Installation Instructions
Model NIM-1W Network Interface Module
NETWORK INTERFACE APPLICATIONS

OPERATION

The Model NIM-1W from Siemens Industry, Inc., provides a new communication path for the following uses:

  • as an XNET networking interface
  • as an HNET connection to NCC WAN
  • as a connection to Foreign Systems
  • as a connection to Air Sampling detectors

When used as an XNET networking interface the NIM-1W allows for the connection of up to 63 MXL and/or XLS Systems. On an XNET network the NIM1W also supports monitor and control functionality by Siemens products, such as NCC and Desigo CC.
Output logic between MXL panels is done using CSG-M programming. CSG-M versions 6.01 and higher include options for networked MXL Systems. Each MXL System is assigned a panel number. This panel number allows interactive programming between panels using CSG-M.

SIEMENS NIM-1W Network Interface Module - fig 1

The NIM-1W supports both Style 4 and Style 7 connection. In the event of an NIM-1W communication failure, each MXL System continues to operate as a standalone panel.
The NIM-1W can also be configured as an RS-485 two wire interface to foreign systems. NIM-1W RS485 only supports Style 4 wiring. Via the add-on modem card NIM-1M, NIM-1W can also be configured for modem connection. This operation is called FSI (Foreign System Interface). The FSI responds to a protocol and gathers information about the MXL status. The interface supports both single MXL Systems and networked systems. Typical use of this interface is between the MXL and building management
systems.
Use the CSG-M to enable the functions accessed by the foreign system. If the foreign system is UL 864 listed with the MXL, the interface can also be enabled to support control of the MXL including the commands to acknowledge, silence, and reset.

SIEMENS NIM-1W Network Interface Module - fig 2

TABLE 1
NETWORK ADDRESS PROGRAMMING (SW1)

ADDR 87654321 ADDR 87654321 ADDR 87654321 ADDR 87654321
000 ILLEGAL 064 OXOOOOOO 128 XOOOOOOO 192 XXOOOOOO
001 ILLEGAL 065 OXOOOOOX 129 XOOOOOOX 193 XXOOOOOX
002 ILLEGAL 066 OXOOOOXO 130 XOOOOOXO 194 XXOOOOXO
003 OOOOOOXX 067 OXOOOOXX 131 XOOOOOXX 195 XXOOOOXX
004 OOOOOXOO 068 OXOOOXOO 132 XOOOOXOO 196 XXOOOXOO
005 OOOOOXOX 069 OXOOOXOX 133 XOOOOXOX 197 XXOOOXOX
006 OOOOOXXO 070 OXOOOXXO 134 XOOOOXXO 198 XXOOOXXO
007 OOOOOXXX 071 OXOOOXXX 135 XOOOOXXX 199 XXOOOXXX
008 OOOOXOOO 072 OXOOXOOO 136 XOOOXOOO 200 XXOOXOOO
009 OOOOXOOX 073 OXOOXOOX 137 XOOOXOOX 201 XXOOXOOX
010 OOOOXOXO 074 OXOOXOXO 138 XOOOXOXO 202 XXOOXOXO
011 OOOOXOXX 075 OXOOXOXX 139 XOOOXOXX 203 XXOOXOXX
012 OOOOXXOO 076 OXOOXXOO 140 XOOOXXOO 204 XXOOXXOO
013 OOOOXXOX 077 OXOOXXOX 141 XOOOXXOX 205 XXOOXXOX
014 OOOOXXXO 078 OXOOXXXO 142 XOOOXXXO 206 XXOOXXXO
015 OOOOXXXX 079 OXOOXXXX 143 XOOOXXXX 207 XXOOXXXX
016 OOOXOOOO 080 OXOXOOOO 144 XOOXOOOO 208 XXOXOOOO
017 OOOXOOOX 081 OXOXOOOX 145 XOOXOOOX 209 XXOXOOOX
018 OOOXOOXO 082 OXOXOOXO 146 XOOXOOXO 210 XXOXOOXO
019 OOOXOOXX 083 OXOXOOXX 147 XOOXOOXX 211 XXOXOOXX
020 OOOXOXOO 084 OXOXOXOO 148 XOOXOXOO 212 XXOXOXOO
021 OOOXOXOX 085 OXOXOXOX 149 XOOXOXOX 213 XXOXOXOX
022 OOOXOXXO 086 OXOXOXXO 150 XOOXOXXO 214 XXOXOXXO
023 OOOXOXXX 087 OXOXOXXX 151 XOOXOXXX 215 XXOXOXXX
024 OOOXXOOO 088 OXOXXOOO 152 XOOXXOOO 216 XXOXXOOO
025 OOOXXOOX 089 OXOXXOOX 153 XOOXXOOX 217 XXOXXOOX
026 OOOXXOXO 090 OXOXXOXO 154 XOOXXOXO 218 XXOXXOXO
027 OOOXXOXX 091 OXOXXOXX 155 XOOXXOXX 219 XXOXXOXX
028 OOOXXXOO 092 OXOXXXOO 156 XOOXXXOO 220 XXOXXXOO
029 OOOXXXOX 093 OXOXXXOX 157 XOOXXXOX 221 XXOXXXOX
030 OOOXXXXO 094 OXOXXXXO 158 XOOXXXXO 222 XXOXXXXO
031 OOOXXXXX 095 OXOXXXXX 159 XOOXXXXX 223 XXOXXXXX
032 OOXOOOOO 096 OXXOOOOO 160 XOXOOOOO 224 XXXOOOOO
033 OOXOOOOX 097 OXXOOOOX 161 XOXOOOOX 225 XXXOOOOX
034 OOXOOOXO 098 OXXOOOXO 162 XOXOOOXO 226 XXXOOOXO
035 OOXOOOXX 099 OXXOOOXX 163 XOXOOOXX 227 XXXOOOXX
036 OOXOOXOO 100 OXXOOXOO 164 XOXOOXOO 228 XXXOOXOO
037 OOXOOXOX 101 OXXOOXOX 165 XOXOOXOX 229 XXXOOXOX
038 OOXOOXXO 102 OXXOOXXO 166 XOXOOXXO 230 XXXOOXXO
039 OOXOOXXX 103 OXXOOXXX 167 XOXOOXXX 231 XXXOOXXX
040 OOXOXOOO 104 OXXOXOOO 168 XOXOXOOO 232 XXXOXOOO
041 OOXOXOOX 105 OXXOXOOX 169 XOXOXOOX 233 XXXOXOOX
042 OOXOXOXO 106 OXXOXOXO 170 XOXOXOXO 234 XXXOXOXO
043 OOXOXOXX 107 OXXOXOXX 171 XOXOXOXX 235 XXXOXOXX
044 OOXOXXOO 108 OXXOXXOO 172 XOXOXXOO 236 XXXOXXOO
045 OOXOXXOX 109 OXXOXXOX 173 XOXOXXOX 237 XXXOXXOX
046 OOXOXXXO 110 OXXOXXXO 174 XOXOXXXO 238 XXXOXXXO
047 OOXOXXXX 111 OXXOXXXX 175 XOXOXXXX 239 XXXOXXXX
048 OOXXOOOO 112 OXXXOOOO 176 XOXXOOOO 240 XXXXOOOO
049 OOXXOOOX 113 OXXXOOOX 177 XOXXOOOX 241 XXXXOOOX
050 OOXXOOXO 114 OXXXOOXO 178 XOXXOOXO 242 XXXXOOXO
051 OOXXOOXX 115 OXXXOOXX 179 XOXXOOXX 243 XXXXOOXX
052 OOXXOXOO 116 OXXXOXOO 180 XOXXOXOO 244 XXXXOXOO
053 OOXXOXOX 117 OXXXOXOX 181 XOXXOXOX 245 XXXXOXOX
054 OOXXOXXO 118 OXXXOXXO 182 XOXXOXXO 246 XXXXOXXO
055 OOXXOXXX 119 OXXXOXXX 183 XOXXOXXX 247 XXXXOXXX
056 OOXXXOOO 120 OXXXXOOO 184 XOXXXOOO 248 ILLEGAL
057 OOXXXOOX 121 OXXXXOOX 185 XOXXXOOX 249 ILLEGAL
058 OOXXXOXO 122 OXXXXOXO 186 XOXXXOXO 250 ILLEGAL
059 OOXXXOXX 123 OXXXXOXX 187 XOXXXOXX 251 ILLEGAL
060 OOXXXXOO 124 OXXXXXOO 188 XOXXXXOO 252 ILLEGAL
061 OOXXXXOX 125 OXXXXXOX 189 XOXXXXOX 253 ILLEGAL
062 OOXXXXXO 126 OXXXXXXO 190 XOXXXXXO 254 ILLEGAL
063 OOXXXXXX 127 OXXXXXXX 191 XOXXXXXX 255 ILLEGAL

O = OPEN (or OFF) X = CLOSED ( or ON)
TABLE 2
PANEL NUMBER PROGRAMMING (SW2)

ADDR 8 7 6 5 4 3 2 1 ADDR 8 7 6 5 4 3 2 1 ADDR 8 7 6 5 4 3 2 1 ADDR 8 7 6 5 4 3 2 1
000 ROOOOOOO 016 SOOXOOOO 032 SOXOOOOO 048 SOXXOOOO
001 SOOOOOOX 017 SOOXOOOX 033 SOXOOOOX 049 SOXXOOOX
002 SOOOOOXO 018 SOOXOOXO 034 SOXOOOXO 050 SOXXOOXO
003 SOOOOOXX 019 SOOXOOXX 035 SOXOOOXX 051 SOXXOOXX
004 SOOOOXOO 020 SOOXOXOO 036 SOXOOXOO 052 SOXXOXOO
005 SOOOOXOX 021 SOOXOXOX 037 SOXOOXOX 053 SOXXOXOX
006 SOOOOXXO 022 SOOXOXXO 038 SOXOOXXO 054 SOXXOXXO
007 SOOOOXXX 023 SOOXOXXX 039 SOXOOXXX 055 SOXXOXXX
008 SOOOXOOO 024 SOOXXOOO 040 SOXOXOOO 056 SOXXXOOO
009 SOOOXOOX 025 SOOXXOOX 041 SOXOXOOX 057 SOXXXOOX
010 SOOOXOXO 026 SOOXXOXO 042 SOXOXOXO 058 SOXXXOXO
011 SOOOXOXX 027 SOOXXOXX 043 SOXOXOXX 059 SOXXXOXX
012 SOOOXXOO 028 SOOXXXOO 044 SOXOXXOO 060 SOXXXXOO
013 SOOOXXOX 029 SOOXXXOX 045 SOXOXXOX 061 SOXXXXOX
014 SOOOXXXO 030 SOOXXXXO 046 SOXOXXXO 062 SOXXXXXO
015 SOOOXXXX 031 SOOXXXXX 047 SOXOXXXX 063 SOXXXXXX
————— ————— ————– 064 SXOOOOOO
S = Closed selects Style 7
S = Open selects Style 4
O = Open or OFF
X = Closed or ON
R = Closed selects AnaLASER
R = Open selects FSI

NOTE:
To open a dipswitch, press down on the side of the dipswitch marked OPEN.
To close a dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.
To open a slide switch, push the slide to the side opposite the side marked ON.
To close a slide switch, push the slide to the side marked ON.

The NIM-1W also provides for the connection of up to 31 Air Sampling detectors. The MXL supports individual programming and monitoring of the Air Sampling devices. Each detector can be uniquely programmed from the MKB menu or by using CSG-M. All three alarm levels (PreAlarm 1, PreAlarm 2, and Alarm) are supported.
NOTE: When the NIM-1W is configured as an Air Sampling interface, it cannot support either MXL networking or the FSI. If these functions are required, additional NIM-1Ws must be used.
For additional information on the MXL/MXLV System, refer to the MXL/MXLV Manual, P/N 315-092036.

INSTALLATION

Remove all system power before installation, first battery and then AC. (To power up, connect the AC first, then the battery.)
The NIM-1W installs into the MXL optional MOM-4/2 card cage where it occupies one full width slot. The NIM-1W can be installed in either of the full slots of the MOM-4/2. The slot determines if the wiring is connected to TB3 or TB4 of the MOM-4/2.

Setting the Switches
Set all switches, configuration jumpers, and connection cables before installing the NIM-1W into the MOM-4.
Use switch SW1 to set the MXL network address. Set this switch according to the address where the NIM-1W is installed in the MXL’s network map. Refer to the CSG-M configuration printout for the address of the module. See Table 1 for settings.
Use switch SW2 to set either the panel number for networked systems or to select FSI or Air Sampling operation. Refer to Table 2 for panel settings, Table 3 for FSI settings, and Table 4 for Air Sampling settings.

  1. When installing the NIM-1W in a networked system, set the panel number to agree with the panel number for the NIM-1W assigned to the MXL System in CSG-M.
  2. Switch position 8 selects Style 4 or Style 7 operation for the NIM-1W network.
  3. Set jumper plugs on JP4 to the “M” position.
  4. Set jumper plugs on P6 to the “X” position (Figure 1) if using NIM-1W for RS-485 interface. Set jumper plugs on P6 as shown in Figure 2 if using NIM-W for modem interface.

SIEMENS NIM-1W Network Interface Module - fig 3

NOTES:

  1. 18 AWG minimum.
  2. 80 ohms maximum per pair.
  3. Use shielded twisted pair.
  4. Terminate the shield at MXL Panel 1 only.
  5. Power limited to NFPA 70 per NEC 760.
  6. Maximum voltage 8V peak to peak.
  7. Maximum current 150mA.
  8. For Style 4 omit all Network Pair B connections.
  9. CC-5 terminals 9-14 are not connected and can be used to tie shields together.
  10. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315092772 revision 6 or higher, for additional wiring information.

5. When installing the NIM-1W for FSI operation, set the switch to all open (or OFF).

TABLE 3
FSI PROGRAMMING

ADDR 8 7 6 5 4 3 2 1
FSI OOOOOOOO
O = Open or OFF

6. When installing the NIM-1W for Air Sampling detection connection, set the switch as follows:
TABLE 3
AIR SAMPLING PROGRAMMING

ADDR FSI 8 7 6 5 4 3 2 1
Air Sampling XOOOOOOO
O = Open or OFF
X = Closd or ON

After setting the switches, install the NIM-1W into the MOM-4/2 card cage. Make sure that the module is in the card guides and the card edge is firmly seated in the connectors on the MOM-4/2.

CAUTION
At all times handle all plug-in cards with extreme care. When inserting or removing a card, be sure the position of the card is kept at right angles to the MOM-4 board. Otherwise, the plug-in card can damage or displace other components.

ELECTRICAL CONNECTIONS

NIM-1W On An XNET Network
Figure 3 shows the wiring diagram for the NIM-1W on an XNET network. Up to 32 MXL and/or XLS Systems can be connected in the XNET network with an NIM-1W installed in each MXL System. For the highest level of fault protection, install the NIM-1W in the enclosure with the MMB, although this is not necessary. When connecting more than 32 MXL Systems, an REP-1 repeater, a D2300CPS or a D2325CPS is required. Refer to the REP-1 Installation Instructions, P/N 315-092686, the D2300CPS Installation Instructions, P/N 315-050018 or the D2325CPS Installation Instructions, P/N 315-050019, as applicable, for the wiring diagram.
The XNET network can be installed as either Style 4 or Style 7. Figure 3 shows which wires must be added to support Style 7. Style 7 is required in Canada. Each NIM-1W is  shipped with two 120 ohm EOLRs— only two are required for each network pair. Install an EOLR at the ends of each network pair. Do not install an EOLR at each NIM-1W. (A simple rule of thumb for the NIM-1W: an EOLR must be installed where only a single wire lands on a screw terminal.)
Do not T-tap the network wiring. If T-tapping is required, use the REP-1 repeater. Refer to the REP-1 Installation Instructions, P/N 315-092686, the D2300CPS Installation Instructions, P/N 315-050018 or the D2325CPS Installation Instructions, P/N 315050019, as applicable, for the wiring diagram.
For Style 4 wiring, terminate the secondary network pair (terminals 3 and 4) on each NIM-1W with an EOLR.

Network Command Center (NCC/Desigo CC)
Figure 4 shows the wiring to the NCC/Desigo CC.
To connect the NCC/Desigo CC, observe the following restrictions:

  1. Give the NCC/Desigo CC a panel number. (This panel number is in addition to the panel number for the MXL System that the NCC/Desigo CC connects to.)
  2. The total number of panels in the XNET must not exceed 64, including the NCC/Desigo CC.

SIEMENS NIM-1W Network Interface Module - fig 4

Figure 4
Connecting the NIM-1W to the NCC/Desigo CC and FireFinder-XLS

NOTES:

  1. No EOLR required for NIC-C.
  2. The screw terminals can accommodate one 12-24AWG or two 1624AWG.
  3. From the NCC-2F to NIM-1R, NIM-1W or NCC-2F: 80 Ohms max. per pair.
    Unshielded twisted pair – .5μF line to line Shielded twisted pair – .3μF line to line, .4μF line to shield
  4. From the NCC-2F to NIC-C:
    2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s.
    Unshielded twisted pair .25μF max. line to line Shielded twisted pair.15μF max. line to line.2μF max. line to shield
  5. Use twisted pair or twisted shielded pair.
  6. Terminate shields at one end only.
  7. Power limited to NFPA 70 per NEC 760.
  8. CC-5 terminals 9 – 14 are not connected and can be used to tie shields together.
  9. Positive or negative ground fault detected at <10K ohms on pins 3-4, 7-8 of the NIC-C.
  10. Each pair independently supervised.
  11. Maximum voltage 8V P-P.
  12. Maximum current 75mA during message transmission.

Foreign System Interface (FSI)
The FSI installs on TB3 or TB4, terminals 1 and 2, of the MOM-4/2 depending on where the NIM-1W is installed, as shown in Figure 5. Use one of the EOLRs provided with the NIM-1W on terminals 1 and 2. This properly terminates the FSI. Use the second EOLR on terminals 3 and 4. Never use terminals 3 and 4 to connect to the FSI. Refer to Figure 5 for the polarity of the FSI driver.
If multiple FSI connections are required, up to four NIM-1Ws may be installed in an individual MXL System. In networked systems each MXL can support up to four FSI ports. For networked systems, each FSI port must be configured as either local or global in the CSG-M. Local FSI ports display information only on the MXL System to which they are connected. Global FSI ports display all events in all MXL Systems. Refer to the CSG-M Manual, P/N 315-090381, for further information.

Connection via NIM-1W RS-485 Interface
NIM-W RS485 FSI connection should be wired Style 4 only. The recommended Serial Baud Rate when using NIM-1W RS485 FSI is 19200 bpm. P6 jumper position on the NIM-1W should be set for RS-485 configuration as shown in Figure 1. Refer to Figure 5 for wiring instructions.

NOTES:

  1. 18 AWG minimum.
  2. 80 ohms maximum per pair.
  3. Use shielded twisted pair.
  4. Terminate the shield at the NIM-1W enclosure only.
  5. Power limited to NFPA 70 per NEC 760.
  6. Maximum voltage 8V peak to peak.
  7. Maximum current 150mA.
  8. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information.

Connection via NIM-1W/NIM-1M Modem
NIM-1W/NIM-1M modem FSI connection should be wired Style 4 only. P6 jumper position on the NIM-1W should be set for Modem configuration as shown in Figure 2. The recommended Serial Baud Rate when using NIM-1W/NIM-1M Modem FSI is 19200 bpm. Refer to Figure 16 for wiring instructions.

Air Sampling Interface
AnaLASER Interface
The AnaLASER Air Sampling interface connects to the MOM-4/2, TB3 or TB4, terminals 1 and 2, depending on where the NIM-1W is installed (Refer to Figure 7). Up to 31 Air Sampling detectors can be connected to a single NIM-1W.
The ACC-1 requires an RS-485 to RS-232 converter which mounts in the back of the ACC-1 enclosure. The converter model number is AIC-4Z. The AIC-4Z supports from one to four AnaLASER detectors. Refer to the AIC-4Z Installation Instructions, P/N 315093792, for the mounting and configuration of the converter and the ACC-1s.

Complete wiring of the converter as shown in Figure 7 before installing the ACC-1 in the enclosure.

  • Place the end-of-line resistors in the locations specified in Figure 7.
  • Install the cable P/N IC-12 between the converter and the ACC-1.
  • Refer to the AnaLASER Air Sampling Smoke Detection Manual, P/N 315-092893, for connection to the AnaLASER detector and power supply, as well as mechanical  mounting of the ACC-1.

SIEMENS NIM-1W Network Interface Module - fig 5

  1. FSK @ 19.2kbps
    Transmit level: 10Dbm
    Receive level: 43 Dbm
  2. Modem Ratings
    14-18 AWG 10 miles Max.
    20 AWG 6 miles Max.
    22 AWG 4 miles Max.
    0.8 uf max line to line
    14-22 AWG unshielded twisted pair
  3. Power limited to NFPA 72 per NEC 760
  4. Refer to NIM-1M instructions, P/N 315-099105 for
    configuration settings and specific wiring guidelines
  5. Install the LLM-1 in the MXL enclosure.
  6. Positive or negative ground fault detected <5K ohms on CC-5 1-16

SIEMENS NIM-1W Network Interface Module - fig 6

VESDA Interface
The VESDA Air Sampling interface connects to the MOM-4/2, TB3 or TB4, terminals 12-16, depending on where the NIM-1W is installed (Refer to Figure 8). Up to 31 Air Sampling detectors can be connected to a single NIM-1W.
The VESDA/MXL-IQ Intelligent Interface requires a model CPY-HLI which consists of an MXL-IQ/VESDA High Level Interface and a VESDAnet Socket. The CPY-HLI can support up to 31 VESDA detectors utilizing a VESDA network. Refer to the CPY-HLI Installation Instructions, P/N 315-099200, for mounting and installation of the CPY-HLI to the VESDA detectors.

Complete wiring of the Intelligent Interface as shown in Figure 8.

  •  Place the end-of-line resistors in the locations specified in Figure 8.
  • Install the 5 leads of the Model CPY-HLICABLE interface cable (P/N 500-699911) to the MOM-4/2 according to the CPY-HLI Installation Instructions, P/N 315-099200. (Refer to Figure 8.)
  • To connect the CPY-HLI to the VESDA network, refer to the CPY-HLI Installation Instructions, P/N 315-099200.

NOTE: VESDA is supported in NIM-1W firmware version 2.0 and higher, SMB ROM version 6.10 and higher and CSG-M version 11.01 and higher.

ELECTRICAL RATINGS

Active 5VDC Module Current OmA
Active 24VDC Module Current 60mA
Standby 24VDC Module Current 60mA

NOTES:

  1. 18 AWG minimum.
  2. 80 ohms maximum per pair.
  3. Use twisted pair or shielded twisted pair.
  4. Terminate the shield at the NIM-1W enclosure only.
  5. Power limited to NFPA 70 per NEC 760.
  6. Maximum voltage 8V peak to peak.
  7. Maximum current 150mA.
  8. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information.

SIEMENS NIM-1W Network Interface Module - fig 7

SIEMENS NIM-1W Network Interface Module - fig 8

MODEL CPY-HLICABLE (P/N 500-699911) Requirements:

  1. 18 AWG minimum.
  2. Maximum distance between MXL-IQ and CPY-HLI enclosures is 6 feet.
  3. Cable must be in rigid conduit and can not leave the room.
  4. Shielded cable is not recommended.
  5. Power limited to NFPA 70 per NEC Article 760.

REFER TO THE CPY-HLI INSTALLATION INSTRUCTIONS, P/N 315-099200, FOR MOUNTING AND INSTALLATION OF THE MODEL CPY-HLI TO THE
VESDA DETECTORS.
REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 315-092772 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION.

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-099165-10
Document ID A6V10239281
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada