Description

TPE2 electronic timer is used for realization of time functions in the control and automation systems. It operates according to the set time schedule planned by the user.
There is an internal battery which can protect real time clock and all the settings when the electric power supply is off.

Features

  • Electronic timer with weekly and pulse programs.
  • Replaceable battery (CR2032 lithium battery).
  • 50 on/off.
  • 50 PULSE programs.
  • Sealable cover of the front panel, easy setting by 4 keys.
  • Automatic summer/winter time changeover.
  • LCD display with backlight.
  • Holiday mode.
  • Single channel.
  • Manual control by keys combination.
  • Automatic transfer of weekdays.
  • 24-264VAC/DC input supply.
  • Double-module, mounted on TH-35 rail.

Safety instruction

Symbol WARNING

Security

Before mounting, read the instructions and disconnect the power supply. Installation should be performed by a qualified user authorized to mount electrical devices depending on the applicable regulations in a given country, in accordance with the mounting diagram. Modifications to the product may cause threat and loss of warranty. Use protection against frost when working below 0 °C.

Maintenance
All maintenance work should be carried out after disconnecting the power supply. The product temperature may rise to an elevated value. Before commencing maintenance, make sure that the product temperature is safe to make it. Guarantee unrestricted air supply, do not cover the product. Use dry and delicate materials for cleaning. Do not use chemical agents. Product not adapted to work in an environment with unfavorable conditions, i.e. high dustiness / humidity, water, explosive zones, vibrations, chemical fumes.

Recommendations
Failure to follow the instructions in the manual may result in a fire, electric shock, burns or other damage. Bemko sp. O.o. is not responsible for failure to comply with the above recommendations. We also reserve the right to make changes to the manual – the current version is available at www.bemko.eu.

Technical data

Supply terminals A1,A2
Rated voltage AC/DC 24-264V
Rated frequency 50/60Hz
Power consumption 1W
Number of programs 50 on/off
Program weekly, daily and pulse programs
Mode of work manual, automatic, holiday
Summer/winter time off, automatic changes
Time tolerance ≤1s/day at 25°C
Replaceable battery CR2032
Data readout Back-lighted LCD display
Number of contacts 1 C/O
Current of contacts Current of contacts
Switching capacity 4000VA/AC1, 384W/DC
Mechanical life 10 6
Electrical life 10° 5
Rated insulation voltage 250V
Protection degree IP20
Pollution degree 3
Altitude ≤ 2000m
Ambient temperature -20°C~55°C
Permissible relative humidity ≤50% (40°C, without condensation)
Storage temperature -30°C~70°C
Wire size 1mm²~4mm²
Tightening torque 0.5Nm
Mounting TH-35 Rail (EN60715)
Standard IEC 60730-1/IEC 60730-2-7

Display and keys

Display and keys

MO TU WE TH FR SA SU Days of the week, Monday, Tuesday,…… Sunday

Digit Icon Digit Icon Relay status: Digit Icon Activate
Digit Icon Deactivate
Display Icon Automatic mode Display Icon Summer time
Display Icon Manual mode Display Icon Pulse setting
Display Icon Winter time Display Icon Low battery
Display Icon Display Icon Back from menu
Display Icon Restore/cancel programs
Display Icon Display Icon Enter main menu
Display Icon Confirm selection
Display Icon Display Icon Select menu
Display Icon Increase a numerical value
Display Icon Display Icon Select menu
Display Icon Decrease a numerical value
Display Icon Display Icon manual operation

Display and keys

Maximum pilotable power

Maximum pilotable power Maximum pilotable power Maximum pilotable power Maximum pilotable power Maximum pilotable power
2000W 2000W 1000W 500W 500W

Wiring diagram

Wiring diagram

Dimensions

Dimensions

Initial operation

Initial operation

Select adequate year with “▲▼” keys and press “OK” key.
Select adequate month with “▲▼” keys and press “OK” key.
Select adequate day with “▲▼” keys and press “OK” key.
Select adequate hour with “▲▼” keys and press” OK” key.
Select the minute with “▲▼” keys and press” OK” key.
Select the second with ” keys and press” OK” key.

Note: If the settings were not ended and not operated by keys for 2 minutes, device will return to year setting.

Main menu

Main menu

Digit Icon Program setting menu
Digit Icon Time setting menu
Digit Icon Date setting menu
Digit Icon Summer/winter setting menu
Digit Icon Pulse setting menu
Digit Icon Time correction setting menu
Digit Icon End settings and exit from menu

Display Icon Press “OK” key to enter menus setting.
Display Icon If not operated for 2 minutes, the device will automatically exit from setting.
Display Icon Select the desired menu by pressing “▲▼ “keys.

Program setting

Time setting

Time setting

Select TIME and press “OK” key.
Select adequate hour with”▲▼” keys and press “OK” key. adjusting range is 0-23.
Select adequate minute with”▲▼” keys and press “OK” key. adjusting range is 0~59.
Select adequate second with”▲▼” keys and press “OK” key. adjusting range is 0~59.
Exit from the setting by pressing “ESC” key.

Long press▲ 0.5s, increase the numerical value quickly
Long press▼ 0.5s, decrease the numerical value quickly

Date setting

Date setting

Select DATE and press “OK” key.
Select adequate year with “▲▼” keys and press “OK” key. adjusting range is 2000~2095.
Select adequate month with”▲▼” keys and press “OK” key.
Select adequate day with”▲▼” keys and press “OK” key.
Exit from the setting by pressing “ESC” key.

Long press▲ 0.5s, increase the numerical value quickly
Long press▼ 0.5s, decrease the numerical value quickly

Program setting

Program setting

Program setting

Select PROG and press “OK” key.
Select the number of program and press “OK” key. If exit, press “ESC” for more than 0.5s. The programs are number as pairs (ON/OFF)
 Set the hour of ON time by pressing “▲▼” keys.
 Set the minute of ON time by pressing “▲▼” keys.
Set the week’s day of ON time by pressing “▲▼” keys.
Set the hour of OFF time by pressing “▲▼” keys.
 Set the minute of OFF time by pressing “▲▼” keys.
Set the week’s day of OFF time by pressing “▲▼” keys.
End the setting of one pair program and back to Program number selection.

Program cancel

Program cancel

Select PROG and press “OK” key.
Select the program to be cancelled and press “OK” key. If exit, press “ESC” for more than 0.5s.
 Press “ESC” key to cancel the program

Impulse program setting

Impulse program setting

Select PULSE and press “OK” key.
Select OFF to switch off the pulse function.
Select ON to switch on the pulse function, acknowledge with “OK” key
Set impulse duration time with”▲▼” keys and then press “OK” key. Setting range is 1-99s.
 Return to pulse setting menu.

Long press▲ 0.5s, increase the numerical value rapidly
Long press▼ 0.5s, decrease the numerical value rapidly

Summer/winter time setting

Summer/winter time setting

Select S-W and press “OK” key.
    Select the required summer/winter mode with “▲▼” keys and press “OK” key.
Set the start month of summer time and press “OK” key.
Set the start day of summer time and press “OK” key.
Set the start month of winter time and press “OK” key.
Set the start day of winter time and press “OK” key.
  Exit from the setting by pressing “MENU” key.

Display Function Summer switching Winter switching
Digit Icon Europe sum/win Last Sunday in March Last Sunday in October
Digit Icon U.S.A sum/win Second Sunday in March First Sunday in November
Digit Icon Free sum/win Freely programmed Freely programmed
Digit Icon No sum/win None None

Long press▲ 0.5s, increase the numerical value quickly
Long press▼ 0.5s, decrease the numerical value quickly

Time correction setting

Time correction setting

Select CORR and press “OK” key.
 Set correction time with “▲▼” keys and press “OK” key. Correction time range:-9.9~+9.9s; Step value: 0.1s
 Return back to main menu by pressing “ESC” key

Keys combination for MANUAL control

Display Icon AUTO/MANUAL

Time correction setting Press “▲▼” keys simultaneously, the output state of channel 1 switches to MANUAL. When the output states of other operation modes was changed, Manual mode exits automatically.

Display Icon PERM ON/PERM OFF

Time correction setting Press “▲▼” keys simultaneously for 2s, the output state of channel 1 switches to PERM ON/PERM OFF Display Icon flashes.

Digit Icon AUTO mode
Digit Icon MANUAL mode
Digit Icon PERMANENT ON mode
Digit Icon PERMANENT ON mode

Reset

Press the four keys simultaneously for 0.5 second to reset automatically. The device was restored to factory settings.

Battery replacement

Battery replacement

  1. Disconnect the main connection.
  2. Open the battery cover and insert the battery with the positive(+) side facing up as shown in the figure.
  3. Make sure the battery is seated correctly in the battery slot and close the battery cover.

Customer support

Symbol

www.schelinger.eu