SELTRON logoACD10 Constant Temperature Controller
Instruction Manual

ACD10 Constant Temperature Controller

Warnings
Check the controller and its packaging carefully. If you see visible damage to the controller, do not use it. Installing a damaged product can be life-threatening.
When adjusting the controller, pay attention to the correct opening direction of the valve. Wrong turning direction can lead to high or low temperatures in the system and consequently damage to the system. When adjusting the controller, make sure you set the minimum and maximum value of requested temperatures correctly. Incorrectly
selected limit values for setting the requested temperature lead to a wrong setup of requested temperature and, consequently, undesirable operation and/or damage to the system and user.
If the controller is installed in an environment where flooding or contact with water is possible, it shall be mounted above a possible water level or away from sources of water, so that it is not exposed to standing or dripping water. Contact of the controller with water can damage the controller and the person who is in contact with it.
Every project with controller must have independent system protection for cases of too low or too high temperatures. The controller does not perform protection functions for cases of too high or too low temperatures in the system. High or low temperatures in the system can cause damage to the system and user.

Introduction

SELTRON ACD10 Constant Temperature Controller - 1

Controllers ACD10 are modern designed, microprocessor-driven devices made with digital and SMT technology.
The controller is provided as a constant temperature controller with actuator designed for heating and cooling applications. The most common use is to control the return temperature in the boiler and the stand-pipe temperature in the system.

Description of the controller

SELTRON ACD10 Constant Temperature Controller - 2

  1.  Button SELTRON ACD10 Constant Temperature Controller - icon. Return back.
  2. ButtonSELTRON ACD10 Constant Temperature Controller - icon1 . Move to the left, decreasing.
  3. Button SELTRON ACD10 Constant Temperature Controller - icon2. Move to the right, increasing.
  4. ButtonSELTRON ACD10 Constant Temperature Controller - icon3 . Menu entry, confirmation of selection.
  5. USB port for software updates and connection to a personal computer.
  6. Graphic display.
  7. Button SELTRON ACD10 Constant Temperature Controller - icon4. Help.
  8. Manual operation clutch.
  9. Manual movement button.
  10. Pre-wired power cord with plug.
  11. Pre-wired sensor.

Installation of the controller

In a dry interior, the controller can be mounted directly on the mixing valve with the help of the linkage kit provided. Avoid close proximity to sources of strong electromagnetic field.
Warning Each project with constant temperature controller ACD needs to base exclusively on customer design and calculations and needs to be in compliance with valid rules and regulations. Pictures, diagrams and text in this manual are intended solely as an example and the manufacturer does not accept any responsibility for them. If you use content of this manual as a base for your project, then you carry also full responsibility for it. Responsibility of publisher for unprofessional, wrong and false information and consecutive damage are explicitly excluded. We retain the right for technical errors, mistakes, changes and corrections without prior notice.
Installation of controlling devices should be done by an expert with suitable qualifications or by an authorised organisation. Before you deal with the main wiring, make sure that the main switch is switched off. You have to follow the rules for low-voltage installations IEC 60364 and VDE 0100, law prescriptions for prevention of accidents, law
prescriptions for environmental protection and other national regulations.

SELTRON ACD10 Constant Temperature Controller - 3

SELTRON ACD10 Constant Temperature Controller - 4

Hydraulic schemes

Warning Installation schemes show the principle of operation and do not include all auxiliary and protection elements.
Scheme 1 – Control of return – heating

SELTRON ACD10 Constant Temperature Controller - 5

Scheme 1 – Control of return – cooling

SELTRON ACD10 Constant Temperature Controller - 6Scheme 2 – Control of supply – heating

SELTRON ACD10 Constant Temperature Controller - 7

Scheme 2 – Control of supply – cooling

SELTRON ACD10 Constant Temperature Controller - 8

Commissioning of the controller

Controller is equipped with an innovative solution “Easy start” which enables the setup of controller in just few easy steps. When the controller is switched on for the first time and after the version of the program and the logo are displayed, the controller guides us to the initial setup with the animation on the display. Knob for manual operation must be removed to access the buttons. Initial setup is started by pressing the buttons SELTRON ACD10 Constant Temperature Controller - iconand SELTRON ACD10 Constant Temperature Controller - icon3for 5 seconds.

SELTRON ACD10 Constant Temperature Controller - 9

Selecting heating or cooling operation
With the buttons SELTRON ACD10 Constant Temperature Controller - icon1andSELTRON ACD10 Constant Temperature Controller - icon2 you can select the required operation mode – heating or cooling. Confirm the selected operating mode with theSELTRON ACD10 Constant Temperature Controller - icon3 button. If you accidentally selected the wrong operating mode, you can return to the operating mode selection with the SELTRON ACD10 Constant Temperature Controller - iconbutton.

SELTRON ACD10 Constant Temperature Controller - 10

Selecting a hydraulic scheme
Here you select the hydraulic scheme for the controller operation. Use the buttons SELTRON ACD10 Constant Temperature Controller - icon1and SELTRON ACD10 Constant Temperature Controller - icon2to navigate between schemes. Confirm the selected scheme with the SELTRON ACD10 Constant Temperature Controller - icon3button. If you accidentally selected the wrong scheme, you can return to the scheme selection with the SELTRON ACD10 Constant Temperature Controller - iconbutton.

SELTRON ACD10 Constant Temperature Controller - 11

Select the opening direction of the mixing valve
Here you can select the opening direction of the mixing valve. Use the buttonsSELTRON ACD10 Constant Temperature Controller - icon1 andSELTRON ACD10 Constant Temperature Controller - icon2 to navigate between directions. Confirm the selected direction with the SELTRON ACD10 Constant Temperature Controller - icon3button. If you accidentally selected the wrong direction, you can return to the direction selection with theSELTRON ACD10 Constant Temperature Controller - icon button.

SELTRON ACD10 Constant Temperature Controller - 12

Setting the lower limit for the requested heating temperature

SELTRON ACD10 Constant Temperature Controller - 13

With the buttonsSELTRON ACD10 Constant Temperature Controller - icon1 andSELTRON ACD10 Constant Temperature Controller - icon2 you can determine the lower limit setting of the requested temperature in heating mode. Confirm the setting with the SELTRON ACD10 Constant Temperature Controller - icon3button. If you accidentally selected the wrong lower limit, you can return to the lower limit selection with theSELTRON ACD10 Constant Temperature Controller - iconbutton.
Setting the upper limit for the requested heating temperature

SELTRON ACD10 Constant Temperature Controller - 14

With the buttons SELTRON ACD10 Constant Temperature Controller - icon1andSELTRON ACD10 Constant Temperature Controller - icon2 you can determine the upper limit setting of the requested temperature in heating mode. Confirm the setting with theSELTRON ACD10 Constant Temperature Controller - icon3 button. If you accidentally selected the wrong uper limit, you can return to the upper limit selection with theSELTRON ACD10 Constant Temperature Controller - iconbutton.
Setting the requested heating temperature

SELTRON ACD10 Constant Temperature Controller - 15

With the buttonsSELTRON ACD10 Constant Temperature Controller - icon1 andSELTRON ACD10 Constant Temperature Controller - icon2 you can determine the requested temperature in heating mode. Confirm the setting with the SELTRON ACD10 Constant Temperature Controller - icon3button. If you accidentally selected the wrong requested temperature, you can return to the requested temperature selection with the SELTRON ACD10 Constant Temperature Controller - iconbutton.
Setting the lower limit for the requested cooling temperature

SELTRON ACD10 Constant Temperature Controller - 16With the buttonsSELTRON ACD10 Constant Temperature Controller - icon1 andSELTRON ACD10 Constant Temperature Controller - icon2 you can determine the requested temperature in heating mode. Confirm the setting with the SELTRON ACD10 Constant Temperature Controller - icon3button. If you accidentally selected the wrong requested temperature, you can return to the requested temperature selection with the SELTRON ACD10 Constant Temperature Controller - iconbutton.
Setting the upper limit for the requested cooling temperature
SELTRON ACD10 Constant Temperature Controller - 17With the buttonsSELTRON ACD10 Constant Temperature Controller - icon1 andSELTRON ACD10 Constant Temperature Controller - icon2 you can determine the requested temperature in heating mode. Confirm the setting with the SELTRON ACD10 Constant Temperature Controller - icon3button. If you accidentally selected the wrong requested temperature, you can return to the requested temperature selection with the SELTRON ACD10 Constant Temperature Controller - iconbutton.
Setting the requested cooling temperature

SELTRON ACD10 Constant Temperature Controller - 18

With the buttonsSELTRON ACD10 Constant Temperature Controller - icon1 andSELTRON ACD10 Constant Temperature Controller - icon2 you can determine the requested temperature in heating mode. Confirm the setting with the SELTRON ACD10 Constant Temperature Controller - icon3button. If you accidentally selected the wrong requested temperature, you can return to the requested temperature selection with the SELTRON ACD10 Constant Temperature Controller - iconbutton.

Symbol Description
SELTRON ACD10 Constant Temperature Controller - icon5 Return-pipe – heating.
SELTRON ACD10 Constant Temperature Controller - icon6 Return-pipe – cooling.
SELTRON ACD10 Constant Temperature Controller - icon7 Stand-pipe – heating.
SELTRON ACD10 Constant Temperature Controller - icon8 Stand-pipe – cooling.

Basic screen

All the important information about the operation of the controller is displayed on the two basic screens. With the buttons SELTRON ACD10 Constant Temperature Controller - icon1and SELTRON ACD10 Constant Temperature Controller - icon2you can move between basic screens.
Temperatures

SELTRON ACD10 Constant Temperature Controller - 19

Hydraulic scheme

SELTRON ACD10 Constant Temperature Controller - 20

Symbol Description
SELTRON ACD10 Constant Temperature Controller - icon10 Heating.
Cooling.
Valve rotation direction counter clockwise.
Valve rotation direction counter clockwise.
Manual operation – the clutch is activated.
Sensor error.
Requested temperature.
Return-pipe temperature.
Stand-pipe temperature.

Help

By pressingSELTRON ACD10 Constant Temperature Controller - icon4 we can start the display animation, which shows a shortcuts for setting the requested temperature and selecting the heating or cooling operation.

SELTRON ACD10 Constant Temperature Controller - 21

Setting the requested heating temperature
To set the requested temperature, press and hold the SELTRON ACD10 Constant Temperature Controller - icon1andSELTRON ACD10 Constant Temperature Controller - icon2 keys for 1s. With the buttons SELTRON ACD10 Constant Temperature Controller - icon1andSELTRON ACD10 Constant Temperature Controller - icon2you can set the requested temperature. Confirm the setting with theSELTRON ACD10 Constant Temperature Controller - icon3 button.

SELTRON ACD10 Constant Temperature Controller - 22

Selecting heating or cooling operation
To set the heating or cooling, press and hold the SELTRON ACD10 Constant Temperature Controller - icon3button for 5 s. Use the SELTRON ACD10 Constant Temperature Controller - icon1andSELTRON ACD10 Constant Temperature Controller - icon2 keys to select the requested operating mode. Confirm the setting with theSELTRON ACD10 Constant Temperature Controller - icon3 button.

SELTRON ACD10 Constant Temperature Controller - 23

Clutch and manual valve movement
Manual movement of the mixing valve is activated by pressing the clutch button I. The requested position of the mixing valve is set by turning the rotary knob II. With renewed pressure on the clutch button I, manual movement is deactivated.

SELTRON ACD10 Constant Temperature Controller - 24

SELTRON ACD10 Constant Temperature Controller - icon11 When the clutch is activated, the control of the mixing valve switches off. The clutch symbol appears on the display.
Error
In the event of sensor malfunction, the controller informs us with a red symbol on the display.

SELTRON ACD10 Constant Temperature Controller - 25

Dimensions

SELTRON ACD10 Constant Temperature Controller - 26

Technical data

Technical information Value
Torque 5 Nm
Rotation angle 90 <°
Rotation speed 2 min / 90 <°
Type of operation 3-point, PID
Supply voltage 230 V ~ , 50 Hz
Max. power consumption 5 VA
Degree of protection IP42 according to EN 60529
Safety class I according to EN 60730-1
Dimensions (W x L x H) 86.5 x 95 x 80.3 mm
Weight 800 g
Material PC

Copyright © 2022 Seltron
This user manual is protected by copyright laws. No part of this document may be reprinted, reproduced, translated or copied to a system used for storage and retrieval of data by electronic or mechanical means, photocopying, recording or storing without the written permission of Seltron.
We reserve the right to make changes or errors.

SELTRON logoSeltron d.o.o.
Tržaška cesta 85 A
SI-2000 Maribor
Slovenia
T: +386 (0) 2 671 96 00
F: +386 (0) 2 671 96 66
sales@seltron.eu
www.seltron.euSELTRON ACD10 Constant Temperature Controller - br code

Documents / Resources

SELTRON ACD10 Constant Temperature Controller [pdf] Instruction Manual
ACD10 Constant Temperature Controller, ACD10, Constant Temperature Controller, Temperature Controller, Controller