Quick Recommendation Guide
Typical Applications
Private Offices | (Typical Energy Savings: 30% – 50%) | |
Up to 15’x15’ Without Obstructions | WSXA** / WSXA D** | Sensor must have visibility to desktop activity |
Up to 15’x15’ With Obstructions | WSXA PDT** / WSXA PDT D** | Small rooms without direct line of sight (also required if occupant has back to sensor) |
Up to 20’x20′ | CM PDT 9* | Place within visual sight of main entry door |
0-10V Dimming | WSXA PDT D** or SPODMRA D** | LED dimming control with or without motion sensor |
Conference Rooms | (Typical Energy Savings: 30% – 50%) † | |
Up to 15’x15′ | WSXA PDT** / WSXA PDT D** | Sensor will detect both motion and sound |
Up to 20’x20′ | CM PDT 9* | Place within visual sight of main entry door |
Up to 30’x30′ | WV PDT 16* | Place sensor in corner along entrance wall |
Classrooms | (Typical Energy Savings: 40% – 60%) † | |
Up to 30’x30′ | WV PDT 16* | Place sensor in corner along entrance wall |
Greater than 30’x30′ | Multiple WV PDT 16* or CM PDT 10* | Place sensors in opposite corners |
Open Office Areas | (Typical Energy Savings: 20% -40%) † | |
8′-10′ Mounting Height | Multiple CM PDT 9* | Place sensors on 25’ – 30’ centers and cover all entrances |
Restrooms | (Typical Energy Savings: 50% – 80%) † | |
Private | WSXA ** | For rooms without obstructions |
Private with Fan | WSXA 2P: FAN | No obstructions, relay 1 controls lights, relay 2 is for fan |
Up to 4 Stalls | WSXA PDT** | For rooms with obstructions |
4 to 7 Stalls | CM PDT 9* | Place within visual sight of the main entry door |
More than 7 Stalls | Multiple CM PDT 9* | Contact your Acuity Sales Representative for assistance |
Corridors | (Typical Energy Savings: 20% – 60%) † | |
9′ Mounting Height | CM 10* | Place sensors 50’ on center |
12′ Mounting Height | CM 10* | Place sensors 60’ on center |
Gymnasiums | (Typical Energy Savings: 20% – 50%) † | |
25′ Mounting Height | LSXR 6 | Place sensors on 40’ centers and cover all entrances |
Warehouses | (Typical Energy Savings: 20% – 50%) † | |
360°, 15′ – 45′ Mounting Height | LSXR 6 | 1 sensor per fixture |
Aisle Control | LSXR 50 | Coverage spans multiple fixtures |
* Requires power pack(s).† Results typical; actual savings may differ.
**Multi-way (3-way) configurations are available – look for “MWO” on the spec sheet!
***For 347 VAC applications, please add 347 to product nomenclature Visible Light Programming, learn more at https://sensorswitch.acuitybrands.com/overview/vlp
Wiring Diagrams
Notes:
- Unit will draw power from either line connection.
- When switching loads on both relays (2P version), the line inputs must be on the same phase.
- Substitute PP20 with PP16X for 347 VAC applications
LINE VOLTAGE – SINGLE RELAY (I.E., LSXR XX)
Notes
- Black wires can be reversed
- Wire is red for HVOLT version (required for 347 VAC)
- Disconnect and cap black output wire going to driver/ballast if switching fixture is not required.
LINE VOLTAGE – DUAL RELAY (I.E., LSXR XX 2P)
Notes
- Black wires can be reversed.
- Blue wires can be reversed.
- Wire is red 347 VAC version.
- Red wires can be reversed.
One Lithonia Way
Conyers, Georgia 30012
800.705.SERV (7378)
www.acuitybrands.com
©2017-2020, 2023 Acuity Brands Lighting, Inc.
All rights reserved. | SSI_5989_0223
Documents / Resources
![]() | sensorswitch WSXA Occupancy Motion Sensor Switch [pdf] User Guide WSXA, WSXA D, WSXA PDT, WSXA PDT D, CM PDT 9, CM PDT 10, WV PDT 16, SPODMRA D, SPODMRD, LSXR 6, LSXR 50, WSXA Occupancy Motion Sensor Switch, Occupancy Motion Sensor Switch |