Quick Recommendation Guide

Typical Applications

sensorswitch WSXA Occupancy Motion Sensor Switch - fig 1

Private Offices(Typical Energy Savings: 30% – 50%)
Up to 15’x15’ Without ObstructionsWSXA** / WSXA D**Sensor must have visibility to desktop activity
Up to 15’x15’ With ObstructionsWSXA PDT** /
WSXA PDT D**
Small rooms without direct line of sight (also required if occupant
has back to sensor)
Up to 20’x20′CM PDT 9*Place within visual sight of main entry door
0-10V DimmingWSXA PDT D** or
SPODMRA D**
LED dimming control with or without motion sensor
Conference Rooms(Typical Energy Savings: 30% – 50%) †
Up to 15’x15′WSXA PDT** /
WSXA PDT D**
Sensor will detect both motion and sound
Up to 20’x20′CM PDT 9*Place within visual sight of main entry door
Up to 30’x30′WV PDT 16*Place sensor in corner along entrance wall
Classrooms(Typical Energy Savings: 40% – 60%) †
Up to 30’x30′WV PDT 16*Place sensor in corner along entrance wall
Greater than 30’x30′Multiple WV PDT 16* or CM PDT 10*Place sensors in opposite corners
Open Office Areas(Typical Energy Savings: 20% -40%) †
8′-10′ Mounting HeightMultiple CM PDT 9*Place sensors on 25’ – 30’ centers and cover all entrances
Restrooms(Typical Energy Savings: 50% – 80%) †
PrivateWSXA **For rooms without obstructions
Private with FanWSXA 2P: FANNo obstructions, relay 1 controls lights, relay 2 is for fan
Up to 4 StallsWSXA PDT**For rooms with obstructions
4 to 7 StallsCM PDT 9*Place within visual sight of the main entry door
More than 7 StallsMultiple CM PDT 9*Contact your Acuity Sales Representative for assistance
Corridors(Typical Energy Savings: 20% – 60%) †
9′ Mounting HeightCM 10*Place sensors 50’ on center
12′ Mounting HeightCM 10*Place sensors 60’ on center
Gymnasiums(Typical Energy Savings: 20% – 50%) †
25′ Mounting HeightLSXR 6Place sensors on 40’ centers and cover all entrances
Warehouses(Typical Energy Savings: 20% – 50%) †
360°, 15′ – 45′ Mounting HeightLSXR 61 sensor per fixture
Aisle ControlLSXR 50Coverage spans multiple fixtures

* Requires power pack(s).† Results typical; actual savings may differ.
**Multi-way (3-way) configurations are available – look for “MWO” on the spec sheet!
***For 347 VAC applications, please add 347 to product nomenclature
sensorswitch WSXA Occupancy Motion Sensor Switch - icon 1 Visible Light Programming, learn more at https://sensorswitch.acuitybrands.com/overview/vlp

Wiring Diagrams

sensorswitch WSXA Occupancy Motion Sensor Switch - fig 2

Notes:

  1. Unit will draw power from either line connection.
  2. When switching loads on both relays (2P version), the line inputs must be on the same phase.
  3. Substitute PP20 with PP16X for 347 VAC applications

sensorswitch WSXA Occupancy Motion Sensor Switch - fig 3

LINE VOLTAGE – SINGLE RELAY (I.E., LSXR XX)

sensorswitch WSXA Occupancy Motion Sensor Switch - fig 4

Notes

  1. Black wires can be reversed
  2. Wire is red for HVOLT version (required for 347 VAC)
  3. Disconnect and cap black output wire going to driver/ballast if switching fixture is not required.

LINE VOLTAGE – DUAL RELAY (I.E., LSXR XX 2P)

sensorswitch WSXA Occupancy Motion Sensor Switch - fig 5

Notes

  1. Black wires can be reversed.
  2. Blue wires can be reversed.
  3. Wire is red 347 VAC version.
  4. Red wires can be reversed.

sensorswitch logo 2

One Lithonia Way
Conyers, Georgia 30012
800.705.SERV (7378)
www.acuitybrands.com
©2017-2020, 2023 Acuity Brands Lighting, Inc.
All rights reserved. | SSI_5989_0223