CAUTION
Before attempting calibration or commissioning of the DCM510 control system, water chemistry must be stable and within normal operating ranges of 7.2-7.8 pH, Free Chlorine at 1-3 ppm, and Total Alkalinity level at 80-120 ppm.

Calibrations

pH Single Point Calibration Example

Press theproMinent DCM510 Series Controller-1 button, then use the arrow buttons proMinent DCM510 Series Controller-2 to scroll to pH sensor E, then pressproMinent DCM510 Series Controller-3 .
Login with your password, if requested.
Next, take a water test and using theproMinent DCM510 Series Controller-4 buttons ,enter the results, one decimal place at a time followed by the SAVEproMinent DCM510 Series Controller-6 key. The LED screen should indicate Sensor

proMinent DCM510 Series Controller-5

Calibrated. Press NEXTproMinent DCM510 Series Controller-6 to continue to the next sensor to be calibrated, or press ESCproMinent DCM510 Series Controller-7 twice to return to the Home screen.

Chlorine/Bromine Sensor Single Point Calibration Example
NOTE: The ppm sensor CAL sequence was designed to optimize the DPDproMinent DCM510 Series Controller-6 calibration by remembering the sensor value when the DPD button is pressed.

Press theproMinent DCM510 Series Controller-1 button, then use theproMinent DCM510 Series Controller-2 buttons

proMinent DCM510 Series Controller-8

to scroll to desired sensor C:Free Chlorine, then pressproMinent DCM510 Series Controller-3 .

Login with your password, if requested.

proMinent DCM510 Series Controller-9

Next, remember to press the DPDproMinent DCM510 Series Controller-6 button when taking a DPD sample. This starts the calibration sequence the moment the DPDproMinent DCM510 Series Controller-6 button is pushed. A timer is also started for your reference. Then, once the water test is complete, using theproMinent DCM510 Series Controller-4 buttons, enter the results followed by the SAVEproMinent DCM510 Series Controller-6 key.

proMinent DCM510 Series Controller-10

The LED screen should then indicate Sensor Calibrated. Press NEXT proMinent DCM510 Series Controller-6to continue to the next sensor to be calibrated, or press ESCproMinent DCM510 Series Controller-7 twice to return to the Home screen.

proMinent DCM510 Series Controller-11

Adjusting Setpoints

NOTE: Water chemistry is controlled by the chemical feeders. In our controllers, the setpoint adjustments are therefore in the outputs to the feeders.

pH Setpoint Example:
For our default example, the pH feeder is assigned to Relay 1: Acid Feed. To change the pH set point, press theproMinent DCM510 Series Controller-26 button then use theproMinent DCM510 Series Controller-2 buttons to point to ►Adjust Setpoints. Press then use the buttons to point to the ►1: Acid Feed relay, then pressproMinent DCM510 Series Controller-3 .

proMinent DCM510 Series Controller-13

Login with your password if requested, then pressproMinent DCM510 Series Controller-3 .Use the arrow buttons to change the control setpoint, then pressproMinent DCM510 Series Controller-3 to save the new setpoint.

pH Deadband Example:
Deadband is the control overlap necessary to keep a feeder from turning on and off too rapidly or “chattering”.
By default, the pH feeder is assigned a deadband of 0.20 pH. This means the pH must deviate 0.20 pH above the setpoint before the acid feeder will turn on.
To change the pH deadband, press theproMinent DCM510 Series Controller-26 button then use theproMinent DCM510 Series Controller-2 buttons to point to ►Adjust Setpoints. PressproMinent DCM510 Series Controller-3 then use theproMinent DCM510 Series Controller-2 buttons to point to the ►1:Acid Feed relay, then press proMinent DCM510 Series Controller-3.

proMinent DCM510 Series Controller-14

Login with your password if requested, then pressproMinent DCM510 Series Controller-3 .
Press DEDBNDproMinent DCM510 Series Controller-6 and Use theproMinent DCM510 Series Controller-4  buttons to change the deadband, then pressproMinent DCM510 Series Controller-3 to save the new value. PressproMinent DCM510 Series Controller-31 to return to the Home screen.

Refer to the Operation and Installation manual for more information on the Deadband and its function.

Alarms

Alarm Info and Alarm Clear Example:

NOTE: All alarms in the DCM 510 series controllers are latching alarms by default which means once an alarm is triggered, it must be acknowledged or cleared. Alarm latching can be turned off in the DCM 510 I/O Setup menus.

proMinent DCM510 Series Controller-15

If an alarm is active with the red LED flashing,pressing ALARMS [F2] will show how many alarms there are on the top line, and specific alarms on the 2nd and 3rd lines.

proMinent DCM510 Series Controller-16

Press and hold INFOproMinent DCM510 Series Controller-17 and it will show detailed information on each alarm selected.

proMinent DCM510 Series Controller-17 proMinent DCM510 Series Controller-18

Pressing CLEARproMinent DCM510 Series Controller-19 will clear the selected alarm

proMinent DCM510 Series Controller-20

CLRALL proMinent DCM510 Series Controller-6 will clear all alarms, extinguish the flashing ALARM light and return to the Home screen.

START / STOP key

A quick way to force all chemical feed relays to the OFF position is to press theproMinent DCM510 Series Controller-21 button. The status LED in the upper right corner willproMinent DCM510 Series Controller-22 change to a steady RED as will all the active control output LEDs. To resume normal control on all outputs pressproMinent DCM510 Series Controller-21 again. A steady BLUE status LED indicates normal operation withproMinent DCM510 Series Controller-23 no alarms, and a flashing RED LED indicates normal opreration with an uncleared alarm.

proMinent DCM510 Series Controller-24

Feeder Prime/Force OFF

Forcing a relay or feeder ON, we call “Priming” because that is the most common use of this function. The relays can also be forced to STOP or Prime Cancel to be returned to normal operation from this menu.

proMinent DCM510 Series Controller-25

To Prime or Force ON a relay using the Prime function, from the Home screen, pressproMinent DCM510 Series Controller-26 thenproMinent DCM510 Series Controller-27 to select Prime, Force ON then pressproMinent DCM510 Series Controller-3 .

proMinent DCM510 Series Controller-28

Enter an operator level password or higher if required, then pressproMinent DCM510 Series Controller-3 .

NOTE: For safety, if the feeder selected is in an alarm timeout, or the flow switch or START/STOP button has stopped chemical feed, you will not be able to force the feeder ON until these conditions are changed.

Select the relay/feeder to force ON or OFF, then pressproMinent DCM510 Series Controller-3 .

proMinent DCM510 Series Controller-29

CAUTION: Forcing a feeder on for an extended time can be hazardous.

The default time on the Prime function is 5 minutes. Change the Prime timer duration if desired using theproMinent DCM510 Series Controller-4 keys, then press STARTproMinent DCM510 Series Controller-19 . Pressing CANCEL again cancels the Prime, and returns the relay to normal control. Pressing STOPproMinent DCM510 Series Controller-6forces the relay OFF until you “UNSTOP” the relay.

proMinent DCM510 Series Controller-30

ProMinent Fluid Controls, Inc.
136 Industry Drive
Pittsburgh, PA 15275
412.787.2484
www.prominent.us
Part Number 7750427 Rev.1 9/29/22
© 2022 ProMinent Fluid Controls, Inc. All Rights Reserved

Documents / Resources

proMinent DCM510 Series Controller [pdf] User Guide
DCM510 Series Controller, DCM510 Series, Controller, DCM510 Series Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *