QK-CE2204UNI Swing Gate Control Board

Product Specifications

  • Model: V25 HB2125
  • Origin: Made in Italy
  • Control Board: QK-CE2204UNI 230V
  • Power Supply: 230 VAC 50/60 HZ +- 10%
  • Operating Modes: Sliding, Swing, Dual Sliding

Product Usage Instructions

Gate Configuration

The control board has three operating modes for different gate
types: Sliding, Swing, or Dual Sliding. When powered up, the
display shows the operating mode set followed by the firmware
version.

Changing Control Board Mode

To change the control board mode:

  1. Hold down Button A or B until the display shows “DT”.
  2. Hold down Button C or D until the display blinks to show the
    operating mode you are setting.
  3. When the display stops blinking, the configuration has been
    set.

Checking Motor Direction

To check if the motors turn in the right direction:

  1. Ensure the phases cables of the motor/s are correctly
    connected.
  2. If one or both motors close instead of open, swap the
    connections.
  3. DIR2 = CLOSE is the default setting for swing gate
    operation.

Frequently Asked Questions (FAQ)

Q: Where can I find the complete user manual?

A: The complete user manual is available for download in the
reserved area of our website quikoitaly.com. Please refer to it for
more detailed information.

“`

® QK-CE2204UNI 230V CONTROL BOARD QUICK

MADE IN ITALY

V25 HB2125

SWING GATE CONFIGURATION GUIDE

TERMINAL BLOCK CONNECTION

GO

START

5t

STOP

E1

+24V

E2

+24V

1 2 3 4 5 6 7 8 9 101112

1 2 3 4 5 6 7 8 9 101112

E1 = GO

PE

PEDESTRIAN

E7 +24V

1 2 3 4 5 6 7 8 9 101112

E2 = 5t
FLASHING LAMP
1 2 3 4 5 6 7 8 9 101~11~2

QK-CE2204UNI 230V CONTROL BOARD

V25 HB2125

SWING GATE CONFIGURATION

The control board has three opera ng modes for different kinds of gate: SLIDING, SWING, or DUAL SLIDING. When powered up the display shows the opera ng mode set followed by the firmware version. The opera ng mode can also be viewed by selec ng DT parameter.

A

x5 SLIDING xb SWING

B C

xx DOUBLE SLIDING D

UP DOWN
YES NO

QUICK
GUIDE

®
MADE IN ITALY

BLACK

SIGNAL SCREEN
RED

E7 = PE
24 VDC OUTPUT
+24V -24V
1 2 3 4 5 6 7 8 9 101112

TA OPENING PHOTOCELLS

E4

+24V GND

1 2 3 4 5 6 7 8 9 101112

TA

RX

TX

E4 = TA

NC +

+

A MOTOR

First motor to open, last motor to close.

1314 15

COM

DIR1

DIR2

A

13

15

If one or both motors closes instead, swap

L8 = NO DIR1 = OPEN

24 VAC 20 W
230 VAC POWER SUPPLY

230 VAC 50/60 HZ +- 10%

19 G120

G2

on PCB

N

L

TD CLOSING PHOTOCELLS

E3

+24V GND

1 2 3 4 5 6 7 8 9 101112

Td

RX

TX

E3 = TD

NC +

+

B MOTOR

1617 18

COM

DIR1

DIR2

B

16

18

the phases cables of the motor/s that was closing.

DIR2 = CLOSE swing gate default

A 88
B

24 VAC

230 VAC
G2

C+ – D
E1 E2 E3 E4 E5 E6 E7 +24

+24 TEST – 24V

~~

FUSE 52A30V

230VAC

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A MOTOR B MOTOR 19 G1 20

NL

HOW TO CHANGE CONTROL BOARD MODE

Hold A er

down or keep pressing about one second, the

BUTTON A or B un l display shows display shows the current opening

DT. mode:

H5

HB

HH

Hold down BUTTON C or D of the control board. The display blinks showing the opera ng

mode you are se ng.

When the display stops blinking, the configura on has been set.

CHECKING IF THE MOTORS TURN IN THE RIGHT DIRECTION

Once all the connec ons have been done and the system is ready to start, before se ng the system it is important to check that the motors turn in the right direc on. To do that: 1 Power supply the control board and check that the display shows Hb 21 25 2 Remove electricity. 3 Unlock both motors and manually put the leafs in the middle. 4 Give electricity. 5 Give a first start impulse to the system with remote control or push – bu on. 6 Make sure that both motors open. 7 If one or both motors closes instead, swap the phases cables of the motor/s that was closing. 8 Once you have swapped motor/s phases cables, repeat the procedure above and make sure that now both motors open at first start signal a er giving electricity. 9 The system is now ready for setup.

QK-CE2204UNI ®
MADE IN ITALY

V25 HB2125

XB 230V CONTROL BOARD SWING GATE CONFIGURATION

QUICK GUIDE

®
MADE IN ITALY

MENU

xb default

A1 14

A2 7.0

A3 0.8

A4 06

A5 06

MOTOR A SETTING
Standard Working me Slowdown working me Start up me Displacement me on closure Standard force

IMPORTANT NOTICE: when you see this symbol please refer to the complete user manual for more details. The complete user manual is available for download in the reserved area of our website quikoitaly.com

MENU

xb default

r0

r1

A6 08 A7 no A8 No aa no

Slowdown force
C D from 00 to 99 to no Standard oblstacle detec on threshold. During opening, for standard working me, the display shows motor A stress. C D from 00 to 99 to no Slowdown oblstacle detec on threshold. During opening, for slowdown working me, the display shows motor A stress.
Final release: motor A open for “0. aa” sec at the end of closing to be er meet european safety standards. It works with obstacle detec on only.

MENU

xb default

f0 10

f1 07

f2 0.0

f3 0.0

f4 No

f5 01

FUNCTIONS
Automa c closure me. To disable hold down C bu on un l display shows 5t Pedestrian working me Kick-back func on during closing. It can be useful when an electric-lock is installed. Pre-blinking me
Kick-back func on during opening. It can be useful when an electric-lock is installed. Logic: STANDARD 01 COMMUNITY 02 STEP-BY-STEP 03

R2 R3 R4

MENU

xb default

b1 14

b2 7.0

b3 0.8

b4 03

b5 06

b6 08

b7 no

b8 No

MOTOR B SETTING
Standard Working me
Slowdown working me
Start up me
Displacement me on closure
Standard force
Slowdown force C D from 00 to 99 to no Standard oblstacle detec on threshold. During opening, for standard working me, the display shows motor B stress. C D from 00 to 99 to no Slowdown oblstacle detec on threshold. During opening, for slowdown working me, the display shows motor B stress.

f7 5.0 f8 No l0 no
l1 no l5 no l6
l7 00 l8 no
t1 no t2 51 o1 07
o2 13

Fast closure delay

Safety devices as sliding

Electric lock me from no (disabled) to 99 seconds. Cold winter func on It is useful in countries where the winter is extremely cold. Assistance request from cycle counter

Work cycles counter Flashing lamp opera ng mode Swap motors direc on

0 = FLASHING LAMP 1 = FIXED LAMP

Photocells test

Motors thermal protec on test 51 = ENABLE

Output 1 func on Output 2 func on

QK-RELAY *op onal
These func ons are useful when output expansions are used.

MENU

xb default

WORKING TIME PROGRAMMING

P2

2 motors working me programming

P6

Obstacle detec on threshold programming

MENU

xb default

CONTROL BOARD MODE

MENU

xb default

RB 01

RADIO SELECTION
Internal radio 01 External radio module 02

ON PCB QK-MODRAL4 *op onal

MENU

xb default

t=

r=

e=

LOGS
Errors log
Radio log
Input log

R5

MENU

xb default

r6 PO

r7 PC

r8 el

MENU

xb default

e1 go

e2 no

e3 no

e4 no

e5 op

e6 cL

e7 pe

D0 DT

Restore factory se ng selected by dt

CD

Change control board mode and set its factory se ng.

MENU
TA

SAFETY DEVICE DISPLAY REPORT Opening photocells

MENU
GO PE FG

START & SERVICE COMMAND DISPLAY REPORT Start / Pedestrian / Fast Closure

MENU
9A 9b 7A 7b 1t

TEST & GATE FUNCTION DISPLAY REPORT Motor A/B is in thermal protec on Motor A/B has detected an obstacle Photocells test error

TD TC Fx OO CC

Closing photocells mode 2/1 Opening + Closing photocells Opening / closing 8K2 Sa y Edge

OP Cl Po PC el do

Open only / Close only Open / Close Dead man Eletric lock Remote key dummy func on

5l

Assistance request func on

5T

Stop

Eo

Terminal block dummy func on

®

REMOTE KEY CONFIGURATIONS
Erase a remote control key: hold down C bu on on the selected code un l display turns off.
Save a remote control key as START: hold down a remote key. When the display shows __._ push down C bu on.
Save a remote control key as STOP: hold down a remote key. When the display shows __._ push down C bu on.
Save a remote control key as PEDESTRIAN START: hold down a remote key. When the display shows __._ push down C bu on.
Save a remote control key as FAST CLOSURE: hold down a remote key. When the display shows __._ push down C bu on.
Erase all remotes control keys: hold down C bu on un l display stops flashing 51

PROGRAMMABLE FUNCTIONS
The func on you can select is one of the following: op Open Only, Cl Close Only, PO Dead Man Open, PC Dead Man Close, el Electric lock, dO dummy output, rt radio range.

TERMINAL BLOCKS FUNCTIONS

1

Terminal block input 1

2

Terminal block input 2

3

Terminal block input 3

4

Terminal block input 4

5

Terminal block input 5

6

Terminal block input 6

7

Terminal block input 7

MENU
FC LC fa la ua xa uC xC ab 1x 2x 3x

LIMIT SWITCHES DISPLAY REPORT Motor A closing limit switch NC / NO Motor A opening limit switch NC / NO Motor B closing limit switch NC / NO Motor B opening limit switch NC / NO Motor A+B limit switches Motor A limit switches error Motor B limit switches error Motor A+B limit switches error

MADE IN ITALY