Schelinger TPE2 Electronic Timer
Description
TPE2 electronic timer is used for realization of time functions in the control and automation systems. It operates according to the set time schedule planned by the user.
There is an internal battery which can protect real time clock and all the settings when the electric power supply is off.
Features
- Electronic timer with weekly and pulse programs.
- Replaceable battery (CR2032 lithium battery).
- 50 on/off.
- 50 PULSE programs.
- Sealable cover of the front panel, easy setting by 4 keys.
- Automatic summer/winter time changeover.
- LCD display with backlight.
- Holiday mode.
- Single channel.
- Manual control by keys combination.
- Automatic transfer of weekdays.
- 24-264VAC/DC input supply.
- Double-module, mounted on TH-35 rail.
Safety instruction
WARNING
Security
Before mounting, read the instructions and disconnect the power supply. Installation should be performed by a qualified user authorized to mount electrical devices depending on the applicable regulations in a given country, in accordance with the mounting diagram. Modifications to the product may cause threat and loss of warranty. Use protection against frost when working below 0 °C.
Maintenance
All maintenance work should be carried out after disconnecting the power supply. The product temperature may rise to an elevated value. Before commencing maintenance, make sure that the product temperature is safe to make it. Guarantee unrestricted air supply, do not cover the product. Use dry and delicate materials for cleaning. Do not use chemical agents. Product not adapted to work in an environment with unfavorable conditions, i.e. high dustiness / humidity, water, explosive zones, vibrations, chemical fumes.
Recommendations
Failure to follow the instructions in the manual may result in a fire, electric shock, burns or other damage. Bemko sp. O.o. is not responsible for failure to comply with the above recommendations. We also reserve the right to make changes to the manual – the current version is available at www.bemko.eu.
Technical data
Supply terminals | A1,A2 |
Rated voltage | AC/DC 24-264V |
Rated frequency | 50/60Hz |
Power consumption | 1W |
Number of programs | 50 on/off |
Program | weekly, daily and pulse programs |
Mode of work | manual, automatic, holiday |
Summer/winter time | off, automatic changes |
Time tolerance | ≤1s/day at 25°C |
Replaceable battery | CR2032 |
Data readout | Back-lighted LCD display |
Number of contacts | 1 C/O |
Current of contacts | Current of contacts |
Switching capacity | 4000VA/AC1, 384W/DC |
Mechanical life | 10 6 |
Electrical life | 10° 5 |
Rated insulation voltage | 250V |
Protection degree | IP20 |
Pollution degree | 3 |
Altitude | ≤ 2000m |
Ambient temperature | -20°C~55°C |
Permissible relative humidity | ≤50% (40°C, without condensation) |
Storage temperature | -30°C~70°C |
Wire size | 1mm²~4mm² |
Tightening torque | 0.5Nm |
Mounting | TH-35 Rail (EN60715) |
Standard | IEC 60730-1/IEC 60730-2-7 |
Display and keys
MO TU WE TH FR SA SU Days of the week, Monday, Tuesday,…… Sunday
![]() ![]() |
Relay status: | ![]() ![]() |
|
![]() |
Automatic mode | ![]() |
Summer time |
![]() |
Manual mode | ![]() |
Pulse setting |
![]() |
Winter time | ![]() |
Low battery |
![]() |
![]() ![]() |
![]() |
![]() ![]() |
![]() |
![]() ![]() |
![]() |
![]() ![]() |
![]() |
![]() |
Maximum pilotable power
![]() |
![]() |
![]() |
![]() |
![]() |
2000W | 2000W | 1000W | 500W | 500W |
Wiring diagram
Dimensions
Initial operation
❶ Select adequate year with “▲▼” keys and press “OK” key.
❷ Select adequate month with “▲▼” keys and press “OK” key.
❸ Select adequate day with “▲▼” keys and press “OK” key.
❹ Select adequate hour with “▲▼” keys and press” OK” key.
❺ Select the minute with “▲▼” keys and press” OK” key.
❻ Select the second with ” keys and press” OK” key.
Note: If the settings were not ended and not operated by keys for 2 minutes, device will return to ❶ year setting.
❶ | ![]() |
Program setting menu |
❷ | ![]() |
Time setting menu |
❸ | ![]() |
Date setting menu |
❹ | ![]() |
Summer/winter setting menu |
❺ | ![]() |
Pulse setting menu |
❻ | ![]() |
Time correction setting menu |
❼ | ![]() |
End settings and exit from menu |
Press “OK” key to enter menus setting.
If not operated for 2 minutes, the device will automatically exit from setting.
Select the desired menu by pressing “▲▼ “keys.
Program setting
Time setting
❶ Select TIME and press “OK” key.
❷ Select adequate hour with”▲▼” keys and press “OK” key. adjusting range is 0-23.
❸ Select adequate minute with”▲▼” keys and press “OK” key. adjusting range is 0~59.
❹ Select adequate second with”▲▼” keys and press “OK” key. adjusting range is 0~59.
❺ Exit from the setting by pressing “ESC” key.
Long press▲ 0.5s, increase the numerical value quickly
Long press▼ 0.5s, decrease the numerical value quickly
Date setting
❶ Select DATE and press “OK” key.
❷ Select adequate year with “▲▼” keys and press “OK” key. adjusting range is 2000~2095.
❸ Select adequate month with”▲▼” keys and press “OK” key.
❹ Select adequate day with”▲▼” keys and press “OK” key.
❺ Exit from the setting by pressing “ESC” key.
Long press▲ 0.5s, increase the numerical value quickly
Long press▼ 0.5s, decrease the numerical value quickly
Program setting
❶ Select PROG and press “OK” key.
❷ Select the number of program and press “OK” key. If exit, press “ESC” for more than 0.5s. The programs are number as pairs (ON/OFF)
❸ Set the hour of ON time by pressing “▲▼” keys.
❹ Set the minute of ON time by pressing “▲▼” keys.
❺ Set the week’s day of ON time by pressing “▲▼” keys.
❻ Set the hour of OFF time by pressing “▲▼” keys.
❼ Set the minute of OFF time by pressing “▲▼” keys.
❽ Set the week’s day of OFF time by pressing “▲▼” keys.
❾ End the setting of one pair program and back to Program number selection.
Program cancel
❶ Select PROG and press “OK” key.
❷ Select the program to be cancelled and press “OK” key. If exit, press “ESC” for more than 0.5s.
❸ Press “ESC” key to cancel the program
Impulse program setting
❶ Select PULSE and press “OK” key.
❷ Select OFF to switch off the pulse function.
❸ Select ON to switch on the pulse function, acknowledge with “OK” key
❹ Set impulse duration time with”▲▼” keys and then press “OK” key. Setting range is 1-99s.
❺ Return to pulse setting menu.
Long press▲ 0.5s, increase the numerical value rapidly
Long press▼ 0.5s, decrease the numerical value rapidly
Summer/winter time setting
❶ Select S-W and press “OK” key.
❷ ❸ ❹ ❺ Select the required summer/winter mode with “▲▼” keys and press “OK” key.
❻ Set the start month of summer time and press “OK” key.
❼ Set the start day of summer time and press “OK” key.
❽ Set the start month of winter time and press “OK” key.
❾ Set the start day of winter time and press “OK” key.
❿ ⓫ ⓬ ⓭ Exit from the setting by pressing “MENU” key.
Display | Function | Summer switching | Winter switching |
![]() |
Europe sum/win | Last Sunday in March | Last Sunday in October |
![]() |
U.S.A sum/win | Second Sunday in March | First Sunday in November |
![]() |
Free sum/win | Freely programmed | Freely programmed |
![]() |
No sum/win | None | None |
Long press▲ 0.5s, increase the numerical value quickly
Long press▼ 0.5s, decrease the numerical value quickly
Time correction setting
❶ Select CORR and press “OK” key.
❷ Set correction time with “▲▼” keys and press “OK” key. Correction time range:-9.9~+9.9s; Step value: 0.1s
❸ Return back to main menu by pressing “ESC” key
Keys combination for MANUAL control
AUTO/MANUAL
Press “▲▼” keys simultaneously, the output state of channel 1 switches to MANUAL. When the output states of other operation modes was changed, Manual mode exits automatically.
PERM ON/PERM OFF
Press “▲▼” keys simultaneously for 2s, the output state of channel 1 switches to PERM ON/PERM OFF
flashes.
![]() |
AUTO mode |
![]() |
MANUAL mode |
![]() |
PERMANENT ON mode |
![]() |
PERMANENT ON mode |
Reset
Press the four keys simultaneously for 0.5 second to reset automatically. The device was restored to factory settings.
Battery replacement
- Disconnect the main connection.
- Open the battery cover and insert the battery with the positive(+) side facing up as shown in the figure.
- Make sure the battery is seated correctly in the battery slot and close the battery cover.
Customer support
Bemko Sp. z O.O.
ul. Bocznicowa 13
05-850 Jawczyce
Documents / Resources
![]() |
Schelinger TPE2 Electronic Timer [pdf] Instructions TP16A, TP2, TPE2 Electronic Timer, TPE2, Electronic Timer, Timer |