Raychem ECW-GF-DP Remote Display Panel
ព័ត៌មានអំពីផលិតផល
លក្ខណៈបច្ចេកទេស
- ឈ្មោះផលិតផល៖ ECW-GF-DP
- ការប្រើប្រាស់៖ Remote Display Panel for Raychem ECW-GF electronic controller
- ទីតាំង៖ ទីតាំងគ្មានគ្រោះថ្នាក់
- ចម្ងាយ៖ Can be located up to 328 feet (100 m) from the ECW-GF controller
ការណែនាំអំពីការប្រើប្រាស់ផលិតផល
ការដំឡើង
The ECW-GF-DP remote display panel must be installed in conjunction with the ECW-GF controller. Follow the ECW-GF installation instructions (H58339) for detailed installation steps.
ឧបករណ៍ដែលត្រូវការ
- Alpha Cat. No. 1298C or equivalent
សម្ភារៈបន្ថែមដែលត្រូវការ
- Single duplex outlet cover plate with mounting screws
សេចក្តីណែនាំប្រតិបត្តិការ
- Reset Test: Press the Reset button once the ground-fault error has been corrected.
- Ground-Fault Test: To test the ground-fault circuitry, press and hold the Test button. If the circuit passes, the Amber LED will blink rapidly.
- ប្រព័ន្ធរោទិ៍៖ If the Red and Amber LEDs are blinking alternately, check the ECW-GF controller for the displayed error.
ការអនុម័ត
ទីតាំងគ្មានគ្រោះថ្នាក់
KIT មាតិកា
ធាតុ | ចំនួន | ការពិពណ៌នា |
A | 1 | Display panel with mounting screws |
B | 1 | Single duplex outlet cover plate with mounting screws |
ការពិពណ៌នា
The Raychem ECW-GF-DP is a remote display panel only for the Raychem ECW-GF electronic controller. The ECW-GF-DP allows remote monitoring of the heating cable system operation. The display has LED indicators which signal communication loss to the controller, high/low temperature alarm, and temperature sensor failure. The display also has buttons to test and reset the ground-fault sensor. The display may be located up to 328 feet (100 m) from the ECW-GF controller.
The ECW-GF-DP remote display panel must be installed in conjunction with the ECW-GF controller. Refer to the ECW-GF installation instructions (H58339) for further details.
សម្រាប់ជំនួយផ្នែកបច្ចេកទេស សូមទូរស័ព្ទទៅ Chemelex នៅ ៨៦៦-៤៤៧-២១៩៤.
ឧបករណ៍ដែលត្រូវការ
- ទួណឺវីសរន្ធដោតធំ
- ទួណឺវីសខ្នាតតូច
- ម្ជុលច្រមុះ
- អ្នកកាត់ខ្សែ
សម្ភារៈបន្ថែមត្រូវបានទាមទារ
- Duplex junction box
- 1/2 inch conduit
- Communication cable: 8 conductor 22 AWG shielded Alpha Cat. No. 1298C or equivalent
This unit should be installed, opened, and repaired by qualified personnel only.
To avoid shock hazard, do not open the front cover with power connected to the controller or any controlled equipment. Always open any circuit breakers and remove power from any high voltage electrical circuits installed in close proximity to or sharing an enclosure with the ECW-GF-DP prior to removing the enclosure cover plate. Read all instructions carefully before installation. Save this Installation and Operation Instruction for future reference.
រូបភាពប្រព័ន្ធ
- Install the ECW-GF-DP in an indoor dry location in a standard duplex junction box, up to 328 ft (100 m) from the ECW-GF.
- Route the communication cable through the 1/2-in entry.
- Communication cable type: 8 conductor 22 AWG shielded (Alpha 1298C or equivalent)
- Connect the cable to the controller and display in the following order:
- Prepare communication cable by stripping 1/4 in of insulation from each wire.
- Install wires according to Steps 4 and 5.
- Connect the communication cable to the ECW-GF controller.
- Terminate cable shield in the SH position on the J5 (Thermistor) terminal block.
- Connect the communication cable to the ECW-GF-DP.
- Stow wires and install ECW-GF-DP in duplex junction box.
- ធានាដោយវីសដែលបានផ្គត់ផ្គង់។
- Install plastic cover over ECW-GF-DP Remote Display Panel.
- Multiple heating cable circuits may be monitored by mounting the ECW-GF-DP in multiplex boxes.
ការណែនាំអំពីប្រតិបត្តិការ
- ប្រតិបត្តិការធម្មតា។
The Green LED shows that the display is connected to the ECW-GF controller and the controller is powered. - កំហុសទំនាក់ទំនង
If the Green LED is blinking verify that the wiring to the display and controller are correct. - Ground-Fault Error
If the Red LED is blinking, the system has a ground-fault error. Check the ECW-GF controller for the error code on the display. Press the Reset button once the ground-fault error has been corrected. - Ground-Fault Test
To test the ground-fault circuitry, press and hold the Test button, if the circuit passes, the Amber LED will blink rapidly. - ប្រព័ន្ធរោទិ៍
If the Red and Amber LEDs are blinking alternately, the heating cable system is in alarm. (Temperature sensor failure or high/low temperature alarm.) Check the ECW-GF controller for the displayed error.
អាមេរិកខាងជើង
ទូរស័ព្ទ +1 800 545 6258 info@chemelex.com
អាមេរិកឡាទីន
ទូរស័ព្ទ +1 713 868 4800 info@chemelex.com
អឺរ៉ុបមជ្ឈឹមបូព៌ាអាហ្វ្រិកឥណ្ឌា
ទូរស័ព្ទ +32 16 213 511 ទូរសារ +32 16 213 604 info@chemelex.com
អាស៊ីប៉ាស៊ីហ្វិក
ទូរស័ព្ទ +86 21 2412 1688 infoAPAC@chemelex.com
© 2025 Chemelex ។ ស្លាកសញ្ញា និងស្លាកសញ្ញា Chemelex ទាំងអស់ត្រូវបានគ្រប់គ្រង ឬផ្តល់អាជ្ញាប័ណ្ណដោយ Chemelex Europe GmbH ឬសាខារបស់វា។ ពាណិជ្ជសញ្ញាផ្សេងទៀតទាំងអស់គឺជាកម្មសិទ្ធិរបស់ម្ចាស់រៀងៗខ្លួន។ Chemelex រក្សាសិទ្ធិក្នុងការផ្លាស់ប្តូរលក្ខណៈពិសេសដោយមិនចាំបាច់ជូនដំណឹងជាមុន។
Raychem-IM-H58410-ECWGFDP-EN-2504
សំណួរគេសួរញឹកញាប់
What should I do if the Red LED is blinking on the display?
If the Red LED is blinking, it indicates a ground-fault error. Check the ECW-GF controller for the error code and press the Reset button once the ground-fault error has been corrected.
How far can the ECW-GF-DP remote display panel be located from the ECW-GF controller?
The display panel can be located up to 328 feet (100 m) from the ECW-GF controller.
ឯកសារ/ធនធាន
![]() |
Raychem ECW-GF-DP Remote Display Panel [pdf] សៀវភៅណែនាំ ECW-GF-DP, ECW-GF-DP Remote Display Panel, Remote Display Panel, Display Panel |