Raychem ECW-GF-DP Remote Display Panel

Product Information
Specifications
- Product Name: ECW-GF-DP
- Usage: Remote Display Panel for Raychem ECW-GF electronic controller
- Location: Nonhazardous Locations
- Distance: Can be located up to 328 feet (100 m) from the ECW-GF controller
Product Usage Instructions
Installation
The ECW-GF-DP remote display panel must be installed in conjunction with the ECW-GF controller. Follow the ECW-GF installation instructions (H58339) for detailed installation steps.
Tools Required
- Alpha Cat. No. 1298C or equivalent
Additional Materials Required
- Single duplex outlet cover plate with mounting screws
Operating Instructions
- Reset Test: Press the Reset button once the ground-fault error has been corrected.
- Ground-Fault Test: To test the ground-fault circuitry, press and hold the Test button. If the circuit passes, the Amber LED will blink rapidly.
- System Alarm: If the Red and Amber LEDs are blinking alternately, check the ECW-GF controller for the displayed error.
APPROVALS
Nonhazardous Locations

KIT CONTENTS
| Item | Qty | Description |
| A | 1 | Display panel with mounting screws |
| B | 1 | Single duplex outlet cover plate with mounting screws |
DESCRIPTION
The Raychem ECW-GF-DP is a remote display panel only for the Raychem ECW-GF electronic controller. The ECW-GF-DP allows remote monitoring of the heating cable system operation. The display has LED indicators which signal communication loss to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be located up to 328 feet (100 m) from the ECW-GF controller.
The ECW-GF-DP remote display panel must be installed in conjunction with the ECW-GF controller. Refer to the ECW-GF installation instructions (H58339) for further details.
For technical support, call Chemelex at 800-545-6258.
TOOLS REQUIRED
- Large slotted screwdriver
- Small slotted screwdriver
- Needle nose pliers
- Wire strippers
ADDITIONAL MATERIALS REQUIRED
- Duplex junction box
- 1/2 inch conduit
- Communication cable: 8 conductor 22 AWG shielded Alpha Cat. No. 1298C or equivalent

This unit should be installed, opened, and repaired by qualified personnel only.
To avoid shock hazard, do not open the front cover with power connected to the controller or any controlled equipment. Always open any circuit breakers and remove power from any high voltage electrical circuits installed in close proximity to or sharing an enclosure with the ECW-GF-DP prior to removing the enclosure cover plate. Read all instructions carefully before installation. Save this Installation and Operation Instruction for future reference.
SYSTEM ILLUSTRATION

- Install the ECW-GF-DP in an indoor dry location in a standard duplex junction box, up to 328 ft (100 m) from the ECW-GF.
- Route the communication cable through the 1/2-in entry.
- Communication cable type: 8 conductor 22 AWG shielded (Alpha 1298C or equivalent)

- Connect the cable to the controller and display in the following order:

- Prepare communication cable by stripping 1/4 in of insulation from each wire.
- Install wires according to Steps 4 and 5.

- Connect the communication cable to the ECW-GF controller.
- Terminate cable shield in the SH position on the J5 (Thermistor) terminal block.

- Connect the communication cable to the ECW-GF-DP.

- Stow wires and install ECW-GF-DP in duplex junction box.
- Secure with screws supplied.

- Install plastic cover over ECW-GF-DP Remote Display Panel.

- Multiple heating cable circuits may be monitored by mounting the ECW-GF-DP in multiplex boxes.

OPERATING INSTRUCTIONS

- Normal Operation
The Green LED shows that the display is connected to the ECW-GF controller and the controller is powered. - Communication Error
If the Green LED is blinking verify that the wiring to the display and controller are correct. - Ground-Fault Error
If the Red LED is blinking, the system has a ground-fault error. Check the ECW-GF controller for the error code on the display. Press the Reset button once the ground-fault error has been corrected. - Ground-Fault Test
To test the ground-fault circuitry, press and hold the Test button, if the circuit passes, the Amber LED will blink rapidly. - System Alarm
If the Red and Amber LEDs are blinking alternately, the heating cable system is in alarm. (Temperature sensor failure or high/low temperature alarm.) Check the ECW-GF controller for the displayed error.
North America
Tel +1 800 545 6258 info@chemelex.com
Latin America
Tel +1 713 868 4800 info@chemelex.com
Europe, Middle East, Africa, India
Tel +32 16 213 511 Fax +32 16 213 604 info@chemelex.com
Asia Pacific
Tel +86 21 2412 1688 infoAPAC@chemelex.com
©2025 Chemelex. All Chemelex marks and logos are owned or licensed by Chemelex Europe GmbH or its affiliates. All other trademarks are the property of their respective owners. Chemelex reserves the right to change specifications without notice.
Raychem-IM-H58410-ECWGFDP-EN-2504
FAQs
What should I do if the Red LED is blinking on the display?
If the Red LED is blinking, it indicates a ground-fault error. Check the ECW-GF controller for the error code and press the Reset button once the ground-fault error has been corrected.
How far can the ECW-GF-DP remote display panel be located from the ECW-GF controller?
The display panel can be located up to 328 feet (100 m) from the ECW-GF controller.