirements

ItemRequirements
Working temperature(-40~+70)ºC
Working Humidity(20~90)%RH
Installation elevation≤5000m
Pollution classIII
Installation type

ATS WIRING CONNECTION DIAGRAM

N AND T TYPE WIRING CONNECTION DIAGRAM

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-5

  1. Position control I
  2. Position control II
  3. Aux. contact of position I
  4. Aux. contact of position II
    • SB2 is #2 power close button
    • SB1 is #1 power close button

M TYPE WIRING CONNECTION DIAGRAM 

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-6

  1. Position control I
  2. Position control II
  3. Aux. contact of position I
  4. Aux. contact of position II

INSTALLATION AND DEBUGGING

All operations about ATS installation and debugging shall be conducted by professionals or persons knowing the switch device and protection and precaution measures must be considered during the operation. Wiring connection of main loop must make sure leading wire is not taking any pressure or force. Before installation and debugging please check firstly whether switch is damaged or whether there is harmful environment effect on it. At the same time please check whether there is loose wire resulting from transportation; clear the smudge, especially the smudge on the surface of insulating parts. The smudge probably is caused by the packing materials in the transportation process or in the storage process. Please make sure the phase sequences are in accordance at connecting the first circuit; please observe the wiring connection diagram of user manual strictly at connecting the second circuit and pay attention to control power voltage class at the same time. Ground must be well connected on switch installation. Considering personal safety and switch changeover rapidity, debugging handle can only be used for debugging and users are prohibited to operate on-load with debugging handle. First use the handle to operate switch, and if nothing unusual occurs, then operate button manually. If nothing unusual happens, then normal running can start.

ORDER MODELS

SmartGen-SGQ-ATS-Automatic-Transfer-Switch-7

SmartGen make your generator smart
SmartGen Technology Co., Ltd.
No. 28 Jinsuo Road Zhengzhou City Henan Province P. R. China
Tel: 86 371 67988888/67981888 /67992951+86 371 67981000(overseas)
Fax: 86 371 67992952
Web: www.smartgen.com.cn/
www.smartgen.cn/
Email: sales@smartgen.cn

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of t he copyright holder. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above. Any reference to trademarked product names used within this publication on is owned by their respective companies. SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

DateVersionNote
2006-03-181.0Original release.
2010-10-192.0Revision.
2011-06-082.1Modify the wiring diagram of N type, T type and M type.
2011-11-222.2Modify the technical data of N type, T type and M type.
2012-06-292.3Lines of wiring diagram are bold.
2012-11-082.4Format Modification.
2014-05-302.5Add terminal number in wiring connection diagram.
2015-03-302.6Modify some details.
2019-06-262.7Modify M type wiring diagram, and add Q type switch.
2019-09-112.8Modify wiring diagram of M type and Q type.
2020-01-072.9Delete Q type switch and related parameters.