resideo-LOGO

resideo VISTAHTKVR-V-002-V0 Gateway Module

resideo-VISTAHTKVR-V-002-V0-Gateway-Module-PRODUCT

FAQs

  • Q: How many VISTAHTKVR-V modules does the VISTAH3 Control panel support?
    • A: The VISTAH3 Control panel supports up to 4 VISTAHTKVR-V modules, one for each partition.

GENERAL INFORMATION

The VISTAHTKVR-V Gateway module allows compatibility for Resideo V-Plex devices to operate on compatible First Alert Pro VISTA Hybrid Control Panels. It connects to the control’s iBus bus wiring terminals and is mounted remotely. The VISTAH3 Control panel support 4 VISTAHTKVR-V modules, one for each partition.

Maximum Number of Devices

  • 96 total devices supported.
  • 172 number of input zones
  • 52 relay modules (4101SNs)

IMPORTANT NOTE:

PROHVPLEX module only supports serial mode! Modules that support zone assignment and serial must be set for serial mode. Refer to the module’s installation instructions for more information.

V-Plex Sensor Compatibility

Sensor Description Sensor Description
269SN Hold up Switch 4939SN Surface Mount Contact
4101SN 1 Zone + 1 Relay 4959SN OHD Contact
4190SN 2-zone Expander 5193SD Smoke Detector
4191SN Recessed Contact 5193SDT Smoke Detector
4193SN 1 zone Expander DT8050A-SN Dual Tec PIR, w/Anti-Mask
4193SNP 1 zone Expander DT7500SN Dual-Tec PIR
4208SN 8 Zone Expander FG1625SN Glass Break Detector
4208SNF 8 Zn Exp. w/Class A IS2500SN V-Plex/Sim Dual Tech
4208U* 8 Zone Expander IS3050A-SN Motion Detector
4209U* 4, 2-Wire Smoke Zn VPLEX-VSI V-Plex Short Isolator

INSTALLATION

  • The module has two built-in tampers (front and rear), allowing it to detect and report the removal of its cover and/or the removal from the wall to the control panel.
  • Communication with the module is supervised. If the wiring is cut, a supervision or alarm signal will result, indicating that this module (and possibly other devices connected to the iBus wiring) has become inoperative.

MOUNTING

  1. Push the button on top of the module to open the cover.resideo-VISTAHTKVR-V-002-V0-Gateway-Module-FIG (1)
  2. For surface installations, using the 5 provided screws [2a], mount the back case to the wall using the designated mounting holes and back case tamper [2b].resideo-VISTAHTKVR-V-002-V0-Gateway-Module-FIG (2)
    • 2b. For gang box installations, carefully remove PCB and using the 5 provided screws [2a], mount the back case to the wall using the designated mounting holes and back case tamper [2b].resideo-VISTAHTKVR-V-002-V0-Gateway-Module-FIG (3)
  3. Using best practices, choose the appropriate knockout [3a] to feed the wires through (or use the hole provided in the back of the box [3b]).
    • IMPORTANT:
    • Damage to the product can occur if incorrectly wired. See a summary of connections for proper wiring.resideo-VISTAHTKVR-V-002-V0-Gateway-Module-FIG (4)
  4. Rotate the cover and snap it into place [4a], secure it with provided lock screw [4b].resideo-VISTAHTKVR-V-002-V0-Gateway-Module-FIG (5)

SUMMARY OF CONNECTIONS

iBus Input V-Plex Connections
1 Red: Positive (+) 5 12V Positive (+)*
2 Black: Negative (-) 6 12V Negative (-)*
3 Yellow: iBus B 7 V-Plex Positive (+)
4 Green: iBus A 8 V-Plex Negative (-)
iBus Output  
9 Green: iBus A 13 LED
10 Yellow: iBus B 14 Tamper
11 Red: Positive (+)    
12 Black: Negative (-)    
* This AUX power can be used to connect to V-Plex devices that have 4 terminals on board (Power+, Power-, Loop+, Loop-) when current drawn from V-Plex Loop

exceed 128mA.

resideo-VISTAHTKVR-V-002-V0-Gateway-Module-FIG (6)

iBUS WIRING LIMITATIONS

Wire Gauge (AWG) Total Current of All Devices Connected to a Single Wire Run
50mA or less 100mA 300mA 500mA 600mA
#22 700ft (213m) 350ft (107m) 120ft (37m) 70ft (21m) 60ft (19m)
#20 1200ft (366m) 600ft (183m) 200ft (61m) 120ft (37m) 100ft (30m)
#18 1900ft (579m) 950ft (290m) 320ft (98m) 190ft (58m) 160ft (49m)
#16 3000ft (914m) 1500ft (457m) 500ft (152m) 300ft (91m) 260ft (76m)

NOTE: The length of all wire runs for all partitions combined must not exceed 3000 feet (914m) when unshielded quad conductor cable is used or 1500 feet (457m) if shielded cable is used.

CONNECTIONS AND SETTINGS

  1. Power should be disconnected before proceeding.
  2. Be sure to mount the module before making any wire connections.

Using the summary of connections above; using best practices, connect to the control’s iBus terminals via a 4-position terminal block (input). After powering up, enroll the module through the panel’s iBus programming. Refer to the module’s installation instructions for specific information on enabling and configuring each V-Plex device. After enrollment, the module is configurable via the control panel programming or the app.

ENROLLMENT

  1. The unique identifier defined on the attached label is required.
  2. The control panel automatically assigns each V-Plex device to the next available zone or relay.
  3. Confirm and document each device and its assignments for multimodule installations to prevent confusion.

LED OPERATION

Color Indication Function
Green Slow Blink Module Firmware Updating
  Solid Normal Operation, iBus Online
Amber Fast Blink iBus Offline
  Solid System Trouble”

1. Tamper Fault

2. Power Overload

3. Relay Output Supervision Trouble

4. Device Supervision Trouble

N/A Off 1. No power or communication

2. Panel is in AC Loss mode

SPECIFICATIONS

  • Physical
    • Dimensions 6.93” W x 5.43” H x 1.99 D
    • (176mm x 138mm x 50.5mm)
  • Electrical
    • Input Voltage 12VDC nominal (10-14VDC)
    • Input Current 56mA
      • NOTE: This does not include powered devices using the AUX terminals or current of the V-Plex devices.
  • Environmental
    • Operating Temperature 32° – 122°F (0° – 50°C)
    • Operating Humidity 0 – 95% Relative Humidity

FCC

FEDERAL COMMUNICATIONS COMMISSION (FCC) & INDUSTRY CANADA (IC) STATEMENTS

The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User’s Manual. Unauthorized changes or modifications could void the user’s authority to operate the equipment.

CLASS B DIGITAL DEVICE STATEMENT

This equipment has been tested and found to comply with the limits for a Class B digital device, as defined by FCC Rules Part 15.105. The Class B Digital Device statement can be viewed at: https://customer.resideo.com/en-US/support/residential/codes-andstandards/ FCC15105/Pages/default.aspx

FCC / IC STATEMENT

This device complies with Part 15 of the FCC Rules, and Industry Canada’s license-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subsidiary of Resideo Technologies, Inc., 2 Corporate Center Drive., Melville, NY 11747, Ph: 516-577-2000

  • REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED, FOR DETAILS ON THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
  • For the latest warranty information, please go to: www.resideo.com
  • For technical support, call 1-800-645-7492, M-F 8:30 am to 5 pm EST.
  • For documentation, go to: www.resideo.com

This equipment should be installed in accordance with National Electrical Code, NFPA 70, Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540 and Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided with this  equipment

Canadian Installations

For Installation in Canada, wiring shall be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations; CAN/ULC S302, Standard for the Installation, Inspection and Testing of Intrusion Alarm Systems; and CAN/ULC S301, Standard for Signal Receiving Centre Intrusion Alarm Systems and Operations.

Warning: Owner’s instruction notice: ’Not to be removed by anyone except occupant’ This system must be checked by a qualified technician at least once every three (3) years.

Note: The product should not be disposed of with other household waste. Check for the nearest authorized collection centers or authorized recyclers. The correct disposal of end-of-life equipment will help prevent potential negative consequences for the environment and human health. Any attempt to reverse-engineer this device by decoding proprietary protocols, de-compiling firmware, or any similar actions is strictly prohibited.

Documents / Resources

resideo VISTAHTKVR-V-002-V0 Gateway Module [pdf] User Guide
VISTAHTKVR-V-002-V0, VISTAHTKVR-V-001-V0, VISTAHEXPHW-005-V0, VISTAHTKVR-V-002-V0 Gateway Module, VISTAHTKVR-V-002-V0, Gateway Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *