WWP V3 MS Group Controller Wired Wall Pad Controller
“
Product Specifications:
- Model: WWP V3 MS_2024.V1
- Functions: Cooling, Dehumidification, Heating, Ventilation,
Auto Mode - Control: Wall pad interface
- Timer Functions: Timer-ON, Timer-OFF
- Special Functions: Sleep Mode, Swing Function, Screen Lock
Function
Product Usage Instructions:
Setting Up the Unit:
- Use a screwdriver to remove the screw on the bottom of the
unit. - Follow the wiring diagram to connect it to the FCU.
Operating the Wall Pad:
- To select a mode: Cooling, Dehumidification, Heating,
Ventilation, or Auto mode, press the corresponding button. - To change fan speed, press the speed setting button (0=Auto
speed, 1=Low speed, 2=Medium speed, 3=High speed).
Setting Timers:
- Press and hold for 5 seconds to set the current day of the
week. Use the arrows to change from Monday to Sunday. - Press and hold for 5 seconds, then short press once to set the
current time. Use arrows to change the time. - To set Timer ON function:
- Press and hold for 5 seconds, then short press twice. Use
arrows to set day of the week and time. - Press to turn Timer ON function on or off.
- Press and hold for 5 seconds, then short press twice. Use
- To set Timer OFF function:
- Press and hold for 5 seconds, then short press three times. Use
arrows to set day of the week and time. - Press to turn Timer OFF function on or off.
- Press and hold for 5 seconds, then short press three times. Use
Additional Functions:
- To set temperature unit, press for 6 times until U00
appears. - To lock/unlock the screen, press for 5 seconds.
- To activate/deactivate swing function, press for 5
seconds. - To activate/deactivate sleep mode, press for 5 seconds.
Selecting Unit Address:
- Press and hold for 5 seconds, then short press five times.
Press or to change the unit address (0 for all units or 1-32 for
specific units). - Once the unit(s) have been selected, operate the wall pad as
per the user instructions above.
Frequently Asked Questions (FAQ):
Q: How do I change the fan speed?
A: Press the fan speed setting button to cycle through Auto
speed, Low speed, Medium speed, and High speed options.
Q: How do I lock/unlock the screen?
A: Press and hold for 5 seconds to lock the screen. Repeat the
action to unlock it.
Q: How do I set the Timer functions?
A: Follow the instructions provided in the user manual to set
Timer-ON and Timer-OFF functions based on your desired
schedule.
“`
WWP V3 MS_2024.V1
Operation Guide
# Legend
#
S1 Monday
S16
S2 Tuesday
S17
S3 Wednesday
S18
S4 Thursday
S19
S5 Friday
S20
S6 Saturday
S21
S7 Sunday
S22
S8 Timer-ON
S23
S9 Timer-ON time S24 (When Timer-ON is off: Current time)
S10 Timer-OFF
S25
S11 Timer-OFF time S26
S12 Cooling Mode
S27
S13 Dehumidification S28
S14 Heating Mode S29
S15 Ventilation Mode S30
Legend
Auto Mode Sleep mode Swing mode LED lock Setting Temperature Room Temperature
Data Display
Fahrenheit degree Celsius degree Fan 0-Auto / 1-Low 2 Medium / 3 – High.
connect@polarglobalgroup.com www.polaraircs.com
# Legend
S31 Unit address S32 Unit No. / Error code S33 Weekly timer S34 S35 S36 S37 S38 On/Off Button S39 Mode setting
S38 On/Off Button S39 Mode setting S40 Fan speed setting S41 Parameter setting S42 Up S43 Down
1
WWP V3 MS_2024.V1
connect@polarglobalgroup.com
www.polaraircs.com
2
Use screwdriver to remove the screw on the bottom
WWP V3 MS_2024.V1
Follow the wiring diagram to connect it to the FCU
connect@polarglobalgroup.com
www.polaraircs.com
3
WWP V3 MS_2024.V1
[S38] ON/OFF Button Press the button to turn on. Press it again to turn it off [S39] MODE ButtonWith the wall pad turned on, press a) Cooling b) Dehumidification c) Heating
to select sequentially: d) Ventilation or, e) Auto mode
[S40] FAN SPEED ButtonPress to change from: a) 0=Auto speed b) 1=Low speed
c) 2=Medium speed d) 3=High speed
[S41] TIMER PARAMETER Setting1. Press for 5 seconds to set the current day of the week, and press
or
to change from
Monday to Sunday
2. Press for 5 seconds, then short press it once to set the current time. Press
or
to
change the time
3. Press for 5 seconds, then short press it twice to set the “Timer ON” function. The “Timer ON” function is used to for setting up a specific time or date for the unit to be turned on.
3.1. Press 3.2. Press
to set the day of the week (from Monday to Sunday)
or
to change the “Timer ON” time
3.3. Press to turn the “Timer ON” function on or off, and you’ll notice that S8 (Timer ON Led) appears or disappears
4. Press for 5 seconds, then short press it 3 times to set “Timer OFF” function. The “Timer OFF” function is used to for setting up a specific time or date for the unit to be turned off.
4.1. Press 4.2. Press
to set the day of the week (from Monday to Sunday)
or
to change the “Timer OFF” time
4.3. Press to turn the “Timer OFF” function on or off, and you’ll notice that S10 (Timer OFF Led) appears or disappears
connect@polarglobalgroup.com
www.polaraircs.com
4
WWP V3 MS_2024.V1
[S41] CHANGE DEGREE PARAMETER Setting1. Press for 5 seconds, then short press
2. Press
or
to change:
a. 0 = Degree ºC
b. 1 = Degree ºF
for 6 times to set temperature unit. U00 appear.
SCREEN LOCK FUNCTION
1) Press
for 5 seconds, S19 appears, and screen is locked.
2) Press
for 5 seconds again; S19 disappears, and the screen is unlocked.
SWING FUNCTION
1) Press
for 5 seconds, S18 appears, and the swing is ON.
2) Press
for 5 seconds again; S18 disappears, and the swing is OFF.
SLEEP MODE 1) Press for 5 seconds, S17 appears, and sleep mode is ON 2) Press for 5 seconds again, S17 disappears, and sleep mode is OFF
To select the address of the unit to be controlled:
1) Press for 5 seconds, then short press for 5 times, press
or
address.
a) 0 is used to control all units
b) From 1 – 32 is used to control the specific address unit
to change the unit
2) Once the unit or all the units have been selected, operate the wall pad as described in the user instructions above.
IMPORTANT NOTE:
The WWP3-MS is unable to change the unit address. If you need to do so, please use the standard WWP3, via BMS changing the Modbus parameter 300004 or use one that’s preconfigured from the factory.
connect@polarglobalgroup.com
www.polaraircs.com
5
WWP V3 MS_2024.V1
Error Description
Room temperature sensor error
Indoor coil sensor 1 failure
Indoor coil sensor 2 failure
Float switch error
Indoor coil lowtemperature protection Indoor coil over-heat protection Filter switch protection
Code Reason
Solution
1. Check if Tr plug is connected or
Room sensor unplugged not.
E1 or damaged.
2. Check if sensor’s resistance is
correct or not.
1. Check if Ti1 plug is connected or
E2
Ti1 sensor unplugged or not.
damaged.
2. Check if sensor’s resistance is
correct or not.
1. Check if Ti2 plug is connected or
E3
Ti2 sensor unplugged or not.
damaged.
2. Check if sensor’s resistance is
correct or not.
1. Check if the condensate water pipe
E4
The float switch is opened.
is connected or not. 2. Check if the pump is functioning or
not.
E5 water temp. < 3 ºC.
Check the water temperature.
E6 Water temp. > 70 ºC.
Check the water temperature
E7 Filter Switch is open.
Replace or clean filter.
Electric Heater failure EC motor failure (CN4)
Only for units with EH. E8 EH safety switch is
opened.
E9 No EC motor feedback
1. Change fan speed to high. 2. Replace the damaged EH safety switch. 1. Check Modbus setting.
2. Check the EC motor.
EC motor failure (CN5)
Motor qty setting error (S6 PCB) 1 Anti-frozen protection
Indoor coil sensor 3 failure (S6 PCB) 1
E10 No EC motor feedback
1. Check Modbus setting. 2. Check the EC motor.
E11 Motor Qty setting error 1: check Modbus setting
E12
When the unit is on standby, Tr < 2ºC.
1. Turn on unit to keep Tr high than 5ºC
1. Check if Ti3 plug is connected or
E13
Ti3 sensor unplugged or damaged.
not. 2. Check if sensor’s resistance is
correct or not.
1 Only aplicable to S6 PCB Models
connect@polarglobalgroup.com
www.polaraircs.com
6
WWP V3 MS_2024.V1
Error Description
Indoor coil sensor 4 failure (S6 PCB) 2
PM2.5 sensor failure (S6 PCB) 2
AQI sensor failure (S6 PCB) 2
Wired Wall Pad failure
Code Reason
Solution
1. Check if Ti4 plug is connected or
E14
Ti4 sensor unplugged or damaged.
not. 2. Check if the sensor’s resistance is
correct or not.
1. Check if PM2.5 plug is connected
E15
PM2.5 sensor unplugged or not.
or damaged.
2. Check if the sensor’s resistance is
correct or not.
1. Check if AQI plug is connected or
E16
AQI sensor unplugged or not.
damaged.
2. Check if the sensor’s resistance is
correct or not.
WWP unplugged or not
E17 well
Check plugs
connect@polarglobalgroup.com
www.polaraircs.com
7
Documents / Resources
![]() |
POLARAIR WWP V3 MS Group Controller Wired Wall Pad Controller [pdf] Installation Guide WWP V3 MS, WWP V3 MS Group Controller Wired Wall Pad Controller, Group Controller Wired Wall Pad Controller, Controller Wired Wall Pad Controller, Wired Wall Pad Controller, Wall Pad Controller, Controller |