Pepperl Fuchs LB3005A2 HART Transmitter Power Supply Input Isolator Instruction Manual
HART Transmitter Power Supply, Input Isolator LB3005A2
- 4-channel
- Power supply for 2-wire transmitters with 4 mA … 20 mA
- Installation in Zone 2 or safe area
- Supply circuit 15 V (20 mA)
- Input from active signals of 4-wire transmitters
- HART communication via field bus or service bus
- Simulation mode for service operations (forcing)
- Line fault detection (LFD): one LED per channel
- Permanently self-monitoring
- Module can be exchanged under voltage
Function
The transmitter power supply feeds 2-wire transmitters.
Active signals from separately powered field devices and 4-wire transmitters can be connected. Open and short circuit line faults are detected.
The inputs are galvanically isolated from the bus and the power supply.
Connection
Technical Data
Slots | |
Occupied slots | 2 |
Supply | |
Connection | backplane |
Rated voltage | Ur 12 V DC , only in connection with the power supplies LB9*** |
Power dissipation | 1.5 W |
Power consumption | 2.7 W |
Internal bus | |
Connection | backplane bus |
Interface | manufacturer-specific bus to standard com unit |
Analog input | |
Number of channels | 4 |
Suitable field devices | |
Field device | pressure converter |
Field device [2] | flow converter |
Field device [3] | level converter |
Field device [4] | Temperature Converter |
Field device interface | |
Connection | 2-wire transmitter |
Connection (2) | 3-wire transmitte |
Connection(3) | 4-wire transmitter |
Connection | 2-wire transmitter (HART):Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-3-wire transmitter: Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-4-wire transmitter (powered externally):Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16 |
Transmitter supply voltage | min. 15 V at 20 mA ; 21.5 V at 4 mA |
Input resistance | 15 Ω |
Conversion time | max. 100 ms |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration too |
Short-circuit | factory setting: > 22 mA configurable between 0 … 26 mA |
Open-circuit | actory setting: < 1 mA configurable between 0 … 26 mA |
HART communication | yes |
HART secondary variable | No |
Transfer characteristics | |
Deviation | |
After calibration | 0.1 % of the signal range at 20 °C (68 °F) |
Influence of ambient temperature | 0.1 %/10 K of the signal range |
Resolution | 12 Bit (0 … 26 mA) |
Refresh time | 100 ms |
ndicators/settings | |
LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) |
Coding | optional mechanical coding via front socket |
Directive conformity | |
Electromagnetic compatibility | |
Directive 2014/30/EU | EN 61326-1:2013 |
Conformity | |
Electromagnetic compatibility | NE 21:2007 |
Degree of protectio | IEC 60529:2000 |
Environmental test | EN 60068-2-14:2009 |
Shock resistance | EN 60068-2-27:2009 |
Vibration resistance | EN 60068-2-6:2008 |
Damaging gas | EN 60068-2-42:2003 |
Relative humidity | EN 60068-2-78:2001 |
Ambient conditions | |
Ambient temperature | -40 … 60 °C (-40 … 140 °F) , 70 °C (non-Ex) |
Storage temperature | 40 … 85 °C (-40 … 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications | |
Degree of protection | IP20 when mounted on backplane |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 … 1.5 mm2 ) or screw terminals (0.08 … 1.5 mm2 ) |
Mass | approx. 150 g |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
Data for application in connection with hazardous areas | |
Certificate | BVS 12 ATEX E 105 X |
Marking | 1 II 3 G Ex nA [ic] IIC T4 Gc |
Galvanic isolation | |
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
Directive conformity | |
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 |
International approvals | |
ATEX approval | BVS 12 ATEX E 105 X |
IECEx approval | BVS 12.0055X |
Approved for | Ex nA [ic] IIC T4 Gc |
General information | |
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Assembly
Front view
Documents / Resources
![]() |
Pepperl Fuchs LB3005A2 HART Transmitter Power Supply Input Isolator [pdf] Instruction Manual LB3005A2, 254700, LB3005A2 HART Transmitter Power Supply Input Isolator, HART Transmitter Power Supply Input Isolator, Power Supply Input Isolator, Input Isolator |