C/N: 10310001663
Programmable Logic Controller
Smart I/O
Installation Guide
XEL-BSSRT/F/H10310001663
This installation guide provides simple function information or PLC control. Please read carefully this data sheet and manuals before using products. Especially read precautions then handle the products properly.
Safety Precautions
■ Meaning of warning and caution label
![]() |
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury |
![]() |
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices |
WARNING
- Do not contact the terminals while the power is applied.
- Be sure there are no foreign metallic matters.
- Do not manipulate the battery(charge, disassemble, hitting, short, soldering).
CAUTION
- Be sure to check the rated voltage and terminal arrangement before wiring
- When wiring, tighten the screw of terminal block with the specified torque range
- Do not install the flammable things on surroundings
- Do not use the PLC in the environment of direct vibration
- Except expert service staff, Do not disassemble or fix or modify the product
- Use the PLC in an environment that meets the general specifications contained in this installation guide.
- Be sure that external load does not exceed the rating of output module.
- When disposing of PLC and battery, treat it as industrial waste.
- I/O signal or communication line shall be wired at least 100mm away from a highvoltage cable or power line.
Operating Environment
■ To install, observe the below conditions.
No | Item | Specification | Standard | |||
1 | Ambient temp. | 0 ~ 55℃ | – | |||
2 | Storage temp. | -25 ~ 70℃ | – | |||
3 | Ambient humidity | 5 ~ 95%RH, non-condensing | – | |||
4 | Storage humidity | 5 ~ 95%RH, non-condensing | – | |||
5 | Vibration Resistance | Occasional vibration | – | – | ||
Frequency | Acceleration | Amplitude | Number | IEC 61131-2 | ||
5≤f<8.4㎐ | – | 3.5mm | 10 times in each direction for X, Y, Z | |||
8.4≤f≤150㎐ | 9.8㎨(1g) | – | ||||
Continuous vibration | ||||||
Frequency | Acceleration | Amplitude | ||||
5≤f<8.4㎐ | – | 1.75mm | ||||
8.4≤f≤150㎐ | 4.9㎨(0.5g) | – |
Applicable Support Software
■ For system configuration, the following version is necessary.
- XG5000 Software: V4.30 or above
Performance Specifications
■ For more information, please refer to user manual.
Item | Specification |
Communication protocol | RAPIEnet, EtherNet/IP, Modbus-TCP, BOOTP, DHCP |
Transmission speed | 100/1000Mbps |
Communication cable | Electric: S-FTP over CAT5e Optical: Multi-mode/Single-mode fiber optic cable(MMF/SMF) |
Maximum expansion stages | 8 slot |
Output current | 3.0A*1) |
Internal current consumption | BSSRT: 710㎃, BSSRF: 750㎃, BSSRH: 730㎃ |
*1) Be careful that the sum of the current consumption does not exceed the output current.
Parts name and Dimension (mm)
■ This is front part of the product. Refer to each name when operating the system. For more information, refer to user’s manual.
■ Parts name and function
No. | Name | Description |
① | Status LED | RAPIEnet/IP Adapter operation status LED, Network communication status LED |
② | Rotary Switch | Node Address switch |
③ | Power connector | DC24V power input connector |
➃ | Media connector | Media connector (electric, optical) |
⑤ | USB connector | USB connector to connect with XG5000 |
⑥ | USB protection cover | Protection cover for USB connector |
⑦ | Expansion cover | Protection cover for expansion connector |
■ LED details
LED | Status | Description |
RUN | Off | Power Off |
Green On | Master module is RUN | |
Red On | Master module is STOP | |
Green Blink | Waiting for service | |
RMS | Green On | Normal |
Green Blink | Devices setting is not complete | |
Red On | Non-restorable error occurs | |
Red Blink | Invalid setting, Restorable error occurs, Parameter errors, Initialization errors, Different speeds or duplexes between ports | |
RNS | Green On | At least one connection |
Green Blink | Device is not connected | |
Red On | Duplicated IP address/station number is detected | |
Red Blink | Time-out occurs with one or more devices Frame error or heartbeat error occurs | |
RELAY | Off | Relay Off |
Green On | Relay On | |
LINK/ACT1 LINK/ACT2 | Off | Link=No, Activity=NA |
Green On | 1G Link=Yes, Activity=No | |
Green Blink | 1G Link=Yes, Activity=Yes | |
Yellow On | 10/100M Link=Yes, Activity=No | |
Yellow Blink | 10/100M Link=Yes, Activity=Yes |
Installing / Removing Modules
■ Here describes the method to attach each module to the base or remove it.
- Installing module
① When extension input/output module is installe of adapter module up.
② Push the product and connect it agreement with hook for fixation of four edges and hook for connection
③ After connection, get down the hook for fixation and fix it completely - Removing module
① Push up the hook for disconnection.
② Detach the product with two hands. (Don’t force it.)
Wiring
■ Wiring for Communication
- 100/10000BASE-TX’s max.extended length between nodes is 100m.
- This module provides Auto Cross Over function so the user can use both cross and straight cable.
Pin No. | Sign | Cable wiring | ![]() |
|
Straight cable | Cross cable | |||
1 | TD+ | 1 —– 1 | 1 —– 3 | |
2 | TD- | 2 —– 2 | 2 —– 6 | |
3 | RD+ | 3 —– 3 | 3 —– 1 | |
4 | TRD2+ | 4 —– 4 | 4 —– 7 | |
5 | TRD2- | 5 —– 5 | 5 —– 8 | |
6 | RD- | 6 —– 6 | 6 —– 2 | |
7 | TRD3+ | 7 —– 7 | 7 —– 4 | |
8 | TRD3- | 8 —– 8 | 8 —– 5 |
Warranty
■ The warranty period is 36 months from the date of manufacture.
■ The initial diagnosis of faults should be conducted by the user. However, upon request, LS ELECTRIC or its representative(s) can undertake this task for a fee. If the cause of the fault is found to be the responsibility of LS ELECTRIC, this service will be free of charge.
■ Exclusions from warranty
- Replacement of consumable and life-limited parts (e.g. relays, fuses, capacitors, batteries, LCDs, etc.)
- Failures or damages caused by improper conditions or handling outside those specified in the user manual
- Failures caused by external factors unrelated to the product
- Failures caused by modifications without LS ELECTRIC’s consent
- Use of the product in unintended ways
- Failures that cannot be predicted/solved by current scientific technology at the time of manufacture
- Failures due to external factors such as fire, abnormal voltage, or natural disasters
- Other cases for which LS ELECTRIC is not responsible
■ For detailed warranty information, please refer to the user’s manual.
■ The content of the installation guide is subject to change without notice for product performance improvement.
LS ELECTRIC Co., Ltd
www.ls-electric.com
10310001663 V1.4 (2024.6)
- E-mail: automation@ls-electric.com
- Headquarter/Seoul Office
Tel: 82-2-2034-4033,4888,4703 - LS ELECTRIC Shanghai Office (China)
Tel: 86-21-5237-9977 - LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
Tel: 86-510-6851-6666 - LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam)
Tel: 84-93-631-4099 - LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
Tel: 971-4-886-5360 - LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands)
Tel: 31-20-654-1424 - LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
Tel: 81-3-6268-8241 - LS ELECTRIC America Inc. (Chicago, USA)
Tel: 1-800-891-2941 - Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnamdo, 31226, Korea