Instruction Manual for S S REGELTECHNIK models including: WG01 FSTF1, WG01 FSTFxxLD2, WG01 FSTFxxLD4, WG01 FSTFxxP, WG01 FSTFxxPLW, FSTF Pt100, FSTF Pt1000, FSTF Ni1000, FSTF NiTK, FSTF LM235Z, FSTF NTC1.8K, FSTF NTC10K, FSTF NTC20K, FSTF, FSTF Room Temperature Sensors In Wall Panel Switch, Room Temperature Sensors In Wall Panel Switch, Temperature Sensors In Wall Panel Switch, Sensors In Wall Panel Switch, In Wall Panel Switch, Panel Switch, Switch

 Rumføler med passiv udgang - datablad engelsk, tysk, fransk og russisk

Ni1000 Rumføler plan forsænket. ELSAG.DK


File Info : application/pdf, 32 Pages, 1.14MB

PDF preview unavailable. Download the PDF instead.

29300
D G F r 6000-2930-0000-1XX 29300-2022 V105 02 / 2022
THERMASGARD®FSTF

D Bedienungs- und Montageanleitung

FSTF

Raumtemperaturfühler, Unterputz im Flächenschalterprogramm

G Operating Instructions, Mounting & Installation
Room temperature sensors in-wall, panel switch programme

F Notice d'instruction
Sonde de température d'ambiance, encastrés dans des boîtiers d'interrupteurs

r     
           

S+S REGELTECHNIK GMBH THURN-UND-TAXIS - STR. 22 90411 NÜRNBERG / GERMANY FON +49 (0) 911 / 519 47- 0
mail@SplusS.de www.SplusS.de

CARTONS ET EMBALLAGE PAPIER À TRIER

D G F r
THERMASGARD®FSTF

Maßzeichnung

Dimensional drawing

Plan coté

 

80

55

12

FSTF 1

60

80

55

Maßzeichnung

Dimensional drawing

Plan coté

 

80

55

60

43

3

15.5

FSTF - xx

60

50

80

55

Einbauschema Installation scheme Schéma de montage  

60 FSTF - xx

60

2

D THERMASGARD® FSTF

Rev. 2022 - V15

Der Raumfühler THERMASGARD® FSTF dient der Lufttemperaturmessung oder der Sollwertverstellung, der Präsenzmeldung oder als Raumbediengerät, als Bedientableau mit Temperaturfühler, Tastern, Potentiometer, Zustandsanzeigen (LED). Der Unterputzfühler wird in hochwertigen Flächenschalterprogramme, vorzugsweise der Fabrikate Gira, Berker, Merten, Jung, Siemens oder Busch-Jaeger (mittels Unterputzadapter) einzeln oder in Kombination zu Lichtschaltern, Steckdosen etc. montiert. Er findet Anwendung in nicht aggressiver, staubfreier Umgebung, in der Kälte-, Klima- und Reinraumtechnik, in Innenräumen, wie Wohnräumen, Büros, Hotels etc.

TECHNISCHE DATEN

Messbereiche:

­30...+60 °C

Sensor / Ausgang:

siehe Tabelle, auf Platine, passiv

Bereichseinengung: im Knopf

Messstrom:

siehe Seite 8

Potentiometer:

Standard 1k, max. 0,1 W (optional andere Werte auf Anfrage, z. B. 100 , 2,5 k, 5 k, 10 k, optional Poti 0...10 V linear)

Drehschalter:

max. 24 V AC / DC, max. 130 mA, bis zu 5 Schaltstufen (0, Auto, I, II, III)

Wippschalter:

max. 24 V AC / DC, max. 130 mA

Taster:

Schließer, max. 24 V DC, max. 10 mA

LED:

max. 24 V DC (optional max. 24 V AC),

Standard grün (optional rot, gelb oder zweifarbig)

Montage:

in UP-Dose Ø 55 mm

elektrischer Anschluss: FSTF -1 mittels Schraubklemmen 0,14 - 1,5 mm², FSTF xx mittels Steckklemmen 1,0 - 2,5 mm², nur an Sicherheitskleinspannung, max. 42 V AC, 60 V DC

zulässige Luftfeuchte: max. 90 % r.H., nicht kondensierende Luft

Schutzklasse:

III (nach EN 60 730)

Schutzart:

IP 20 (nach EN 60 529)

SCHALTERPROGRAMM

Hersteller:

GIRA System 55 Standard (andere Schalterhersteller, Schalterprogramme sowie Preise auf Anfrage)

Gehäuse:

Kunststoff, Farbe Reinweiß glänzend (ähnlich RAL 9010) (auf Anfrage sind andere Farben möglich, wobei die Farbvarianten vom Schalterprogramm abhängig sind)

1x Zweileiterschaltung Standard
1x Zweileiterschaltung LM 235 Z (KP 10)

Schaltbild

55

FSTF -xx

THERMASGARD® FSTF 1
Standard-Ausführung mit Fühler

4 6
4 6
3 7
3 7
2211

THERMASGARD® FSTF 1
Typ / WG01 FSTF1 FSTF1 Pt100 FSTF1 Pt1000 FSTF1 Ni1000 FSTF1 NiTK FSTF1 LM235Z FST F1 NTC1,8K FSTF1 NTC10K FSTF1 NTC20K

Raumtemperaturfühler
Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

3

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1000-162 1101-5020-5000-162 1101-5020-9000-162 1101-5021-0000-162 1101-5022-1000-162 1101-5021-2000-162 1101-5021-5000-162 1101-5021-6000-162

D THERMASGARD® FSTF (diverse Ausführungen)

Anschlussbild

Rev. 2022 - V15 FSTF x x LT

THERMASGARD® FSTF xx LT
Ausführung mit Fühler, Leuchtdiode (grün) und Taster (max. 24 V DC, max. 10 mA)

THERMASGARD® FSTF xx LT Raumtemperaturfühler

Typ / WG01 FSTF xx LT FSTF Pt100 L T FSTF Pt1000 L T FSTF Ni1000 L T FSTF NiTK L T FSTF LM235Z L T FST F NTC1,8K L T FSTF NTC10K L T FSTF NTC20K L T

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1593-350 1101-5020-5593-350 1101-5020-9593-350 1101-5021-0593-350 1101-5022-1593-350 1101-5021-2593-350 1101-5021-5593-350 1101-5021-6593-350

Anschlussbild

FSTF xx L D2

THERMASGARD® FSTF xx L D2
Ausführung mit Fühler, Leuchtdiode (grün) und Drehschalter (2-stufig) (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx LD2 Raumtemperaturfühler

Typ / WG01 FSTF xx LD2 FSTF Pt100 D2 L FSTF Pt1000 D2 L FSTF Ni1000 D2 L FSTF NiTK D2 L FSTF LM235Z D2 L FST F NTC1,8K D2 L FSTF NTC10K D2 L FSTF NTC20K D2 L

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

4

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1631-351 1101-5020-5631-351 1101-5020-9631-351 1101-5021-0631-351 1101-5022-1631-351 1101-5021-2631-351 1101-5021-5631-351 1101-5021-6631-351

D THERMASGARD® FSTF (diverse Ausführungen)

Anschlussbild

Rev. 2022 - V15 FSTF xx L D4

THERMASGARD® FSTF xx L D4
Ausführung mit Fühler, Leuchtdiode (grün) und Drehschalter (4-stufig) (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx LD4 Raumtemperaturfühler

Typ / WG01 FSTF xx LD4 FSTF Pt100 D4 L FSTF Pt1000 D4 L FSTF Ni1000 D4 L FSTF NiTK D4 L FSTF LM235Z D4 L FST F NTC1,8K D4 L FSTF NTC10K D4 L FSTF NTC20K D4 L

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1643-352 1101-5020-5643-352 1101-5020-9643-352 1101-5021-0643-352 1101-5022-1643-352 1101-5021-2643-352 1101-5021-5643-352 1101-5021-6643-352

Anschlussbild

FSTF xx P

THERMASGARD® FSTF xx P
Ausführung mit Fühler und Potentiometer (1 kOhm, max. 0,1 W)

THERMASGARD® FSTF xx P Raumtemperaturfühler

Typ / WG01 FSTF xx P FSTF Pt100 P FSTF Pt1000 P FSTF Ni1000 P FSTF NiTK P FSTF LM235Z P FST F NTC1,8K P FSTF NTC10K P FSTF NTC20K P

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

5

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1001-282 1101-5020-5001-162 1101-5020-9001-162 1101-5021-0001-162 1101-5022-1001-162 1101-5021-2001-162 1101-5021-5001-162 1101-5021-6001-162

D THERMASGARD® FSTF (diverse Ausführungen)

Anschlussbild

Rev. 2022 - V15 FSTF xx PLW

THERMASGARD® FSTF xx PLW
Ausführung mit Fühler, Potentiometer (1 kOhm, max. 0,1 W), Leuchtdiode (grün) und Wippschalter (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx PLW Raumtemperaturfühler

Typ / WG01 FSTF xx PLW FSTF Pt100 P L W FSTF Pt1000 P L W FSTF Ni1000 P L W FSTF NiTK P L W FSTF LM235Z P L W FST F NTC1,8K P L W FSTF NTC10K P L W FSTF NTC20K P L W

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1655-353 1101-5020-5655-353 1101-5020-9655-353 1101-5021-0655-353 1101-5022-1655-353 1101-5021-2655-353 1101-5021-5655-353 1101-5021-6655-353

Anschlussbild

FSTF x x PLT

THERMASGARD® FSTF xx PLT
Ausführung mit Fühler, Potentiometer (1 kOhm, max. 0,1 W), Leuchtdiode (grün) und Taster (max. 24 V DC, max. 10 mA)

THERMASGARD® FSTF xx PLT Raumtemperaturfühler

Typ / WG01 FSTF xx PLT FSTF Pt100 P L T FSTF Pt1000 P L T FSTF Ni1000 P L T FSTF NiTK P L T FSTF LM235Z P L T FST F NTC1,8K P L T FSTF NTC10K P L T FSTF NTC20K P L T

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

6

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1663-162 1101-5020-5663-162 1101-5020-9663-350 1101-5021-0663-350 1101-5022-1663-350 1101-5021-2663-350 1101-5021-5663-350 1101-5021-6663-350

D THERMASGARD® FSTF (diverse Ausführungen)

Anschlussbild

Rev. 2022 - V15 FSTF xx PD4

THERMASGARD® FSTF xx PD4
Ausführung mit Fühler, Potentiometer (1 kOhm, max. 0,1 W) und Drehschalter (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx PD4 Raumtemperaturfühler

Typ / WG01 FSTF xx PD4 FSTF Pt100 P D4 FSTF Pt1000 P D4 FSTF Ni1000 P D4 FSTF NiTK P D4 FSTF LM235Z P D4 FST F NTC1,8K P D4 FSTF NTC10K P D4 FSTF NTC20K P D4

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1007-354 1101-5020-5007-354 1101-5020-9007-354 1101-5021-0007-354 1101-5022-1007-354 1101-5021-2007-354 1101-5021-5007-354 1101-5021-6007-354

Anschlussbild

FSTF xx P 2L 2T

THERMASGARD® FSTF xx P 2L 2T
Ausführung mit Fühler, Potentiometer (1 kOhm, max. 0,1 W), 2 Leuchtdioden (grün, rot) und 2 Tastern (max. 24 V DC, max. 10 mA)

THERMASGARD® FSTF xx P 2L 2T Raumtemperaturfühler

Typ / WG01 FSTF xx P 2L 2T FSTF Pt100 P 2L 2T FSTF Pt1000 P 2L 2T FSTF Ni1000 P 2L 2T FSTF NiTK P2L2T FSTF LM235Z P 2L 2T FST F NTC1,8K P 2L 2T FSTF NTC10K P 2L 2T FSTF NTC20K P 2L 2T

Sensor / Ausgang passiv Pt100 (nach DIN EN 60 751, Klasse B) Pt1000 (nach DIN EN 60 751, Klasse B) Ni1000 (nach DIN EN 43 760, Klasse B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V bei O °C), KP10 NTC 1,8 K NTC 10K NTC 20K

7

Art.-Nr. IP 20 (­30...+60 °C) 1101-5020-1672-256 1101-5020-5672-256 1101-5020-9672-256 1101-5021-0672-256 1101-5022-1672-256 1101-5021-2672-256 1101-5021-5672-256 1101-5021-6672-256

D Allgemeine Informationen
Messprinzip für HLK - (HVAC) -Temperaturfühler allgemein: Das Messprinzip der Temperaturfühler beruht darauf, dass der innen liegende Sensor ein temperaturabhängiges Widerstandssignal abgibt. Die Art des innen liegenden Sensors bestimmt das Ausgangssignal. Man unterscheidet die nachfolgenden passiven / aktiven Temperatursensoren:
a) Pt 100 - Messwiderstand (nach DIN EN 60 751) b) Pt 1000 - Messwiderstand (nach DIN EN 60751) c) Ni 1000 - Messwiderstand (nach DIN EN 43 760, TCR=6180 ppm / K) d) Ni 1000_TK5000 - Messwiderstand (TCR=5000 ppm / K) e) LM235Z, Halbleiter IC (10mV / K, 2,73V / °C), beim Anschluss ist auf die Polung + / ­ zu achten! f) NTC (nach DIN 44070) g) PTC h) KTY- Siliziumtemperatursensoren
Die wichtigsten Kennlinien der Temperatursensoren sind auf der letzten Seite dieser Bedienungsanleitung dargestellt. Die einzelnen Temperatursensoren weisen entsprechend ihrer Kennlinie einen unterschiedlichen Anstieg im Bereich 0 bis +100 °C (TK-Wert) auf. Ebenso sind die maximal möglichen Messbereiche von Sensor zu Sensor verschieden (siehe hierzu einige Beispiele unter technischen Daten).

D Widerstandskennlinien (siehe letzte Seite)
Um Schäden / Fehler zu verhindern, sind vorzugsweise abgeschirmte Leitungen zu verwenden. Eine Parallelverlegung mit stromführenden Leitungen ist unbedingt zu vermeiden. Die EMV-Richtlinien sind zu beachten! Die Installation der Geräte darf nur durch einen Fachmann erfolgen!

Grenzabweichungen nach Klassen: Toleranzen bei 0 °C:
Platinsensoren (Pt100, Pt1000): DIN EN 60751, Klasse B .............................................................± 0,3 K 1 / 3 DIN EN 60751, Klasse B .....................................................± 0,1 K
Nickelsensoren: NI1000 DIN EN 43760, Klasse B ..............................................± 0,4 K NI1000 1 / 2 DIN EN 43760, Klasse B......................................± 0,2 K NI1000 TK5000...........................................................................± 0,4 K

ACHTUNG, HINWEIS !
Infolge der Eigenerwärmung beeinflusst der Messstrom die Messgenauigkeit des Thermometers und sollte daher keinesfalls größer sein, als wie folgt angegeben:
Richtwerte für den Messstrom:
Sensorstrom maximal ........................................................................ Imax. Pt1000 (Dünnschicht) ............................................................ < 0,6 mA Pt100 (Dünnschicht) ............................................................ < 1,0 mA Ni1000 (DIN), Ni1000 TK5000 ............................................. < 0,3 mA NTC xx ............................................................................................ < 2 mW LM235Z............................................................................. 400 µA ... 5 mA KTY 81 - 210 .................................................................................... < 2 mA

8

D Wichtige Hinweise
Als AGB gelten ausschließlich unsere sowie die gültigen ,,Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektroindustrie" (ZVEI Bedingungen) zuzüglich der Ergänzungsklausel ,,Erweiterter Eigentumsvorbehalt". Außerdem sind folgende Punkte zu beachten: ­ Vor der Installation und Inbetriebnahme ist diese Anleitung zu lesen und die alle darin gemachten Hinweise sind zu beachten! ­ Um Messabweichungen zu verhindern, muss bei der Montage auf einer Standard-Unterputzdose das Ende des Installationsrohres gegen etwaigen Luftzug
abgedichtet werden. ­ Der Anschluss der Geräte darf nur an Sicherheitskleinspannung und im spannungslosen Zustand erfolgen.
Um Schäden und Fehler am Gerät (z.B. durch Spannungsinduktion) zu verhindern, sind abgeschirmte Leitungen zu verwenden, eine Parallelverlegung zu stromführenden Leitungen zu vermeiden und die EMV- Richtlinien zu beachten. ­ Dieses Gerät ist nur für den angegebenen Verwendungszweck zu nutzen, dabei sind die entsprechenden Sicherheitsvorschriften des VDE, der Länder, ihrer Überwachungsorgane, des TÜV und der örtlichen EVU zu beachten. Der Käufer hat die Einhaltung der Bau- und Sicherungsbestimmung zu gewährleisten und Gefährdungen aller Art zu vermeiden. ­ Für Mängel und Schäden, die durch unsachgemäße Verwendung dieses Gerätes entstehen, werden keinerlei Gewährleistungen und Haftungen übernommen. ­ Folgeschäden, welche durch Fehler an diesem Gerät entstehen, sind von der Gewährleistung und Haftung ausgeschlossen. ­ Montage und Inbetriebnahme der Geräte darf nur durch Fachpersonal erfolgen. ­ Es gelten ausschließlich die technischen Daten und Anschlussbedingungen der zum Gerät gelieferten Montage- und Bedienungsanleitung, Abweichungen zur Katalogdarstellung sind nicht zusätzlich aufgeführt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte möglich. ­ Bei Veränderungen der Geräte durch den Anwender entfallen alle Gewährleistungsansprüche. ­ Dieses Gerät darf nicht in der Nähe von Wärmequellen (z.B. Heizkörpern) oder deren Wärmestrom eingesetzt werden, eine direkte Sonneneinstrahlung oder Wärmeeinstrahlung durch ähnliche Quellen (starke Leuchte, Halogenstrahler) ist unbedingt zu vermeiden. ­ Der Betrieb in der Nähe von Geräten, welche nicht den EMV- Richtlinien entsprechen, kann zur Beeinflussung der Funktionsweise führen. ­ Dieses Gerät darf nicht für Überwachungszwecke, welche dem Schutz von Personen gegen Gefährdung oder Verletzung dienen und nicht als Not-Aus-Schalter an Anlagen und Maschinen oder vergleichbare sicherheitsrelevante Aufgaben verwendet werden. ­ Die Gehäuse- und Gehäusezubehörmaße können geringe Toleranzen zu den Angaben dieser Anleitung aufweisen. ­ Veränderungen dieser Unterlagen sind nicht gestattet. ­ Reklamationen werden nur vollständig in Originalverpackung angenommen. Hinweise zur Inbetriebnahme: Dieses Gerät wurde unter genormten Bedingungen kalibriert, abgeglichen und geprüft. Bei Betrieb unter abweichenden Bedingungen empfehlen wir Vorort eine manuelle Justage erstmals bei Inbetriebnahme sowie anschließend in regelmäßigen Abständen vorzunehmen. Eine Inbetriebnahme ist zwingend durchzuführen und darf nur von Fachpersonal vorgenommen werden! Vor der Montage und Inbetriebnahme ist diese Anleitung zu lesen und die alle darin gemachten Hinweise sind zu beachten!
D Achtung
Auf den richtigen Anschluss des Potentiometer ist zwingend zu achten, da ein verpolen zum Kurzschluss führen kann ! Um unterschiedlich Montagehöhen der Abdeckung auszugleichen, liegen je nach Schalterprogramm zwei Steckachsen für das Potentiometer bei. Damit wird sichergestellt, dass die min. und max. Anschläge des Potentiometers richtig funktionieren.
9

G THERMASGARD® FSTF

Rev. 2022 - V15

A room temperature sensor THERMASGARD® FSTF is used for air temperature measurement or setpoint adjustment, for presence detection or as room control and operating panel with temperature sensor, push-buttons, potentiometers, status indicators (LEDs). The in-wall sensor is mounted in high-quality panel switch programmes, ideally of the brands Gira, Berker, Merten, Jung, Siemens or Busch-Jaeger (using in-wall adapters) either individually or in combination with light switches, socket outlets, etc.It is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and clean room technology, and in interior rooms, such as living rooms, offices, hotels, etc.

TECHNICAL DATA

Measuring ranges:

­30...+60 °C

Sensor / output:

see table, assembled on board, passive

Range suppression:

in the button

Testing current:

see page 15

Potentiometers:

standard 1 k, max. 0.1 W (other ratings optional on request, e. g. 100 , 2.5 k, 5 k, 10 k optional 0 -10 V linear)

Turn switches:

max. 24 V AC / DC, max. 130 mA, max. 5 steps (0, Auto, I, II, III)

Rocker switch:

max. 24 V AC / DC, max. 130 mA

Push-buttons:

normally open contact, max. 24 V DC / 10 mA

LEDs:

max. 24 V DC (optional max. 24 V AC), standard green (red, yellow or two-colour optional)

Installation:

in in-wall flush box Ø 55 mm

Electrical connection:

FSTF -1 via screw terminals 0.14 - 1.5 mm², FSTF xx via plug terminals 1.0 - 2.5 mm², on safety extra-low voltage only, max. 42 V AC, 60 V DC

Humidity:

max. 90 % r.H., non-precipitating air

Protection class:

III (according to EN 60 730)

Protection type:

IP 20 (according to EN 60 529)

SWITCH PROGRAMMES

Manufacturer:

GIRA System 55 (other switch programmes, manufacturers, colours and prices upon request

Housing:

plastic, standard colour pure white, glossy (similar to RAL 9010) (other colours are possible on request with colour variants depending on the respective light switch programme)

1x two-wire connection standard
1x two-wire connection LM 235 Z (KP 10)

Connecting diagram

55

FSTF 1 - U

THERMASGARD® FSTF 1
Standard version with sensor

4 6
4 6
3 7
3 7
2211

THERMASGARD® FSTF 1
Type / WG01 FSTF1 FSTF1 Pt100 FSTF1 Pt1000 FSTF1 Ni1000 FSTF1 NiTK FSTF1 LM235Z FST F1 NTC1,8K FSTF1 NTC10K FSTF1 NTC20K

Room temperature sensors
Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

10

Item No. IP 20 (­30...+60 °C) 1101-5020-1000-162 1101-5020-5000-162 1101-5020-9000-162 1101-5021-0000-162 1101-5022-1000-162 1101-5021-2000-162 1101-5021-5000-162 1101-5021-6000-162

G THERMASGARD® FSTF (diverse versions)

Connecting diagram

Rev. 2022 - V15 FSTF x x LT

THERMASGARD® FSTF xx LT
Version with sensor, LED (green), and push-button (max. 24 V DC, max. 10 mA)

THERMASGARD® FSTF xx LT Room temperature sensors

Type / WG01 FSTF xx LT FSTF Pt100 L T FSTF Pt1000 L T FSTF Ni1000 L T FSTF NiTK L T FSTF LM235Z L T FST F NTC1,8K L T FSTF NTC10K L T FSTF NTC20K L T

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

Item No. IP 20 (­30...+60 °C) 1101-5020-1593-350 1101-5020-5593-350 1101-5020-9593-350 1101-5021-0593-350 1101-5022-1593-350 1101-5021-2593-350 1101-5021-5593-350 1101-5021-6593-350

Connecting diagram

FSTF xx L D2

THERMASGARD® FSTF xx L D2
Version with sensor, LED (green), and turn switch (2-step) (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx LD2 Room temperature sensors

Type / WG01 FSTF xx LD2 FSTF Pt100 D2 L FSTF Pt1000 D2 L FSTF Ni1000 D2 L FSTF NiTK D2 L FSTF LM235Z D2 L FST F NTC1,8K D2 L FSTF NTC10K D2 L FSTF NTC20K D2 L

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

11

Item No. IP 20 (­30...+60 °C) 1101-5020-1631-351 1101-5020-5631-351 1101-5020-9631-351 1101-5021-0631-351 1101-5022-1631-351 1101-5021-2631-351 1101-5021-5631-351 1101-5021-6631-351

G THERMASGARD® FSTF (diverse versions)

Connecting diagram

Rev. 2022 - V15 FSTF xx L D4

THERMASGARD® FSTF xx L D4
Version with sensor, LED (green) and turn switch (4-step) (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx LD4 Room temperature sensors

Type / WG01 FSTF xx LD4 FSTF Pt100 D4 L FSTF Pt1000 D4 L FSTF Ni1000 D4 L FSTF NiTK D4 L FSTF LM235Z D4 L FST F NTC1,8K D4 L FSTF NTC10K D4 L FSTF NTC20K D4 L

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

Item No. IP 20 (­30...+60 °C) 1101-5020-1643-352 1101-5020-5643-352 1101-5020-9643-352 1101-5021-0643-352 1101-5022-1643-352 1101-5021-2643-352 1101-5021-5643-352 1101-5021-6643-352

Connecting diagram

FSTF xx P

THERMASGARD® FSTF xx P
Version with sensor and potentiometer (1 kOhm, max. 0.1 W)

THERMASGARD® FSTF xx P Room temperature sensors

Type / WG01 FSTF xx P FSTF Pt100 P FSTF Pt1000 P FSTF Ni1000 P FSTF NiTK P FSTF LM235Z P FST F NTC1,8K P FSTF NTC10K P FSTF NTC20K P

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

12

Item No. IP 20 (­30...+60 °C) 1101-5020-1001-282 1101-5020-5001-162 1101-5020-9001-162 1101-5021-0001-162 1101-5022-1001-162 1101-5021-2001-162 1101-5021-5001-162 1101-5021-6001-162

G THERMASGARD® FSTF (diverse versions)

Connecting diagram

Rev. 2022 - V15 FSTF xx PLW

THERMASGARD® FSTF xx PLW
Version with sensor, potentiometer (1 kOhm, max. 0.1 W), LED (green), and rocker switch (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx PLW Room temperature sensors

Type / WG01 FSTF xx PLW FSTF Pt100 P L W FSTF Pt1000 P L W FSTF Ni1000 P L W FSTF NiTK P L W FSTF LM235Z P L W FST F NTC1,8K P L W FSTF NTC10K P L W FSTF NTC20K P L W

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

Item No. IP 20 (­30...+60 °C) 1101-5020-1655-353 1101-5020-5655-353 1101-5020-9655-353 1101-5021-0655-353 1101-5022-1655-353 1101-5021-2655-353 1101-5021-5655-353 1101-5021-6655-353

Connecting diagram

FSTF x x PLT

THERMASGARD® FSTF xx PLT
Version with sensor, potentiometer (1 kOhm, max. 0.1 W), LED (green), and push-button (max. 24 V DC, max. 10 mA)

THERMASGARD® FSTF xx PLT Room temperature sensors

Type / WG01 FSTF xx PLT FSTF Pt100 P L T FSTF Pt1000 P L T FSTF Ni1000 P L T FSTF NiTK P L T FSTF LM235Z P L T FST F NTC1,8K P L T FSTF NTC10K P L T FSTF NTC20K P L T

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

13

Item No. IP 20 (­30...+60 °C) 1101-5020-1663-162 1101-5020-5663-162 1101-5020-9663-350 1101-5021-0663-350 1101-5022-1663-350 1101-5021-2663-350 1101-5021-5663-350 1101-5021-6663-350

G THERMASGARD® FSTF (diverse versions)

Connecting diagram

Rev. 2022 - V15 FSTF xx PD4

THERMASGARD® FSTF xx PD4
Version with sensor, potentiometer (1 kOhm, max. 0.1 W) and turn switch (max. 24 V AC / DC, max. 130 mA)

THERMASGARD® FSTF xx PD4 Room temperature sensors

Type / WG01 FSTF xx PD4 FSTF Pt100 P D4 FSTF Pt1000 P D4 FSTF Ni1000 P D4 FSTF NiTK P D4 FSTF LM235Z P D4 FST F NTC1,8K P D4 FSTF NTC10K P D4 FSTF NTC20K P D4

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

Item No. IP 20 (­30...+60 °C) 1101-5020-1007-354 1101-5020-5007-354 1101-5020-9007-354 1101-5021-0007-354 1101-5022-1007-354 1101-5021-2007-354 1101-5021-5007-354 1101-5021-6007-354

Connecting diagram

FSTF xx P 2L 2T

THERMASGARD® FSTF xx P 2L 2T
Version with sensor, potentiometer (1 kOhm, max. 0.1 W), 2 LEDs (green, red), and 2 push-buttons (max. 24 V DC, max. 10 mA)

THERMASGARD® FSTF xx P 2L 2T Room temperature sensors

Type / WG01 FSTF xx P 2L 2T FSTF Pt100 P 2L 2T FSTF Pt1000 P 2L 2T FSTF Ni1000 P 2L 2T FSTF NiTK P2L2T FSTF LM235Z P 2L 2T FST F NTC1,8K P 2L 2T FSTF NTC10K P 2L 2T FSTF NTC20K P 2L 2T

Sensor / Output passive Pt100 (according to DIN EN 60 751, class B) Pt1000 (according to DIN EN 60 751, class B) Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2.73 V at O °C), KP10 NTC 1.8 K NTC 10K NTC 20K

14

Item No. IP 20 (­30...+60 °C) 1101-5020-1672-256 1101-5020-5672-256 1101-5020-9672-256 1101-5021-0672-256 1101-5022-1672-256 1101-5021-2672-256 1101-5021-5672-256 1101-5021-6672-256

G General notes
Measuring principle of HVAC temperature sensors in general: The measuring principle of temperature sensors is based on an internal sensor that outputs a temperature-dependent resistance signal. The type of the internal sensor determines the output signal. The following active / passive temperature sensors are distinguished:
a) Pt 100 measuring resistor (according to DIN EN 60 751) b) Pt 1000 measuring resistor (according to DIN EN 60751) c) Ni 1000 measuring resistor (according to DIN EN 43 760, TCR = 6180 ppm / K) d) Ni 1000_TK 5000 measuring resistor (TCR = 5000 ppm / K) e) LM235Z, semiconductor IC (10 mV / K, 2.73 V / °C). Ensure correct polarity + /­ when connecting! f) NTC (according to DIN 44070) g) PTC h) KTY silicon temperature sensors
The most important resistance characteristics are shown on the last page of these operating instructions. According to their characteristics, individual temperature sensors exhibit different slopes in the range between 0 °C and +100 °C (TK value). Maximum-possible measuring ranges also vary from sensor to sensor (for some examples to this see under technical data).

G Resistance characteristics of passive temperature sensors (see last page)
In order to avoid damages / errors, preferably shielded cables are to be used. Laying measuring cables parallel with current-carrying cables must in any case be avoided. EMC directives shall be observed! These instruments must be installed by authorised specialists only!

Limiting deviation according to classes: Tolerances at 0 °C:
Platinum sensors (Pt100, Pt1000): DIN EN 60751, class B ................................................................± 0.3 K 1 / 3 DIN EN 60751, class B........................................................± 0.1 K
Nickel sensors: NI1000 DIN EN 43760, class B.................................................± 0.4 K NI1000 1 / 2 DIN EN 43760, class B.........................................± 0.2 K NI1000 TK5000...........................................................................± 0.4 K

ATTENTION, NOTE !
Testing current influences the thermometer`s measuring accuracy due to intrinsic heating and therefore, should never be greater than as specified below:
Standard values for testing current:
Sensor current, maximum ................................................................. Imax. Pt1000 (thin-layer) .................................................................. < 0,6 mA Pt100 (thin-layer) .................................................................. < 1,0 mA Ni1000 (DIN), Ni1000 TK5000 ............................................. < 0,3 mA NTC xx ............................................................................................ < 2 mW LM235Z............................................................................. 400 µA ... 5 mA KTY 81 - 210 .................................................................................... < 2 mA

15

G General notes
Our "General Terms and Conditions for Business" together with the "General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry" (ZVEI conditions) including supplementary clause "Extended Retention of Title" apply as the exclusive terms and conditions. In addition, the following points are to be observed: ­ These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded! ­ In order to prevent measuring errors, ensure during installation on an in-wall flush box that the end of the installation pipe is sealed against draught. ­ Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage
induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed. ­ This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and
the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind. ­ No warranties or liabilities will be assumed for defects and damages arising from improper use of this device. ­ Consequential damages caused by a fault in this device are excluded from warranty or liability. ­ These devices must be installed and commissioned by authorised specialists. ­ The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations
from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products. ­ In case of any modifications made by the user, all warranty claims are forfeited. ­ This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.
Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided. ­ Operating this device close to other devices that do not comply with EMC directives may influence functionality. ­ This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,
or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes. ­ Dimensions of enclosures or housing accessories may show slight tolerances on the specifications provided in these instructions. ­ Modifications of these records are not permitted. ­ In case of a complaint, only complete devices returned in original packing will be accepted. Notes on commissioning: This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals. Commissioning is mandatory and may only be performed by qualified personnel! These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!
G Caution
You must ensure that the potentiometer is connected up correctly. Polarity reversal can cause a short circuit. Depending on the switching program, there are two quick release axles enclosed with the potentiometer to compensate different installation heights of the covers. This ensures that the min. and max. stop of the set point adjustment function properly.
16

F THERMASGARD® FSTF

Rev. 2022 - V15

La sonde THERMASGARD® FSTF, sonde de température d'ambiance, sert à la mesure de la température de l'air ou au réglage de consigne, à la signalisation de présence ou comme appareil d'ambiance, comme tableau de commande avec sonde de température, boutons-poussoirs, potentiomètre et affichages d'état (DEL). Le montage de la sonde encastrée s'effectue dans un boîtier d'interrupteurs, de préférence de la marque Gira, Berker, Merten, Jung, Siemens ou Busch-Jaeger (au moyen d'un adaptateur d'encastrement). La sonde est installée de manière individuelle ou en combinaison avec des interrupteurs d'éclairage, des prises de courant, etc. Elle est utilisée dans un environnement non agressif, exempt de poussières, en technique de refroidissement, de climatisation et de salles blanches, dans les pièces d'habitation, les bureaux, les hôtels, etc.

CARACTÉRISTIQUES TECHNIQUES

Plages de mesure :

­30...+60 °C

Capteurs / sortie :

voir tableau, monté sur carte, passif

Limitation de la plage : intégrée dans le bouton de réglage

Courant de mesure : voir page 22

Potentiomètre :

Standard 1k, max. 0,1 W (d'autres valeurs en option sur demande, par ex. 100 , 2,5 k, 5 k, 10 k, option potentiomètre 0...10 V linéaire)

Commutateur rotatif :
Interrupteur à bascule : Bouton-poussoir :

max. 24 V ca /cc, max. 130 mA, 5 positions max. (0, Auto, I, II, III) max. 24 V ca /cc, max. 130 mA contact NO, max. 24 V cc, max. 10 mA

1 x 2 fils Standard

DEL :

max. 24 V cc (max. 24 V ca en option), standard vert (rouge, jaune ou bicolore en option)

Montage :

dans boîte d'encastrement Ø 55 mm

Raccordement électrique : FSTF -1 via bornes à fiche 0,14 - 1,5 mm², FSTF xx via bornes enfichables 1,0 - 2,5 mm², tension de sécurité, 42 V cc max., 60 V ca
Humidité d'air admissible : max. 90 % h.r., sans condensation de l'air

1 x 2 fils LM 235 Z (KP 10)

Classe de protection : III (selon EN 60 730)

Type de protection :

IP 20 (selon EN 60 529)

GAMME D'INTERRUPTEURS

Fabricant :

GIRA System 55 (d'autres gammes d'interrupteurs, fabricants d'interrupteurs, couleurs et prix sur demande)

Boîtier :

matière plastique, couleur standard blanc pur brillant (similaire à RAL 9010) (d'autres couleurs sur demande, les variantes de couleur dépendent des gammes d'interrupteurs de lumière)

Schéma de raccordement

55

FSTF 1 - U

THERMASGARD® FSTF 1
Modèle avec sonde (standard)

4 6
4 6
3 7
3 7
2211

THERMASGARD® FSTF 1
Type / WG01 FSTF1 FSTF1 Pt100 FSTF1 Pt1000 FSTF1 Ni1000 FSTF1 NiTK FSTF1 LM235Z FST F1 NTC1,8K FSTF1 NTC10K FSTF1 NTC20K

Sonde de température d'ambiance
capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

17

référence IP 20 (­30...+60 °C) 1101-5020-1000-162 1101-5020-5000-162 1101-5020-9000-162 1101-5021-0000-162 1101-5022-1000-162 1101-5021-2000-162 1101-5021-5000-162 1101-5021-6000-162

F THERMASGARD® FSTF (différents modèles)

Schéma de raccordement

Rev. 2022 - V15 FSTF x x LT

THERMASGARD® FSTF xx LT
Modèle avec sonde, diode électroluminescente (verte) et bouton-poussoir (max. 24 V cc, max. 10 mA)

THERMASGARD® FSTF xx LT Sonde de température d'ambiance

Type / WG01 FSTF xx LT FSTF Pt100 L T FSTF Pt1000 L T FSTF Ni1000 L T FSTF NiTK L T FSTF LM235Z L T FST F NTC1,8K L T FSTF NTC10K L T FSTF NTC20K L T

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

référence IP 20 (­30...+60 °C) 1101-5020-1593-350 1101-5020-5593-350 1101-5020-9593-350 1101-5021-0593-350 1101-5022-1593-350 1101-5021-2593-350 1101-5021-5593-350 1101-5021-6593-350

Schéma de raccordement

FSTF xx L D2

THERMASGARD® FSTF xx L D2
Modèle avec sonde, diode électroluminescente (verte) et commutateur rotatif (2 positions) (max. 24 V ca/cc, max. 130 mA)

THERMASGARD® FSTF xx LD2 Sonde de température d'ambiance

Type / WG01 FSTF xx LD2 FSTF Pt100 D2 L FSTF Pt1000 D2 L FSTF Ni1000 D2 L FSTF NiTK D2 L FSTF LM235Z D2 L FST F NTC1,8K D2 L FSTF NTC10K D2 L FSTF NTC20K D2 L

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

18

référence IP 20 (­30...+60 °C) 1101-5020-1631-351 1101-5020-5631-351 1101-5020-9631-351 1101-5021-0631-351 1101-5022-1631-351 1101-5021-2631-351 1101-5021-5631-351 1101-5021-6631-351

F THERMASGARD® FSTF (différents modèles)

Schéma de raccordement

Rev. 2022 - V15 FSTF xx L D4

THERMASGARD® FSTF xx L D4
Modèle avec sonde, diode électroluminescente (verte) et commutateur rotatif (4 positions) (max. 24 V ca/cc, max. 130 mA)

THERMASGARD® FSTF xx LD4 Sonde de température d'ambiance

Type / WG01 FSTF xx LD4 FSTF Pt100 D4 L FSTF Pt1000 D4 L FSTF Ni1000 D4 L FSTF NiTK D4 L FSTF LM235Z D4 L FST F NTC1,8K D4 L FSTF NTC10K D4 L FSTF NTC20K D4 L

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

référence IP 20 (­30...+60 °C) 1101-5020-1643-352 1101-5020-5643-352 1101-5020-9643-352 1101-5021-0643-352 1101-5022-1643-352 1101-5021-2643-352 1101-5021-5643-352 1101-5021-6643-352

Schéma de raccordement

FSTF xx P

THERMASGARD® FSTF xx P
Modèle avec sonde et potentiomètre (1 kOhm, max. 0,1 W)

THERMASGARD® FSTF xx P Sonde de température d'ambiance

Type / WG01 FSTF xx P FSTF Pt100 P FSTF Pt1000 P FSTF Ni1000 P FSTF NiTK P FSTF LM235Z P FST F NTC1,8K P FSTF NTC10K P FSTF NTC20K P

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

19

référence IP 20 (­30...+60 °C) 1101-5020-1001-282 1101-5020-5001-162 1101-5020-9001-162 1101-5021-0001-162 1101-5022-1001-162 1101-5021-2001-162 1101-5021-5001-162 1101-5021-6001-162

F THERMASGARD® FSTF (différents modèles)

Schéma de raccordement

Rev. 2022 - V15 FSTF xx PLW

THERMASGARD® FSTF xx PLW
Modèle avec sonde, potentiomètre (1 kOhm, max. 0,1 W), diode électroluminescente (verte) et interrupteur à bascule (max. 24 V ca/cc, max. 130 mA)

THERMASGARD® FSTF xx PLW Sonde de température d'ambiance

Type / WG01 FSTF xx PLW FSTF Pt100 P L W FSTF Pt1000 P L W FSTF Ni1000 P L W FSTF NiTK P L W FSTF LM235Z P L W FST F NTC1,8K P L W FSTF NTC10K P L W FSTF NTC20K P L W

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

référence IP 20 (­30...+60 °C) 1101-5020-1655-353 1101-5020-5655-353 1101-5020-9655-353 1101-5021-0655-353 1101-5022-1655-353 1101-5021-2655-353 1101-5021-5655-353 1101-5021-6655-353

Schéma de raccordement

FSTF x x PLT

THERMASGARD® FSTF xx PLT
Modèle avec sonde, potentiomètre (1 kOhm, max. 0,1 W), diode électroluminescente (verte) et bouton-poussoir (max. 24 V cc, max. 10 mA)

THERMASGARD® FSTF xx PLT Sonde de température d'ambiance

Type / WG01 FSTF xx PLT FSTF Pt100 P L T FSTF Pt1000 P L T FSTF Ni1000 P L T FSTF NiTK P L T FSTF LM235Z P L T FST F NTC1,8K P L T FSTF NTC10K P L T FSTF NTC20K P L T

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

20

référence IP 20 (­30...+60 °C) 1101-5020-1663-162 1101-5020-5663-162 1101-5020-9663-350 1101-5021-0663-350 1101-5022-1663-350 1101-5021-2663-350 1101-5021-5663-350 1101-5021-6663-350

F THERMASGARD® FSTF (différents modèles)

Schéma de raccordement

Rev. 2022 - V15 FSTF xx PD4

THERMASGARD® FSTF xx PD4
Modèle avec sonde, potentiomètre (1 kOhm, max. 0,1 W) et commutateur rotatif (max. 24 V ca/cc, max. 130 mA)

THERMASGARD® FSTF xx PD4 Sonde de température d'ambiance

Type / WG01 FSTF xx PD4 FSTF Pt100 P D4 FSTF Pt1000 P D4 FSTF Ni1000 P D4 FSTF NiTK P D4 FSTF LM235Z P D4 FST F NTC1,8K P D4 FSTF NTC10K P D4 FSTF NTC20K P D4

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

référence IP 20 (­30...+60 °C) 1101-5020-1007-354 1101-5020-5007-354 1101-5020-9007-354 1101-5021-0007-354 1101-5022-1007-354 1101-5021-2007-354 1101-5021-5007-354 1101-5021-6007-354

Schéma de raccordement

FSTF xx P 2L 2T

THERMASGARD® FSTF xx P 2L 2T
Modèle avec sonde, potentiomètre (1 kOhm, max. 0,1 W), 2 diodes électroluminescentes (verte et rouge) et 2 boutons-poussoirs (max. 24 V cc, max. 10 mA)

THERMASGARD® FSTF xx P 2L 2T Sonde de température d'ambiance

Type / WG01 FSTF xx P 2L 2T FSTF Pt100 P 2L 2T FSTF Pt1000 P 2L 2T FSTF Ni1000 P 2L 2T FSTF NiTK P2L2T FSTF LM235Z P 2L 2T FST F NTC1,8K P 2L 2T FSTF NTC10K P 2L 2T FSTF NTC20K P 2L 2T

capteur / sortie passif Pt100 (selon DIN EN 60 751, classe B) Pt1000 (selon DIN EN 60 751, classe B) Ni1000 (selon DIN EN 43 760, classe B, TCR = 6180 ppm / K) Ni1000 TK5000 (TCR = 5000 ppm / K), LG - Ni1000 LM235Z (TCR = 10 mV / K; 2,73 V à 0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

21

référence IP 20 (­30...+60 °C) 1101-5020-1672-256 1101-5020-5672-256 1101-5020-9672-256 1101-5021-0672-256 1101-5022-1672-256 1101-5021-2672-256 1101-5021-5672-256 1101-5021-6672-256

F Généralités
Principe de mesure des sondes de température pour applications CVC (HVAC) en général: Le principe de mesure se base sur le fait que le capteur à l'intérieur génère un signal de résistance dépendant de la température. Le signal de sortie est déterminé par le type de capteur qui se trouve à l'intérieur. On distingue les capteurs de température actifs et passifs suivants:
a) Pt 100 ­ résistance électrique (suivant DIN EN 60 751) b) Pt 1000 ­ résistance électrique (suivant DIN EN 60751) c) Ni 1000 ­ résistance électrique (suivant DIN EN 43 760, TCR=6180 ppm / K) d) Ni 1000_TK5000 ­ résistance électrique (TCR=5000 ppm / K) e) LM235Z, semi-conducteur IC (10mV / K, 2,73V / °C). Lors du raccordement électrique, veiller à la bonne polarisation + / ­ ! f) NTC (suivant DIN 44070) g) PTC h) KTY- capteurs de température en silicium
Les courbes caractéristiques les plus importantes des capteurs de température se trouvent à la dernière page de cette notice d'instruction. Conformément à leur courbe caractéristique, chacun des capteurs de température présente une montée différente dans la plage située entre 0 et +100 °C (valeur du coefficient de température). Pareillement, les plages de mesure maximales possibles varient en fonction du capteur utilisé (voir quelques exemples à ce sujet dans la rubrique données techniques).

F Courbes caractéristiques (cf. dernière page)
Pour éviter des endommagements ou erreurs de mesure, il est conseillé d'utiliser de préférence des câbles blindés. Ne pas poser les câbles de sonde en parallèle avec des câbles de puissance. Les directives CEM sont à respecter ! L'installation des appareils doit être effectuée uniquement par un spécialiste qualifié!

Incertitudes de mesure selon classes: Tolérances à 0 °C:
Sondes platine (Pt100, Pt1000): DIN EN 60751, classe B..............................................................± 0,3 K 1 / 3 DIN EN 60751, classe B......................................................± 0,1 K
Sondes nickel: NI1000 DIN EN 43760, classe B...............................................± 0,4 K NI1000 1 / 2 DIN EN 43760, classe B ......................................± 0,2 K NI1000 TK5000...........................................................................± 0,4 K

ATTENTION !
À cause de son propre échauffement, le courant de mesure influence la précision du thermomètre et ne doit donc pas dépasser les valeurs suivantes :
Valeurs indicatives pour le courant de mesure:
Courant de mesure maximale ............................................................ I max Pt1000 (éléments résistifs) .................................................. < 0,6 mA Pt100 (éléments résistifs) .................................................. < 1,0 mA Ni1000 (DIN), Ni1000 TK5000 ............................................. < 0,3 mA NTC xx ............................................................................................ < 2 mW LM235Z............................................................................. 400 µA ... 5 mA KTY 81 - 210 .................................................................................... < 2 mA

22

F Généralités
Seules les CGV de la société S+S, les « Conditions générales de livraison du ZVEI pour produits et prestations de l'industrie électronique » ainsi que la clause complémentaire « Réserve de propriété étendue » s'appliquent à toutes les relations commerciales entre la société S+S et ses clients. Il convient en outre de respecter les points suivants : ­ Avant de procéder à toute installation et à la mise en service, veuillez lire attentivement la présente notice et toutes les consignes qui y sont précisées ! ­ Afin d'empêcher toute erreur de mesure, lors du montage sur une boîte d'encastrement standard, l'extrémité du tube d'installation doit être étanche aux
courants d'air éventuels. ­ Les raccordements électriques doivent être exécutés HORS TENSION. Ne branchez l'appareil que sur un réseau de très basse tension de sécurité.
Pour éviter des endommagements / erreurs sur l'appareil (par ex. dus à une induction de tension parasite), il est conseillé d'utiliser des câbles blindés, ne pas poser les câbles de sondes en parallèle avec des câbles de puissance, les directives CEM sont à respecter. ­ Cet appareil ne doit être utilisé que pour l'usage qui est indiqué en respectant les règles de sécurité correspondantes de la VDE, des Länders, de leurs organes de surveillance, du TÜV et des entreprises d'approvisionnement en énergie locales. L'acheteur doit respecter les dispositions relatives à la construction et à la sécurité et doit éviter toutes sortes de risques. ­ Nous déclinons toute responsabilité ou garantie pour les défauts et dommages résultant d'une utilisation inappropriée de cet appareil. ­ Nous déclinons toute responsabilité ou garantie au titre de tout dommage consécutif provoqué par des erreurs commises sur cet appareil. ­ L'installation et la mise en service des appareils doit être effectuée uniquement par du personnel qualifié. ­ Seules les données techniques et les conditions de raccordement indiquées sur la notice d'instruction accompagnant l'appareil sont applicables, des différences par rapport à la présentation dans le catalogue ne sont pas mentionnées explicitement et sont possibles suite au progrès technique et à l'amélioration continue de nos produits. ­ En cas de modifications des appareils par l'utilisateur, tous droits de garantie ne seront pas reconnus. ­ Cet appareil ne doit pas être utilisé à proximité des sources de chaleur (par ex. radiateurs) ou de leurs flux de chaleur, il faut impérativement éviter un ensoleillement direct ou un rayonnement thermique provenant de sources similaires (lampes très puissantes, projecteurs à halogène). ­ L'utilisation de l'appareil à proximité d'appareils qui ne sont pas conformes aux directives « CEM » pourra nuire à son mode de fonctionnement. ­ Cet appareil ne devra pas être utilisé à des fins de surveillance qui visent à la protection des personnes contre les dangers ou les blessures ni comme interrupteur d'arrêt d'urgence sur des installations ou des machines ni pour des fonctions relatives à la sécurité comparables. ­ Il est possible que les dimensions du boîtier et des accessoires du boîtier divergent légèrement des indications données dans cette notice. ­ Il est interdit de modifier la présente documentation. ­ En cas de réclamation, les appareils ne sont repris que dans leur emballage d'origine et si tous les éléments de l'appareil sont complets. Consignes de mise en service : Cet appareil a été étalonné, ajusté et testé dans des conditions normalisées. En cas de fonctionnement dans des conditions différentes, nous recommandons un premier réglage manuel sur site lors de la mise en service et à intervalles réguliers par la suite. La mise en service ne doit être effectuée que par du personnel qualifié ! Avant de procéder à l'installation et à la mise en service, veuillez lire attentivement la présente notice et toutes les consignes qui y sont précisées !
F Attention
Veiller impérativement au branchement correct du potentiomètre, car un inversement des pôles peut provoquer un court-circuit ! Pour compenser les différentes hauteurs du capot, deux types d'axes pour le potentiomètre sont livrés avec le matériel. Ainsi le bon fonctionnement en butée min et max du bouton de consigne est assuré.
23

r THERMASGARD® FSTF

Rev. 2022 - V15

    THERMASGARD® FSTF     ,   ,         , ,     (, LED).           ,     Gira, Berker, Merten, Jung  Siemens  Busch-Jaeger (      ),      ,    . .         ,   ,  ,       ,   ,     ,   . .

 

 :   / :  :  : :
 :
 : : :
:     :
   :  :  :    :
:

-30 ...+60 °C

. ,  , 

  

. . 29

 -- 1 , . 0,1  ( --    ; , 100 , 2,5 , 5 , 10 ,  --  0­10 B )

. 24  . /. , . 130 , . 5  (0, Auto, I, II, III)

. 24  . /. , . 130 

, . 24 B . , . 10 
. 24  . , ( -- . 24  . ),  --  ( -- ,   )

1    

   Ø 55 

FSTF -1    0,14­1,5 ², FSTF xx    1,0 - 2,5 ²,     , . 42 B  , 60 B  
. 90 %,  

1   LM 235 Z (KP 10)

III ( EN 60 730)

IP 20 ( EN 60 529)

GIRA System 55 (   ,  ,    --  )
,   --  ,  ( RAL 9010) (   ,        )

 

55

FSTF 1 - U

THERMASGARD® FSTF 1
C   

4 6
4 6
3 7
3 7
2211

THERMASGARD® FSTF 1    

 / WG01 FSTF1 FSTF1 Pt100 FSTF1 Pt1000 FSTF1 Ni1000 FSTF1 NiTK FSTF1 LM235Z FST F1 NTC1,8K FSTF1 NTC10K FSTF1 NTC20K

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

24

.  IP 20 (­30...+60 °C) 1101-5020-1000-162 1101-5020-5000-162 1101-5020-9000-162 1101-5021-0000-162 1101-5022-1000-162 1101-5021-2000-162 1101-5021-5000-162 1101-5021-6000-162

r THERMASGARD® FSTF ( )

 

Rev. 2022 - V15 FSTF x x LT

THERMASGARD® FSTF xx LT
  ,  ()   (. 24  . , . 10 )

THERMASGARD® FSTF xx LT    

 / WG01 FSTF xx LT FSTF Pt100 L T FSTF Pt1000 L T FSTF Ni1000 L T FSTF NiTK L T FSTF LM235Z L T FST F NTC1,8K L T FSTF NTC10K L T FSTF NTC20K L T

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

.  IP 20 (­30...+60 °C) 1101-5020-1593-350 1101-5020-5593-350 1101-5020-9593-350 1101-5021-0593-350 1101-5022-1593-350 1101-5021-2593-350 1101-5021-5593-350 1101-5021-6593-350

 

FSTF xx L D2

THERMASGARD® FSTF xx L D2
  ,  ()    () (. 24  . /. , . 130 )

THERMASGARD® FSTF xx LD2    

 / WG01 FSTF xx LD2 FSTF Pt100 D2 L FSTF Pt1000 D2 L FSTF Ni1000 D2 L FSTF NiTK D2 L FSTF LM235Z D2 L FST F NTC1,8K D2 L FSTF NTC10K D2 L FSTF NTC20K D2 L

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

25

.  IP 20 (­30...+60 °C) 1101-5020-1631-351 1101-5020-5631-351 1101-5020-9631-351 1101-5021-0631-351 1101-5022-1631-351 1101-5021-2631-351 1101-5021-5631-351 1101-5021-6631-351

r THERMASGARD® FSTF ( )

 

Rev. 2022 - V15 FSTF xx L D4

THERMASGARD® FSTF xx L D4
  ,  ()    () (. 24  . /. , . 130 )

THERMASGARD® FSTF xx LD4    

 / WG01 FSTF xx LD4 FSTF Pt100 D4 L FSTF Pt1000 D4 L FSTF Ni1000 D4 L FSTF NiTK D4 L FSTF LM235Z D4 L FST F NTC1,8K D4 L FSTF NTC10K D4 L FSTF NTC20K D4 L

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

.  IP 20 (­30...+60 °C) 1101-5020-1643-352 1101-5020-5643-352 1101-5020-9643-352 1101-5021-0643-352 1101-5022-1643-352 1101-5021-2643-352 1101-5021-5643-352 1101-5021-6643-352

 

FSTF xx P

THERMASGARD® FSTF xx P
     (1 , . 0,1 )

THERMASGARD® FSTF xx P    

 / WG01 FSTF xx P FSTF Pt100 P FSTF Pt1000 P FSTF Ni1000 P FSTF NiTK P FSTF LM235Z P FST F NTC1,8K P FSTF NTC10K P FSTF NTC20K P

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

26

.  IP 20 (­30...+60 °C) 1101-5020-1001-282 1101-5020-5001-162 1101-5020-9001-162 1101-5021-0001-162 1101-5022-1001-162 1101-5021-2001-162 1101-5021-5001-162 1101-5021-6001-162

r THERMASGARD® FSTF ( )

 

Rev. 2022 - V15 FSTF xx PLW

THERMASGARD® FSTF xx PLW
  ,  (1 , . 0,1 ),  ()    (. 24  . /. , . 130 )

THERMASGARD® FSTF xx PLW    

 / WG01 FSTF xx PLW FSTF Pt100 P L W FSTF Pt1000 P L W FSTF Ni1000 P L W FSTF NiTK P L W FSTF LM235Z P L W FST F NTC1,8K P L W FSTF NTC10K P L W FSTF NTC20K P L W

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

.  IP 20 (­30...+60 °C) 1101-5020-1655-353 1101-5020-5655-353 1101-5020-9655-353 1101-5021-0655-353 1101-5022-1655-353 1101-5021-2655-353 1101-5021-5655-353 1101-5021-6655-353

 

FSTF x x PLT

THERMASGARD® FSTF xx PLT
  ,  (1 , . 0,1 ),  ()   (. 24  . , . 10 )

THERMASGARD® FSTF xx PLT    

 / WG01 FSTF xx PLT FSTF Pt100 P L T FSTF Pt1000 P L T FSTF Ni1000 P L T FSTF NiTK P L T FSTF LM235Z P L T FST F NTC1,8K P L T FSTF NTC10K P L T FSTF NTC20K P L T

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

27

.  IP 20 (­30...+60 °C) 1101-5020-1663-162 1101-5020-5663-162 1101-5020-9663-350 1101-5021-0663-350 1101-5022-1663-350 1101-5021-2663-350 1101-5021-5663-350 1101-5021-6663-350

r THERMASGARD® FSTF ( )

 

Rev. 2022 - V15 FSTF xx PD4

THERMASGARD® FSTF xx PD4
  ,  (1 , . 0,1 ),    (. 24  . /. , . 130 )

THERMASGARD® FSTF xx PD4    

 / WG01 FSTF xx PD4 FSTF Pt100 P D4 FSTF Pt1000 P D4 FSTF Ni1000 P D4 FSTF NiTK P D4 FSTF LM235Z P D4 FST F NTC1,8K P D4 FSTF NTC10K P D4 FSTF NTC20K P D4

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

.  IP 20 (­30...+60 °C) 1101-5020-1007-354 1101-5020-5007-354 1101-5020-9007-354 1101-5021-0007-354 1101-5022-1007-354 1101-5021-2007-354 1101-5021-5007-354 1101-5021-6007-354

 

FSTF xx P 2L 2T

THERMASGARD® FSTF xx P 2L 2T
  ,  (1 , . 0,1 ),   (  )    (. 24  . , . 10 )

THERMASGARD® FSTF xx P 2L 2T    

 / WG01 FSTF xx P 2L 2T FSTF Pt100 P 2L 2T FSTF Pt1000 P 2L 2T FSTF Ni1000 P 2L 2T FSTF NiTK P2L2T FSTF LM235Z P 2L 2T FST F NTC1,8K P 2L 2T FSTF NTC10K P 2L 2T FSTF NTC20K P 2L 2T

.  /   Pt100 ( DIN EN 60 751,  B) Pt1000 ( DIN EN 60 751,  B) Ni1000 ( DIN EN 43 760,   ,  = 6180 -1 / K) Ni1000 TK5000 ( = 5000 -1 / K), LG - Ni1000 LM235Z ( = 10  / K; 2,73   0 °C), KP10 NTC 1,8 K NTC 10K NTC 20K

28

.  IP 20 (­30...+60 °C) 1101-5020-1672-256 1101-5020-5672-256 1101-5020-9672-256 1101-5021-0672-256 1101-5022-1672-256 1101-5021-2672-256 1101-5021-5672-256 1101-5021-6672-256

r   
      HLK (HVAC):           (),   ,  .       .    /   :
)   Pt 100 (. DIN EN 60 751) )   Pt 1000 (. DIN EN 60751) )   Ni 1000 (. DIN EN 43 760, TCR=6180 ppm / K) )   Ni 1000_TK5000 (TCR=5000 ppm / K) ) LM235Z,  IC (10  / K, 2,73  / °C),     + / ­ ! ) NTC (. DIN 44070) ) PTC )    KTY
        .   ,   ,      0  +100 °C ( TK).         (.     ).

r      (   )
         .       .     !       .

   :   0 °C:
    (Pt100, Pt1000): DIN EN 60751,  ...............................................................± 0,3 K 1 / 3 DIN EN 60751,  .......................................................± 0,1 K
   : NI1000 DIN EN 43760,  ................................................± 0,4 K NI1000 1 / 2 DIN EN 43760,   .......................................± 0,2 K NI1000 TK5000...........................................................................± 0,4 K

 !
                  :
    :
 .................................................................. Imax. Pt1000 () ..................................................... < 0,6 A Pt100 () ..................................................... < 1,0 A Ni1000 (DIN), Ni1000 TK5000 .............................................. < 0,3 A NTC xx ............................................................................................. < 2  LM235Z..............................................................................400 µA ... 5 A KTY 81 - 210 .....................................................................................< 2 A

29

r   
         ,    «        » (ZVEI)    «   ».  ,    : ­          ;        ! ­     - ,          . ­             .
     (,  )    ,           . ­        ,      VDE (  ), ,    ,        .       ,          . ­        ,      . ­ ,     ,     . ­         . ­       ,          .         ,             . ­         . ­           (,  )     ;                (  ,  ). ­   ,      (EMV),     . ­         / ,           / ,               . ­               . ­    . ­          .     :    ,      .                        .        !         ;        !
r 
    ,         !       ,           .       ""  "".
30

D G F r
Einige Ausführungen im Überblick ... An overview of various versions ... Voici les modèles principaux ...   ...
© Copyright by S+S Regeltechnik GmbH Nachdruck, auch auszugsweise, nur mit Genehmigung der S+S Regeltechnik GmbH. Reprint in full or in parts requires permission from S+S Regeltechnik GmbH. La reproduction des textes même partielle est uniquement autorisée après accord de la société S+S Regeltechnik GmbH. ,      ,     S+S Regeltechnik GmbH. Irrtümer und technische Änderungen vorbehalten. Alle Angaben entsprechen unserem Kenntnisstand bei Veröffentlichung. Sie dienen nur zur Information über unsere Produkte und deren Anwendungsmöglichkeiten, bieten jedoch keine Gewähr für bestimmte Produkteigenschaften. Da die Geräte unter verschiedensten Bedingungen und Belastungen eingesetzt werden, die sich unserer Kontrolle entziehen, muss ihre spezifische Eignung vom jeweiligen Käufer bzw. Anwender selbst geprüft werden. Bestehende Schutzrechte sind zu berücksichtigen. Einwandfreie Qualität gewährleisten wir im Rahmen unserer Allgemeinen Lieferbedingungen. Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions. Sous réserve d'erreurs et de modifications techniques. Toutes les informations correspondent à l'état de nos connaissances au moment de la publication. Elles servent uniquement à informer sur nos produits et leurs possibilités d'application, mais n'offrent aucune garantie pour certaines caractéristiques du produit. Etant donné que les appareils sont soumis à des conditions et des sollicitations diverses qui sont hors de notre contrôle, leur adéquation spécifique doit être vérifiée par l'acheteur ou l'utilisateur respectif. Tenir compte des droits de propriété existants. Nous garantissons une qualité parfaite dans le cadre de nos conditions générales de livraison.     .         .           ,       .         ,     ,        .      .        «  ».
31

D G F r
Widerstandskennlinien für passive Temperatursensoren Resistance characteristics of passive temperature sensors Courbes caractéristiques pour capteurs de température passive     

° C ­ 50 ­ 40 ­ 30 ­ 20 ­ 10
0 + 10 + 20 + 30 + 40 + 50 + 60 + 70 + 80 + 90 + 100 + 110 + 120 + 130 + 140 + 150

PT 100
 80.3 84.3 88.2 92.2 96.1 100.0 103.9 107.8 111.7 115.5 119.4 123.2 127.1 130.9 134.7 138.5 142.3 146.1 149.8 153.6 157.3

PT 1000
 803 843 882 922 961 1000 1039 1078 1117 1155 1194 1232 1271 1309 1347 1385 1423 1461 1498 1536 1573

Ni 1000
 743 791 842 893 946 1000 1056 1112 1171 1230 1291 1353 1417 1483 1549 1618 1688 1760 1833 1909 1987

Ni 1000 TK 5000
 790.8 826.8 871.7 913.4 956.2 1000.0 1044.8 1090.7 1137.6 1185.7 1235.0 1285.4 1337.1 1390.1 1444.4 1500.0 1557.0 1625.4
­ ­ ­

FeT (T1)
 ­ ­ 1935 2031 2128 2227 2328 2429 2534 2639 2746 2856 2967 3079 3195 3312 3431 3552 3676 3802 3929

° C ­ 50 ­ 40 ­ 30 ­ 20 ­ 10
0 + 10 + 20 + 30 + 40 + 50 + 60 + 70 + 80 + 90 + 100 + 110 + 120 + 130 + 140 + 150

NTC 1.8 kOhm
 ­ 39073 22301 13196 8069 5085 3294 2189 1489 1034 733 529 389 290 220 169 131 103 ­ ­ ­

NTC 2.2 kOhm
 ­ ­ 27886 16502 10070 6452 4138 2719 1812 1248 876 626 454 335 251 190 146 ­ ­ ­ ­

NTC 3 kOhm
 ­ ­ 53093 29125 16599 9795 5971 3747 2417 1597 1081 746 526 346 275 204 138 105 81 64 50

NTC 5 kOhm
 ­ ­ 88488 48541 27664 16325 9951 6246 4028 2662 1801 1244 876 627 458 339 255 195 151 118 93

NTC 10 kOhm
 ­ ­ 175785 96597 55142 32590 19880 12491 8058 5329 3605 2489 1753 1256 915 678 509 389 300 234 185
32

NTC 10 kPRE
 ­ ­ 135200 78910 47540 29490 18790 12270 8196 5594 3893 2760 1900 1457 1084 817 624 482 377 298 238

KTY 81-210
 1030 1135 1247 1367 1495 1630 1772 1922 2080 2245 2417 2597 2785 2980 3182 3392 3607 3817 4008 4166 4280
NTC 20 kOhm
 ­ 806800 413400 220600 122260 70140 41540 25340 15886 10212 6718 4518 3098 2166 1541 1114 818 609 460 351 272

LM235Z (KP10) mV ­ 2330 2430 2530 2630 2730 2830 2930 3030 3130 3230 3330 3430 3530 3630 3730 3830 3930 ­ ­ ­
NTC 50 kOhm
 ­ 2017000 1033500 551500 305650 175350 103850 63350 39715 25530 16795 11295 7745 5415 3852 2785 2045 1523 1149 878 679

° C ­ 50 ­ 40 ­ 30 ­ 20 ­ 10
0 + 10 + 20 + 30 + 40 + 50 + 60 + 70 + 80 + 90 + 100 + 110 + 120 + 130 + 140 + 150
° C ­ 50 ­ 40 ­ 30 ­ 20 ­ 10
0 + 10 + 20 + 30 + 40 + 50 + 60 + 70 + 80 + 90 + 100 + 110 + 120 + 130 + 140 + 150



References