Rotronic HygroFlex5-EX Humidity Temperature Transmitter
FAQs
Q: How should I connect the device for the power supply?
A: Connect the device to a power supply of +20V to +28V DC for both humidity and temperature measurements.
Q: Can I directly connect the service interface to a USB port?
A: No, always use a service cable (AC3006) to connect the service interface to a PC running the Rotronic HygroSoft software.
OVERVIEW
The HygroFlex5-EX is a humidity/temperature transmitter for fixed installation mounting in applications that require high measurement accuracy. The transmitters are compatible with all Rotronic ATEX sensors from the AirChip 3000 series. Standard sensors must not be used. The op-erating temperature range of the electronics is limited to -40…60 °C (-10…60 °C with optional LCD display).
Further information can be found at ProcessSensing.com or rotronic.com, or scan the QR code to access the Rotronic online manual with further explanations.
COMMISSIONING
HygroFlex5-EX (2-wire circuit, loop-powered): 10…28 VDC depending on the depending on the loads connected to the outputs. The minimum supply voltage can be determined as follows: V min = 10 V + (0.02 A x load*) *load resistance in ohms. For the maximum load of 500 Ω, the minimum supply voltage is 10 V + (0.02 A x 500 Ω ) = 20 VDC. If both output circuits are closed, the maximum current consumption is consumption is 40 mA during operation. The device must be correctly closed during operation to ensure explosion protection.
GROUNDING
STARTING THE DEVICE
The device needs approx. 1 minute for the entire start-up process. After approx. 20 seconds, “Please wait” appears on the display. During this time, both analog signals increase to approx. 21 mA. The device then starts operation and the analogue outputs are set to the corresponding measured value after the first measuring interval.
SERVICE CONNECTOR
The service connector (UART interface with a mini-USB connector) ena-bles the HygroFlex5-EX to be connected to a PC running the Rotronic Hy-groSoft software. A service cable is required. See chapter “Maintenance” for the location of the service connector and the type of service cable.
WARNING:
The service interface is a UART interface with a mini-USB connector. Do not connect the service interface directly to a USB port, but only via service cable AC3006!
The service interface is located inside the device. To access it, the device cover must be removed after loosening the 4 screws. The device must not be located in an explosive zone during service work!
ELECTRICAL SCHEME
VERDRAHTUNG
According to EN60079-14 in accordance with ATEX, no SELV device is required for the power supply (SELV supply = with limited transients). The measuring transducer can also be operated with only one closed measuring loop.
Connection terminals | ||
Permitted conductor cross-section (rigid) | Permitted conductor cross-section (flexible) | Stripping length |
0.2 mm²…4 mm² | 0.2 mm²…2.5 mm² | 10 mm |
Clamps | Description |
K1: CH1- | Relative humidity output 1 (4…20 mA) |
K1: CH1+ | Power supply: 10…28 VDC |
K2: CH2- | Temperature output 2 (4…20 mA) |
K2: CH2+ | Power supply: 10…28 VDC |
Cable gland |
Clamping range
4.5 – 10 mm (nicht armiertes Kabel) |
Tightening torque
10 Nm |
PERIODIC CHECK (CALIBRATION) OF THE SENSOR
The PT-100 RTD temperature sensor used in the probe and the electronics are very stable over the long term and generally require no further calibration after the initial factory adjustment. The long-term stability of the hygrometer humidity sensor from Rotronic is generally better than 1%rh per year. For maximum accuracy, the calibration of the sensor should be checked every 6 to 12 months. Applications where the sensor is exposed to significant contamination may require more frequent checks.
Note: The HygroClip 2 sensor cannot be adjusted when connected to the HygroFlex5-EX transmitter.
REPAIR
Do not repair defective appliances yourself. The appliance must be sent to the manufacturer’s service center for repair.
REPLACEMENT FILTER
Steel sintered filter: SP-FN15
POWER SUPPLY
There are two separate connections for the humidity and temperature sensors. The measuring device connections include the power supply and sensor signal. The supply voltages of the two sensors may be different because they are decoupled via two internal diodes. The device can also be operated with only one loop.
Device input voltage
- USupply = 20 V…28VDC [24 V +/- 15%]
Maximum Power
- ISupply max.= 50 mA [sum of both input currents]
Resistance
- RM = 0…500 Ω [measuring voltage 0V…10V]
Ambient temperature range
- Measuring sensor: TA = [- 40 °C…+ 85 °C]
- Transmitter with LCD: TA = [- 10 °C…+ 60 °C]
- Transmitter without LCD: TA = [- 40 °C…+ 60 °C]
The usual ATEX standards only apply for normal temperature [-20 °C…+40 °C] and for a pressure range of [0.8 bar…1.1 bar]. The extended temperature range must be noted on the rating plate.
INPUT PROTECTION CIRCUIT
The device is protected against reverse polarity by two diodes. In addition, two Z-transit diodes protect against static and transient overvoltages. These measures are not required by ATEX. However, they have been implemented as supplementary protective measures that are easy to realise.
- UM = 28 V DC
Supply circuit sensor
- Maximum output voltage: UO ≤ 6.6 V
- Maximum output current: IO ≤ 82 mA
- Maximum output power: PO ≤ 485 mW
- Capacity: CO = 22 μF
- Inductance: Lo = 2 μH
- HC2-LDPxxx-EX
Sensor circuit
- Maximum input voltage: UI ≤ 6.6 V
- Maximum input current: II ≤ 82 mA
- Maximum input power: PI ≤ 485 mW
- Internal capacitance: CI = 19 μF
- Internal inductance: LI = 0
- All other sensors
Sensor circuit
- Maximum input voltage: UI ≤ 6.6 V
- Maximum input current: II ≤ 82 mA
- Maximum input power: PI ≤ 485 mW
- Internal capacitance: CI = 15 μF
- Internal inductance: LI = 0
Type of ignition protection intrinsic safety Ex ia IIC.
ATEX-DATA
Measuring probe | For operating temperature Tamb = [-40…+60 °C] |
![]() |
Zone 0, gas, intrinsically safe,
temp. 100°C |
![]() |
Zone 20, dust, intrinsically safe,
Temp. 80°C |
IP66 | IP protection 66 |
or | For operating temperature Tamb = [-40…+85 °C] |
![]() |
Zone 0, gas, intrinsically safe,
temp. 130 °C |
![]() |
Zone 20, dust, intrinsically safe,
Temp. 110 °C |
IP66 | IP protection 66 |
(1/2 – 1: Zone 0 and 2: Zone 1 suitable for installation in zone partition wall) (Ga – very high protection level (zone 0), Gb – high protection level (zone 1)) (Da – very high protection level (zone 0), Db – high protection level (zone 1)) (Ga/Gb, Da/Db suitable for installation in zone partition wall) |
Transmitter |
For operating temperature Tamb =
[-40…+60 °C] (without LCD display) For operating temperature Tamb = [-10…+60 °C] (with LCD display) |
![]() |
Zone 1, 2, gas, (intrinsically safe),
Temp. 100 °C |
![]() |
Zone 21, 22, dust, (intrinsically safe),
Temp. 80 °C |
IP66 | IP protection 66 |
(2(1) – 2: Zone 1, (1): contains circuits that may be routed in Zone 0)
(Ex e mb [ia Ga] several types of protection: Ex-e, Ex-mb and output Ex-ia) |
Complete system |
![]() |
![]() |
NAMEPLATE INFORMATION
Manufacturer Company | Rotronic AG, CH-8303 Bassersdorf |
Type Description | HF520-EX |
Series number | < Number > |
Measurement probe | ![]()
|
Measuring transmitter |
![]()
IP66 |
Certification organization | Eurofins, Fehraltorf (CH) |
Certificate no. | SEV 14 ATEX 0107
IECEx SEV 14.0002 CML 22UKEX3190 |
Date | 09.09.2024 |
Operating temperature range | Tamb = [-10 °C…+60 °C] with LCD
Tamb = [-40 °C…+60 °C] without LCD |
In | [20 VDC…28 VDC], 2 W |
Out | [4 mA…20 mA], 2-Wire Current Loop |
Symbols |
![]() |
MORE INFO