Product Information

The product is a room temperature sensor that is designed to be installed in-wall as part of a panel switch program. It is compatible with the GIRA System 55 Standard switch program, but can also work with other switch manufacturers and programs upon request. The sensor has various measuring ranges and outputs, as well as different options for potentiometers, switches, and buttons. It is classified as Schutzklasse III (according to EN 60 730) and has an IP 20 protection rating (according to EN 60 529).

Technical Specifications

  • Measuring ranges: See table
  • Sensor/output: Assembled on board, passive
  • Range suppression: In the button
  • Testing current: See page 8
  • Potentiometer: Standard 1k, max. 0.1 W (Other values available upon request)
  • Drehschalter: Max. 24 V AC/DC, max. 130 mA, up to 5 switching stages (0, Auto, I, II, III)
  • Wippschalter: Max. 24 V AC/DC, max. 130 mA
  • Taster: LED: Max. 24 V DC (Optional max. 24 V AC)
  • Montage: Schutzklasse III (according to EN 60 730)
  • Schutzart: IP 20 (according to EN 60 529)

Product Usage Instructions

  1. Choose the appropriate measuring range for your application based on the table provided in the manual.
  2. Install the room temperature sensor in-wall according to the mounting instructions provided by the switch program manufacturer.
  3. Connect the sensor/output to the designated points on the circuit board.
  4. Adjust the potentiometer to the desired value, taking into consideration the maximum power rating.
  5. If using a Drehschalter or Wippschalter, ensure that the maximum voltage and current ratings are not exceeded.
  6. If using a Taster with LED, make sure to use the appropriate voltage (DC or AC).
  7. Ensure that the device is properly grounded and connected to a power source according to the regulations in your region.
  8. Refer to the general information and important notes sections in the manual for additional guidance and safety precautions.

Dimensional drawing

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-2
S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-3
S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-4

A room temperature sensor THERMASGARD® FSTF is used for air temperature measurement or setpoint adjustment, for presence detection or as room control and operating panel with temperature sensor, push-buttons, potentiometers, status indicators (LEDs). The in-wall sensor is mounted in high-quality panel switch programmes, ideally of the brands Gira, Berker, Merten, Jung, Siemens or Busch-Jaeger (using in-wall adapters) either individually or in combination with light switches, socket outlets, etc.It is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and clean room technology, and in interior rooms, such as living rooms, offices, hotels, etc.

TECHNICAL DATA

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-25

WIRE CONNECTION

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-5

THERMASGARD® FSTF 1

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-6

Standard version with sensor

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-7

THERMASGARD® FSTF 1  Room temperature sensors 

THERMASGARD® FSTF 1 Room temperature sensors  
Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF1 passive IP 20 (–30…+60 °C)
FS T F1 P t100 Pt100 (according to DIN EN 60 751, class B) 1101-5020-1000-162
FS T F1 P t1000 Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5000-162
FS T F1 Ni1000 Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9000-162
FS TF1 Ni TK Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0000-162
FS T F1 LM 235 Z LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1000-162
FST F1 NT C 1,8 K NTC 1.8 K 1101-5021-2000-162
FST F1 NT C 10 K NTC 10K 1101-5021-5000-162
FST F1 NT C 20 K NTC 20K 1101-5021-6000-162

THERMASGARD® FSTF xx LT

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-8

Version with sensor, LED (green), and push-button (max. 24 V DC, max. 10 mA)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-9

THERMASGARD® FSTF xx LT Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx LT passive IP 20 (–30…+60 °C)
FS T F P t100 L T Pt100 (according to DIN EN 60 751, class B) 1101-5020-1593-350
FS T F P t1000 L T Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5593-350
FS T F Ni1000 L T Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9593-350
FS T F Ni T K L T Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0593-350
FS T F LM 235 Z L T LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1593-350
FS T F N T C 1,8 K L T NTC 1.8 K 1101-5021-2593-350
FS T F N T C 10 K L T NTC 10K 1101-5021-5593-350
FS T F N T C 20 K L T NTC 20K 1101-5021-6593-350

THERMASGARD® FSTF xx L D2

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-10

Version with sensor, LED (green), and turn switch (2-step) (max. 24 V AC ⁄ DC, max. 130 mA)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-11

THERMASGARD® FSTF xx LD2 Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx LD2 passive IP 20 (–30…+60 °C)
FS T F P t100 D 2 L Pt100 (according to DIN EN 60 751, class B) 1101-5020-1631-351
FS T F  P t1000 D 2 L Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5631-351
FS T F Ni1000 D 2 L Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9631-351
FS T F Ni T K D 2 L Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0631-351
FS T F LM 235 Z D 2 L LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1631-351
FS T F N T C 1,8 K D 2 L NTC 1.8 K 1101-5021-2631-351
FS T F N T C 10 K D 2 L NTC 10K 1101-5021-5631-351
FS T F N T C 20 K D 2 L NTC 20K 1101-5021-6631-351

THERMASGARD® FSTF xx L D4

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-12

Version with sensor, LED (green) and turn switch (4-step) (max. 24 V AC ⁄ DC, max. 130 mA)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-13

THERMASGARD® FSTF xx LD4 Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx LD4 passive IP 20 (–30…+60 °C)
FS T F P t100 D 4 L Pt100 (according to DIN EN 60 751, class B) 1101-5020-1643-352
FS T F  P t1000 D 4 L Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5643-352
FS T F Ni1000 D 4 L Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9643-352
FS T F Ni T K D 4 L Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0643-352
FS T F LM 235 Z D 4 L LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1643-352
FS T F N T C 1,8 K D 4 L NTC 1.8 K 1101-5021-2643-352
FS T F N T C 10 K D 4 L NTC 10K 1101-5021-5643-352
FS T F N T C 20 K D 4 L NTC 20K 1101-5021-6643-352

THERMASGARD® FSTF xx P

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-14

Version with sensor and potentiometer (1 kOhm, max. 0.1 W)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-15

THERMASGARD® FSTF xx P Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx P passive IP 20 (–30…+60 °C)
FS T F P t100 P Pt100 (according to DIN EN 60 751, class B) 1101-5020-1001-282
FS T F P t1000 P Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5001-162
FS T F Ni1000 P Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9001-162
FS T F Ni T K P Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0001-162
FS T F LM 235 Z P LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1001-162
FS T F N T C 1,8 K P NTC 1.8 K 1101-5021-2001-162
FS T F N T C 10 K P NTC 10K 1101-5021-5001-162
FS T F N T C 20 K P NTC 20K 1101-5021-6001-162

THERMASGARD® FSTF xx PLW

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-16

Version with sensor, potentiometer (1 kOhm, max. 0.1 W), LED (green), and rocker switch (max. 24 V AC ⁄ DC, max. 130 mA)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-17

THERMASGARD® FSTF xx PLW Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx PLW passive IP 20 (–30…+60 °C)
FS T F P t100 P L W Pt100 (according to DIN EN 60 751, class B) 1101-5020-1655-353
FS T F P t1000 P L W Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5655-353
FS T F Ni1000 P L W Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9655-353
FS T F Ni T K P L W Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0655-353
FS T F LM 235 Z P L W LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1655-353
FS T F N T C 1,8 K P L W NTC 1.8 K 1101-5021-2655-353
FS T F N T C 10 K P L W NTC 10K 1101-5021-5655-353
FS T F N T C 20 K P L W NTC 20K 1101-5021-6655-353

THERMASGARD® FSTF xx PLT

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-18

Version with sensor, potentiometer (1 kOhm, max. 0.1 W), LED (green), and push-button (max. 24 V DC, max. 10 mA)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-19

THERMASGARD® FSTF xx PLT Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx PLT passive IP 20 (–30…+60 °C)
FS T F P t100 P L T Pt100 (according to DIN EN 60 751, class B) 1101-5020-1663-162
FS T F P t1000 P L T Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5663-162
FS T F Ni1000 P L T Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9663-350
FS T F Ni T K P L T Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0663-350
FS T F LM 235 Z P L T LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1663-350
FS T F N T C 1,8 K P L T NTC 1.8 K 1101-5021-2663-350
FS T F N T C 10 K P L T NTC 10K 1101-5021-5663-350
FS T F N T C 20 K P L T NTC 20K 1101-5021-6663-350

THERMASGARD® FSTF xx PD4

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-20

Version with sensor, potentiometer (1 kOhm, max. 0.1 W) and turn switch (max. 24 V AC ⁄ DC, max. 130 mA)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-21

THERMASGARD® FSTF xx PD4 Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx PD4 passive IP 20 (–30…+60 °C)
FS T F P t100 P D 4 Pt100 (according to DIN EN 60 751, class B) 1101-5020-1007-354
FS T F P t1000 P D 4 Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5007-354
FS T F Ni1000 P D 4 Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9007-354
FS T F Ni T K P D 4 Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0007-354
FS T F LM 235 Z P D 4 LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1007-354
FS T F N T C 1,8 K P D 4 NTC 1.8 K 1101-5021-2007-354
FS T F N T C 10 K P D 4 NTC 10K 1101-5021-5007-354
FS T F N T C 20 K P D 4 NTC 20K 1101-5021-6007-354

THERMASGARD®  FSTF xx P 2L 2T

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-22

Version with sensor, potentiometer (1 kOhm, max. 0.1 W), 2 LEDs (green, red), and 2 push-buttons (max. 24 V DC, max. 10 mA)

Connecting diagram

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-23

THERMASGARD® FSTF xx P 2L 2T Room temperature sensors

Type ⁄ WG01 Sensor ⁄ Output Item No.
FSTF xx P 2L 2T passive IP 20 (–30…+60 °C)
FS T F P t100 P 2 L 2 T Pt100 (according to DIN EN 60 751, class B) 1101-5020-1672-256
FS T F P t1000 P 2 L 2 T Pt1000 (according to DIN EN 60 751, class B) 1101-5020-5672-256
FS T F Ni1000 P 2 L 2 T Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K) 1101-5020-9672-256
FS T F Ni T K P 2 L 2 T Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG – Ni1000 1101-5021-0672-256
FS T F LM 235 Z P 2 L 2 T LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10 1101-5022-1672-256
FS T F N T C 1,8 K P 2 L 2 T NTC 1.8 K 1101-5021-2672-256
FS T F N T C 10 K P 2 L 2 T NTC 10K 1101-5021-5672-256
FS T F N T C 20 K P 2 L 2 T NTC 20K 1101-5021-6672-256

General notes

Measuring principle of HVAC temperature sensors in general:
The measuring principle of temperature sensors is based on an internal sensor that outputs a temperature-dependent resistance signal. The type of the internal sensor determines the output signal. The following active ⁄ passive temperature sensors are distinguished:

  • Pt 100 measuring resistor (according to DIN EN 60 751)
  •  Pt 1000 measuring resistor (according to DIN EN 60751)
  •  Ni 1000 measuring resistor (according to DIN EN 43 760, TCR = 6180 ppm ⁄ K)
  •  Ni 1000_TK 5000 measuring resistor (TCR = 5000 ppm ⁄ K)
  •  LM235Z, semiconductor IC (10 mV ⁄ K, 2.73 V ⁄ °C). Ensure correct polarity + ⁄– when connecting!
  • NTC (according to DIN 44070)
  • PTC
  •  KTY silicon temperature sensors
    The most important resistance characteristics are shown on the last page of these operating instructions. According to their characteristics, i ndividual temperature sensors exhibit different slopes in the range between 0 °C and +100 °C (TK value). Maximum-possible measuring ranges also vary from sensor to sensor (for some examples to this see under technical data).

Resistance characteristics of passive temperature sensors

In order to avoid damages ⁄ errors, preferably shielded cables are to be used.
Laying measuring cables parallel with current-carrying cables must in any case be avoided. EMC directives shall be observed! These instruments must be installed by authorised specialists only!

Limiting deviation according to classes:
Tolerances at 0 °C:

Platinum sensors (Pt100, Pt1000):

  • DIN EN 60751, class B: ± 0.3 K
  • 1 ⁄ 3 DIN EN 60751, class B: ± 0.1 K

Nickel sensors:

  • NI1000 DIN EN 43760, class B: ± 0.4 K
  • NI1000 1 ⁄ 2 DIN EN 43760, class B: ± 0.2 K
  • NI1000 TK5000: ± 0.4 K
    ATTENTION, NOTE !
    Testing current influences the thermometer‘s measuring accuracy due to intrinsic heating and therefore, should never be greater than as specified below:

Standard values for testing current:

  • Sensor current, maximum: I max.
  • Pt1000 (thin-layer): < 0,6 mA
  • Pt100 (thin-layer): < 1,0 mA
  • Ni1000 (DIN), Ni1000 TK5000 : < 0,3 mA
  • NTC xx : < 2 mW
  • LM235Z: 400 μ A … 5 mA
  • KTY 81 – 210 : < 2 mA

General notes

  • Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and
  • Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
  • In addition, the following points are to be observed:
    • These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
    • In order to prevent measuring errors, ensure during installation on an in-wall flush box that the end of the installation pipe is sealed against draught.
    • Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.
    • This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
    • No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
    • Consequential damages caused by a fault in this device are excluded from warranty or liability.
    • These devices must be installed and commissioned by authorised specialists.
    • The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
    •  In case of any modifications made by the user, all warranty claims are forfeited.
    • This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
    • Operating this device close to other devices that do not comply with EMC directives may influence functionality.
    • This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
    • Dimensions of enclosures or housing accessories may show slight tolerances on the specifications provided in these instructions.
    • Modifications of these records are not permitted.
    • In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals.

Commissioning is mandatory and may only be performed by qualified personnel!
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded

Caution
You must ensure that the potentiometer is connected up correctly. Polarity reversal can cause a short circuit.
Depending on the switching program, there are two quick release axles enclosed with the potentiometer to compensate different installation heights of the covers. This ensures that the min. and max. stop of the set point adjustment function properly.

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-24

An overview of various versions

Resistance characteristics of passive temperature sensors

S-S-REGELTECHNIK-FSTF-Room-Temperature-Sensors-In-Wall-Panel-Switch-FIG-26

Resistance characteristics of passive temperature sensors

 

 

° C

PT 100

 

Ω

PT 1000

 

Ω

Ni 1000

 

Ω

Ni 1000

TK 5000

Ω

FeT (T1)

Ω

KTY 81-210

Ω

LM235Z (KP10)

mV

 

 

° C

– 50 80.3 803 743 790.8 1030 – 50
– 40 84.3 843 791 826.8 1135 2330 – 40
– 30 88.2 882 842 871.7 1935 1247 2430 – 30
– 20 92.2 922 893 913.4 2031 1367 2530 – 20
– 10 96.1 961 946 956.2 2128 1495 2630 – 10
0 100.0 1000 1000 1000.0 2227 1630 2730 0
+ 10 103.9 1039 1056 1044.8 2328 1772 2830 + 10
+ 20 107.8 1078 1112 1090.7 2429 1922 2930 + 20
+ 30 111.7 1117 1171 1137.6 2534 2080 3030 + 30
+ 40 115.5 1155 1230 1185.7 2639 2245 3130 + 40
+ 50 119.4 1194 1291 1235.0 2746 2417 3230 + 50
+ 60 123.2 1232 1353 1285.4 2856 2597 3330 + 60
+ 70 127.1 1271 1417 1337.1 2967 2785 3430 + 70
+ 80 130.9 1309 1483 1390.1 3079 2980 3530 + 80
+ 90 134.7 1347 1549 1444.4 3195 3182 3630 + 90
+ 100 138.5 1385 1618 1500.0 3312 3392 3730 + 100
+ 110 142.3 1423 1688 1557.0 3431 3607 3830 + 110
+ 120 146.1 1461 1760 1625.4 3552 3817 3930 + 120
+ 130 149.8 1498 1833 3676 4008 + 130
+ 140 153.6 1536 1909 3802 4166 + 140
+ 150 157.3 1573 1987 3929 4280 + 150
  NTC NTC NTC NTC NTC NTC NTC NTC  
1.8 kOhm 2.2 kOhm 3 kOhm 5 kOhm 10 kOhm 10 kPRE 20 kOhm 50 kOhm
° C Ω Ω Ω Ω Ω Ω Ω Ω ° C
– 50 – 50
– 40 39073 806800 2017000 – 40
– 30 22301 27886 53093 88488 175785 135200 413400 1033500 – 30
– 20 13196 16502 29125 48541 96597 78910 220600 551500 – 20
– 10 8069 10070 16599 27664 55142 47540 122260 305650 – 10
0 5085 6452 9795 16325 32590 29490 70140 175350 0
+ 10 3294 4138 5971 9951 19880 18790 41540 103850 + 10
+ 20 2189 2719 3747 6246 12491 12270 25340 63350 + 20
+ 30 1489 1812 2417 4028 8058 8196 15886 39715 + 30
+ 40 1034 1248 1597 2662 5329 5594 10212 25530 + 40
+ 50 733 876 1081 1801 3605 3893 6718 16795 + 50
+ 60 529 626 746 1244 2489 2760 4518 11295 + 60
+ 70 389 454 526 876 1753 1900 3098 7745 + 70
+ 80 290 335 346 627 1256 1457 2166 5415 + 80
+ 90 220 251 275 458 915 1084 1541 3852 + 90
+ 100 169 190 204 339 678 817 1114 2785 + 100
+ 110 131 146 138 255 509 624 818 2045 + 110
+ 120 103 105 195 389 482 609 1523 + 120
+ 130 81 151 300 377 460 1149 + 130
+ 140 64 118 234 298 351 878 + 140
+ 150 50 93 185 238 272 679 + 150

 

Documents / Resources

S S REGELTECHNIK FSTF Room Temperature Sensors In Wall Panel Switch [pdf] Instruction Manual
WG01 FSTF1, WG01 FSTFxxLD2, WG01 FSTFxxLD4, WG01 FSTFxxP, WG01 FSTFxxPLW, FSTF Pt100, FSTF Pt1000, FSTF Ni1000, FSTF NiTK, FSTF LM235Z, FSTF NTC1.8K, FSTF NTC10K, FSTF NTC20K, FSTF, FSTF Room Temperature Sensors In Wall Panel Switch, Room Temperature Sensors In Wall Panel Switch, Temperature Sensors In Wall Panel Switch, Sensors In Wall Panel Switch, In Wall Panel Switch, Panel Switch, Switch