RenewAire MC Series Occupancy Sensor
Specifications
- Coverage floor space:
- Ceiling mount: 1500 sq. ft.
- Wall mount: 2500 sq. ft.
- Major motion area:
- Ceiling mount: 50 ft. diameter
- Wall mount: 68 x 50 ft.
OVERVIEW
SPECIFICATIONS
- Passive infared sensor
- Adjustable time-off delay to 30 minutes
- 24VAC power requirement
- Ceiling mount or directable wall mount
- Coverage floor space
- Ceiling mount: 1500 sq. ft.
- Wall mount: 2500 sq. ft.
- Major motion area
- Ceiling mount: 50 ft. diameter
- Wall mount: 68 x 50 ft.
Model | Volts | Current | Isolated Relay | Coverage Area | Suggested Mounting Height |
MC-C | 15-28VAC | 30 mA | 1 A @ 30 VAC/DC | 1500 sq. ft. | 8-10 ft. |
MC-W | 15-28VAC | 30 mA | 1 A @ 30 VAC/DC | 2500 sq. ft. | 8-10 ft. |
INSTALLATION
MC-C CEILING MOUNT
See the Leviton installation instructions provided in the original box for in-details or for more options.
MC-W WALL MOUNT
SETTINGS
ADJUSTMENT KNOBS
DIP SWITCHES
Switch | Switch Functions | Switch Settings | |
Bank A | OFF | ON | |
A1 | N/A | N/A | N/A |
A2 | N/A | N/A | N/A |
A3 | Manual Mode | Auto Adapting Enabled | Auto Adapting Disabled |
A4 | Walk-Through Disabled | Walk-Through Enabled | Walk-Through Disabled |
Bank B | OFF | ON | |
B1 | Override to ON | Auto Mode | Lights Forced ON |
B2 | Override to OFF | Auto Mode | Lights Forced OFF |
B3 | Test Mode | OFF ¢ ON ¢ OFF = Enter/Exit Test Mode | |
B4 | LEDs Disabled | LEDs Enabled | LEDs Disabled |
FIGURE 3.2.0 DIP SWITCH SETTING TABLE
ELECTRICAL
WIRING SCHEMATICS
In this example, Motion Control Occupancy Sensor turns Energy Recovery Ventilator (ERV) on at High speed when space is occupied.
In this example, Motion Control Occupancy Sensor turns the ERV on at speed set by potentiometers when space is occupied.
FACTORY ASSISTANCE
In the unlikely event that you need assistance from the factory for a specific issue, make sure that you have the information called for in the Unit Records page in the Owner Information section of the unit manual. The person you speak with at the factory will need that information to properly identify the unit and the installed options.
To contact RenewAire Customer Service:
- Call 800-627-4499
- Email: RenewAireSupport@RenewAire.com.
About RenewAire
- For over 40 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size. This is achieved while maximizing sustainability through our fifth-generation, static-plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and decrease operational expenses by minimizing equipment needs, resulting in significant energy savings. Our ERVs are competitively priced, simple to install, easy to use and maintain and have a quick payback. They also enjoy the industry’s best warranty with the lowest claims due to long-term reliability derived from innovative design practices, expert workmanship and Quick Response Manufacturing (QRM).
- As the pioneer of static-plate core technology in North America, RenewAire is the largest ERV producer in the USA. We’re committed to sustainable manufacturing and lessening our environmental footprint, and to that end our Waunakee, WI plant is 100% powered by wind turbines. The facility is also one of the few buildings worldwide to be LEED and Green Globes certified, as well as having achieved ENERGY STAR Building status. In 2010, RenewAire joined the Soler & Palau (S&P) Ventilation Group in order to provide direct access to the latest in energyefficient air-moving technologies. For more information, visit: renewaire.com.
Accessories
CONTACT INFORMATION
- 201 Raemisch Road
- Waunakee, WI
- 53597
- 800.627.4499
- RenewAire.com.
- 2025 © RenewAire LLC
- 138280_008_JAN25
FAQs
- Q: What is the suggested mounting height for the MC Series Occupancy Sensor?
- A: The suggested mounting height for both MC-C and MC-W models is between 8-10 feet.
- Q: What is the coverage area of the MC Series Occupancy Sensor?
- A: The coverage area is 1500 sq. ft. for the MC-C (Ceiling Mount) and 2500 sq. ft. for the MC-W (Wall Mount) model.
Documents / Resources
![]() |
RenewAire MC Series Occupancy Sensor [pdf] Instruction Manual MC-C, MC-W, MC Series Occupancy Sensor, MC Series, Occupancy Sensor, Sensor |