Pepperl Fuchs LB3005A2 HART Transmitter Power Supply Input Isolator Instruction Manual
Pepperl Fuchs LB3005A2 HART Transmitter Power Supply Input Isolator

HART Transmitter Power Supply, Input Isolator LB3005A2

  • 4-channel
  • Power supply for 2-wire transmitters with 4 mA … 20 mA
  • Installation in Zone 2 or safe area
  • Supply circuit 15 V (20 mA)
  • Input from active signals of 4-wire transmitters
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD): one LED per channel
  • Permanently self-monitoring
  • Module can be exchanged under voltage

Function

The transmitter power supply feeds 2-wire transmitters.
Active signals from separately powered field devices and 4-wire transmitters can be connected. Open and short circuit line faults are detected.
The inputs are galvanically isolated from the bus and the power supply.

Connection

Connection

Technical Data

Slots
Occupied slots 2
Supply
Connection backplane
Rated voltage Ur 12 V DC , only in connection with the power supplies LB9***
Power dissipation 1.5 W
Power consumption 2.7 W
Internal bus
Connection backplane bus
Interface manufacturer-specific bus to standard com unit
Analog input
Number of channels 4
Suitable field devices
Field device pressure converter
Field device [2] flow converter
Field device [3] level converter
Field device [4] Temperature Converter
Field device interface
Connection 2-wire transmitter
Connection (2) 3-wire transmitte
Connection(3) 4-wire transmitter
Connection 2-wire transmitter (HART):Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-3-wire transmitter: Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-4-wire transmitter (powered externally):Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16
Transmitter supply voltage min. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance 15 Ω
Conversion time max. 100 ms
Line fault detection can be switched on/off for each channel via configuration tool , configurable via configuration too
Short-circuit factory setting: > 22 mA configurable between 0 … 26 mA
Open-circuit actory setting: < 1 mA configurable between 0 … 26 mA
HART communication yes
HART secondary variable No
Transfer characteristics
Deviation
After calibration 0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature 0.1 %/10 K of the signal range
Resolution 12 Bit (0 … 26 mA)
Refresh time 100 ms
ndicators/settings
LED indication Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit)
Coding optional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Conformity
Electromagnetic compatibility NE 21:2007
Degree of protectio IEC 60529:2000
Environmental test EN 60068-2-14:2009
Shock resistance EN 60068-2-27:2009
Vibration resistance EN 60068-2-6:2008
Damaging gas EN 60068-2-42:2003
Relative humidity EN 60068-2-78:2001
Ambient conditions
Ambient temperature -40 … 60 °C (-40 … 140 °F) , 70 °C (non-Ex)
Storage temperature 40 … 85 °C (-40 … 185 °F)
Relative humidity 95 % non-condensing
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protection IP20 when mounted on backplane
Connection removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 … 1.5 mm2 ) or screw terminals (0.08 … 1.5 mm2 )
Mass approx. 150 g
Dimensions 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
Certificate BVS 12 ATEX E 105 X
Marking 1 II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation
Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010
International approvals
ATEX approval BVS 12 ATEX E 105 X
IECEx approval BVS 12.0055X
Approved for Ex nA [ic] IIC T4 Gc
General information
System information The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Assembly

Front view
Assembly

Company logo

Documents / Resources

Pepperl Fuchs LB3005A2 HART Transmitter Power Supply Input Isolator [pdf] Instruction Manual
LB3005A2, 254700, LB3005A2 HART Transmitter Power Supply Input Isolator, HART Transmitter Power Supply Input Isolator, Power Supply Input Isolator, Input Isolator

References

Leave a comment

Your email address will not be published. Required fields are marked *