schneider electric logoElectric LC2D A Series TeSys Deca Reversing Contactor
Instruction Manual
LC1DppApp / LC1DppA3pp / T02DN13pp
LC2DppApp / LC2DppA3pp / T02DN23pp

LC2D A Series TeSys Deca Reversing Contactor

Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 1

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all power before servicing equipment.
Failure to follow these instructions will result in death or serious injury.Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 2Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 3Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 4Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 5

WARNING
HAZARD OF FIRE OR ELECTRIC SHOCK
On contactors connected to a feeder circuit, it is mandatory to install large spacing adapters GV3G66 on top and bottom connections of the contactor to respect UL and  CSA requirements in North America.
Failure to follow these instructions can result in death, serious injury, or equipment damage.Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 6Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 7Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 8

AC/DC:

  • use of this product in EMC environment B may require mitigation measures to avoid unwanted disturbance.
  • full open AC at 10%Us.

WARNING

HAZARD OF FIRE OR ELECTRIC SHOCK (FOR CONTACTOR WITH UL HI-FAULT SHORT CIRCUIT CURRENT RATINGS ONLY)

  • The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted.
  • To reduce the hazard of fire or electric shock, current-carrying parts and the other components of the controller should be examined and replaced if damaged.
    Failure to follow these instructions can result in death, serious injury, or equipment damage.
Additional
ratings
Lighting
Tungsten
Lighting
Ballast
DefLill e Purpose ratings, 3Phase,
Load wiring: breaking all lines
Elevator Duty HP ratings
(except .D and .W DC coil)
High-Fault SCCR
Class J Fuse
High-Fault SCCR
with CB
Device 600 V 600 V FLA LRA 1Ph
120 V
1Ph
240 V
3Ph
200 V
3Ph
230 V
3Ph
480 V
3Ph
600 V
600 V 480 V 600 V
240 V 480 V 600 V
LC1D40A 60 A 60 A 40 A 240 A 200 A 160 A 5hp 10hp 10hp 100 kA 100 kA 50 kA
LC1D50A 70 A 70 A 50 A 300 A 250 A 200 A 3hp’ 7.5hp 15hp 15hp 25hp* 30hp* 100 kA 100 kA 50 kA
LC1D5OANR, 100 kA 100 kA 50 kA
LC1D65A/80A 70 A 80 A 390 A 325 A 208 A 3hr 10hp* 15hp* 20hp’ 25hp* 30hp* 100 kA 100 1(A 50 kA

Refer to information on device label when ordering replacement parts.

The product’s manufacture date is coded PPYYWWD, where:

  • PP: plant code
  • YY: year of manufacture
  • WW: week of manufacture
  • (D: weekday of manufacture (Monday = 1))

LC1D A6

Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 9

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all power before servicing equipment.
Failure to follow these instructions will result in death or serious injury.

Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 10Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 11Schneider Electric LC2D A Series TeSys Deca Reversing Contactor - assembly 12

Schneider Electric Industries SAS
35, rue Joseph Monier
CS 30323
F – 92506 Rueil Malmaison Cedex
www.se.com

Documents / Resources

Schneider Electric LC2D A Series TeSys Deca Reversing Contactor [pdf] Instruction Manual
LC2D A Series, TeSys Deca Reversing Contactor, LC2D A Series TeSys Deca Reversing Contactor, Reversing Contactor, Contactor

References

Leave a comment

Your email address will not be published. Required fields are marked *